DESIGN DATA
Existing System
Design Flow = 330 GPD
P#2017-160
Proposed Single Family
- 2 Bedroom @ 110 GPD
No Garbage Grinder
1 Bedroom Reserved For Future Use
Total Daily Flow = 330 GPD
SEPTIC TANK
330 GPD X 200% = 660 Gallons
Existing 1500 Gal
2 Compartment Septic Tank
LEACHING AREA
330 GPD / 0.74 (LTAR) = 446 SF Required
Existing 15' X 30' Bed = 450 SF (333 GPD)
LEACHING AREA DESIGN
All Pipes Schedule 40 With Ends Vented.
3 - 4"Ø Distribution Lines in a
15' x 30' Double Washed Stone Field as Shown.
SEPTIC NOTES
1. Location of Utilities Shown on This Plan Are Approx. At Least 72 Hours
Prior to Any Excavation For This Project the Contractor Shall Make
the Required Notification to Dig Safe (1-888-344-7233) and contact
Sullivan Engineering & Consulting Inc. (508-428-3344).
2. The Contractor is Required to Secure Appropriate Permits From Town
Agencies For Construction Defined by This Plan.
3. Wherever Sewer Lines Must Cross Water Supply Lines Both Lines Shall
Be Constructed of Class 150 Pressure Pipe and Shall be Water Tested to
Assure Watertightness. In General, Water Lines Shall be Constructed in
Coordination With COMM Water, and Shall be in Accordance
With 248 CMR 1.00 - 7.00 & 310 CMR 15.00.
4. A Minimum of 9" of Cover is Required for All Components.
5. All Structures Buried Three Feet or More or Subject
to Vehicular Traffic to be H-20 Loading. It is the Engineer's
Recommendation that H-20 Always be Used.
6. Install Watertight Risers and Covers to Within 6" of Finished Grade
Over Septic Tank Inlet and Outlet, D-Box, and One Leaching Chamber.
All covers are to be maximum 18" for concrete or 24" Cast Iron.
7. Septic System to be Installed in Accordance With 310 CMR 15.00 &
248 CMR 1.00 - 7.00 Latest Revision and the Town of Barnstable
Board of Health Regulations.
8. All Piping to be Sch. 40 PVC.
9. D-Box Shall Have a Minimum Inside Dimension of 12", and a Minimum
Sump of 6".
10. The Separation Distance Between the Septic Tank Inlets and
Outlets Shall be No Less than the Liquid Depth. Inlet Tees Shall Extend
a Minimum of 10" Below the Flow Line. Outlet Tees Shall Extend 14"
Below the Flow Line, and Shall be Equipped With a Gas Baffle.Osterville - West Barnstable RoadLocus