TOWN OF BARNSTABLE ZONING BOARD OF APPEALS
SUPPLEMENTAL PRE-HEARING SUBMISSION PACKET — APPEAL NO. 2026-014
Appellant: Premier Capital, LLC (200 North Street, Hyannis, MA)
Subject Property: 210 North Street, Hyannis, MA
Hearing Date: November 18, 2026
To the Members of the Barnstable Zoning Board of Appeals:
Premier Capital, LLC. respectfully submits this Supplemental Pre-Hearing Statement in further
support of Appeal No. 2026-014.
A. Transmittal of Expert Report of Christopher S. Downey, PE
Accompanying this submission is the independent forensic engineering report prepared
by Christopher S. Downey, PE (Massachusetts Professional Engineer License No. 46258). Mr.
Downey was retained to perform an engineering and zoning analysis of the newly constructed
four-story, 18-unit residential apartment building located at 210 North Street.
Mr. Downey’s report evaluates the construction drawings, site plans, permitting history,
and physical build. His professional findings substantiate that the as-built structure directly
violates core dimensional and density mandates of the Town of Barnstable Zoning Ordinance,
was constructed substantially outside the authorized permit scope, and fails to qualify as an "as-
of-right" expansion of a preexisting nonconforming structure. A true copy of this report is
attached herewith as Exhibit A.
Mr. Downey’s findings are summarized as follows:
1. Forfeiture of "As-of-Right" Nonconforming Expansion (§ 240-93):
Page 2 of 5
November 17, 2026
Mr. Downey’s forensic review of the structural demolition and construction plans
revealed that the developer completely demolished the roof, the front wall and foundation, and
the rear wall and foundation. While the developer left portions of the ground-floor east and west
masonry side walls, Mr. Downey determined that these remaining masonry walls were non-load-
bearing, have been entirely bypassed structurally by new interior wood-framed walls and helical
piles, and are completely covered in exterior finishes. They serve neither an aesthetic nor a
structural function. Mr. Downey concluded that such near-total superstructure demolition
constitutes voluntary teardown rather than an "alteration" or "expansion" under § 240-93,
voluntarily forfeiting any "as-of-right" grandfathered protections and legally mandating a formal
Special Permit and Site Plan Review.
2. Unlawful Expansion of Building Footprint (Breach of Permit Condition BLDC-24-
138):
Building Permit BLDC-24-138 explicitly authorized work strictly on the "existing
footprint." Comparing the 1983 Southland 7-Eleven foundation plans against the as-built
conditions, Mr. Downey confirmed that the original building had an unenclosed, 6-foot
trapezoidal front overhang canopy that was never part of the original building footprint. The
developer poured a new front foundation directly beneath this overhang and enclosed it into
heated residential interior space, expanding the ground-floor footprint in direct violation of the
express permit terms and the developer’s own certified permit representations.
3. Prohibition on 4 Stories & Disregard of Height Limits (§ 240-24.1.7, Table 4 & §
240-24.1.5-A.4(b)):
Table 4 of the Ordinance (DV Dimensional Standards) limits building height to a
maximum of 3 stories and 40 feet. The building as permitted and constructed is 4 stories and
approximately 60 feet tall. Even if a 4th story could be considered under § 240-24.1.7-C.4, the
ordinance mandates an 8-foot step-back/recess, which was completely omitted, resulting in an
unlawful 60-foot vertical sheer wall looming directly over the shared eastern boundary.
4. Misrepresentation of Gross Floor Area & Volume to Circumvent Oversight:
Mr. Downey verified that the permit application represented the project as 3,476 square
feet of enclosed floor area and under 35,000 cubic feet of volume. In reality, the building was
constructed to 11,451+ square feet and over 100,000 cubic feet (more than triple what was
certified on the application). This gross discrepancy improperly bypassed mandatory
Construction Control and formal Site Plan Review.
5. Deficient Parking Disqualifying By-Right Approval (§ 240-24.1.5C, Table 2):
Mr. Downey noted that current zoning requires 1.5 spaces per dwelling unit (27 spaces
for 18 units). Because the developer must be ordered to re-permit and undergo Special Permit /
Site Plan Review due to the forfeiture of nonconforming rights and dimensional violations, the
project cannot satisfy parking requirements on its constrained ~77.5% lot coverage without
front-yard parking spaces prohibited under § 240-24.1.5C3(b).
Page 3 of 5
November 17, 2026
6. Concrete Particularized Abutter Harm (Standing):
In addition to spatial crowding, loss of light/air, and parking overflow onto Premier's lot 1,
Mr. Downey documented that mechanical exhaust outlets discharging on the east side wall
terminate within one foot of Premier's boundary line, further demonstrating localized physical
impacts directly abutting Premier's property.
B. Zoning Ordinance Violations Table
Zoning
Metric &
Citation
DV District
Requirement
210 North St. Actual
Build
Downey Report
Finding & Section
ZBA Status
Existing
Footprint
Condition
(Permit
BLDC-24-
138; § 240-
24.1.3C(2); §
240-93)
Strictly on existing
footprint; no increase
in nonconformity
New front foundation
poured beneath front
canopy; enclosure of
canopy into interior
space
Section D.2.d (p.
12): Confirms front
entrance overhang
was not enclosed
footprint; enclosure
constitutes unlawful
footprint expansion
violating permit.
VIOLATION
As-of-Right
Expansion vs.
Demolition
(§ 240-93)
Alteration/expansion
permitted only without
intensifying
nonconformity
Complete demolition
of roof, front, and
rear
walls/foundations;
side walls structurally
bypassed
Section D.2.c (pp.
10–11): Near-total
demolition forfeits
as-of-right status;
side walls bypassed
by inner wood frame
and helical piles.
Special Permit
required.
VIOLATION
1 As the direct abutter at 200 North Street, Premier Capital suffers concrete, particularized harm
directly traceable to these zoning violations:
a. Massing and Encroachment: A ~60 -foot sheer wall with zero step-back erected inches
from the shared property line creates oppressive massing, blocks light and air, and prevents
proper exterior building maintenance without trespassing onto Premier's property.
b. Traffic and Parking Overburden: Siting an 18-unit residential complex without compliant,
lawful parking or functional internal turnaround circulation pushes commercial and residential
vehicle overflow directly onto Premier's abutting lot. Further, within the 33-foot shared
passageway, 210 North’s 19-foot perpendicular stalls leave only 14 feet of clear aisle width. This
contradicts 210 North’s owner Mr. Maia’s sworn admission before the Land Court that his 18-
unit building requires an open corridor exceeding 24 feet for two-way passing and turning,
thereby guaranteeing spillover onto 200 North Street.
Page 4 of 5
November 17, 2026
Maximum
Stories &
Height
(§ 240-24.1.7,
Table 4; §
240-24.1.5-
A.4(b))
3 stories max;
40 feet max height
4 stories constructed;
~60 feet height (to
gable peak)
Section D.1.a &
D.1.b (p. 8): Table 4
limits structure to 3
stories and 40 ft.
Exceeds height by
~20 ft; 4 stories
expressly
unauthorized.
VIOLATION
Fourth-Story
Step-Back
(§ 240-24.1.7-
C.4)
Mandatory 8-foot
recess/step-back on 4th
story
0-foot step-back;
sheer 4-story vertical
wall
Section D.1.c (p. 8):
Confirms complete
absence of the
mandatory 8-foot
step-back on the 4th
floor.
VIOLATION
Gross Floor
Area /
Volume
(Permit
Application &
§ 240-
24.1.3B)
Threshold review
based on true scale
11,451+ sq. ft.;
>100,000 cu. ft. (vs.
3,476 sq. ft. / <35,000
cu. ft. claimed)
Section D.2.e (p.
14): Actual build is
>3x permit
application metrics,
improperly evading
regulatory controls.
VIOLATION
Parking &
Frontage
Buffer
(§ 240-
24.1.5C, Table
2 & § 240-
24.1.5C3(b))
18 spaces required (at
permit); 27 spaces
(under Table 2 re-
permitting)
20 spaces claimed;
relies on prohibited
front-yard parking
Section D.1.d (p.
9): Non-compliant
upon required re-
permitting; cannot
meet current 1.5
spaces/unit ratio.
VIOLATION
C. Additional Documents
Premier has likewise submitted the following additional documents in support of its
appeal:
1. LoopNet Commercial Listing for 210 North Street. This document is attached herewith
as Exhibit B.
2. 4-Story Wall, Façade Overhang and Pre-Construction 7-Eleven photographs. These
photographs are attached collectively as Exhibit C.
Page 5 of 5
November 17, 2026
Respectfully Submitted,
PREMIER CAPITAL, LLC., Appellant
By Its Attorney
/s/RICHARD B. REILING
RICHARD B. REILING BBO#629203
BOTTONE I REILING
63 Atlantic Ave., 3rd FL
Boston, MA 02110
P:617 412 4291
F: 617 412 4406
E: richard@bottonereiling.com
c: Charles M. Sabatt, Esq.
Brian Florence
EXHIBIT A
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 1
November 16, 2026
Prepared for:
Bottone | Reiling
63 Atlantic Avenue, 3rd Floor
Boston, MA 02110
Attention: Richard B. Reiling, Esq.
VIA E-MAIL: richard@bottonereiling.com
EXPERT REPORT
RE: 210 North Street
Hyannis, Massachusetts
Barnstable County
Aperture Project No.: C002650
Mr. Reiling,
On September 15, 2026, Bottone | Reiling (“Counsel”) engaged Aperture Consultants
CCA, LLC (“Aperture”), formerly CCA Construction Associates, LLC, on behalf of Premier
Capital (“Premier”).
Premier owns the property at 200 North Street in Hyannis, Massachusetts, which abuts
210 North Street. The property at 210 North Street is owned by 210 North St., LLC, and
is the site of a recently constructed, approximately four-story, 18-unit apartment building
(the “Project”). The Project was constructed by Starbuck Construction Services, Inc.
(“Starbuck”).
Hyannis is a Village within the Town of Barnstable. A Certificate of Occupancy was issued
by the Town of Barnstable on October 8, 2026.
Aperture was asked to provide opinions regarding the design and construction of the
Project based on review of available information and documentation, and in consideration
of applicable building code requirements, applicable zoning requirements, the adequacy
of the structural design and construction, and any other concerns identified by Aperture.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 2
A. ABSTRACT
This expert report is based on information and documentation provided by Counsel and
our independent investigation to date. Aperture reserves the right to modify or change its
observations, opinions, and conclusions at any future time if additional information
becomes available and as our investigation continues.
Based on our investigation to date, there are serious concerns and violations with the as-
constructed building at the Project. These concerns and violations relate to local zoning
ordinances; existing nonconformities; the permitting process; applicable building code
requirements; structural design; and construction record-keeping, testing, and inspection.
As detailed in Section D, below, the concerns associated with the as-constructed
building include, but are not limited to:
Town of Barnstable Chapter 240 Zoning Ordinance (the “Ordinance”):
• Number of Stories. As permitted and constructed, the new four-story building
exceeds the maximum number of stories allowed per Ordinance Table 4.
• Building Height. As permitted and constructed, the new approximately 60-foot tall
building exceeds the maximum total height allowed per Ordinance section 240-
24.1.5-A.4(b).
• Fourth Floor Setback. In the event that construction of a fourth story was
approved, as constructed, the new building does not include the fourth-floor step-
back required by Ordinance section 240-24.1.7-C.4.
• Parking Spaces. While the number of accessory parking spaces provided meets
the Ordinance at the time of permitting, the number of parking spaces does not
meet the current minimum required by Ordinance Table 2.
Existing Nonconformities and the Permitting Process:
• Nonconforming Building. Based on existing primary and secondary setbacks, and
secondary ground floor fenestrations, the existing building was nonconforming
according to the requirements of Ordinance Section 240-24.1.7 and Table 4.
• As-of-Right Expansion. Due to substantial voluntary demolition of the existing
building, the “As of right” ability to expand upon the existing nonconforming
building, as allowed by Ordinance section 240-93, may have been forfeited.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 3
• Special Permit Process. If the “As of right” ability to expand upon the existing
building was forfeited, the construction of a new building on the lot with the same
nonconformities as the original building would have required a Special Permit
process.
• Building Footprint. The footprint of the new building was expanded in comparison
to the original building due to the enclosure of the front entrance roof overhang
area. This is inconsistent with the approved building permit application which
indicated in two sections that the building footprint would not be increased.
• Building Area and Volume. The permit application erroneously indicated that the
new four-story building was to include 3,476 square feet of enclosed floor area,
and that the total volume of the enclosed space was to be less than 35,000 cubic
feet. The actual constructed floor area and building volume were more than three
times those quantities.
Applicable Building Code Requirements:
• Mechanical Exhaust. The termination points of exhaust outlets on the east side
wall are too close to the shared property line, in violation of section 501.3.1 of the
Massachusetts Mechanical Code 2015.
• Footing Frost Depth. According to the original drawings, the bottoms of the
remaining side wall foundations are not at the required four-foot frost depth, in
violation of Section 1809.5 of the Massachusetts State Building Code and there is
no evidence that a substantiating alternate method was submitted to the Building
Official for approval.
Structural Design:
• Unreinforced Existing Masonry Foundation Walls and Concrete Footings. As
detailed and noted on the original structural drawings, the existing masonry
foundation walls are very lightly reinforced and the existing concrete wall footings
were possibly unreinforced, depending on the soil type encountered during original
construction. Based on the documentation provided, and without confirmation that
the footings are reinforced, the remaining foundation walls and footings at the side
walls are not structurally capable of spanning across the tops of the new helical
piles.
• Interior Basement Retaining Walls. As detailed on the structural drawings, the new
interior basement walls, which retain unbalanced lateral soil loads, are significantly
under-reinforced and structurally inadequate.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 4
Construction Record-Keeping, Testing, and Inspection:
• Helical Pile Installation Records. It is our understanding that no installation records
are available for the new helical piles that were installed to support the remaining
east and west foundation walls. If none of the required installation records exist,
and the required testing and inspection was not performed, this is a violation of the
building code, and the structural capacity of the installed piles, and thus the safety
of the building, is unknown.
B. PROPERTY AND PROJECT BACKGROUND
The property at 210 North Street, Hyannis (the “Property”) is located within the Town of
Barnstable in Barnstable County, Massachusetts. According to the Town of Barnstable
Zoning Ordinance and related Zoning Map, the Property, located at the corner of North
Street and Bassett Lane, is situated within the Downtown Village (“DV”) district (Figures
A and B).
A 7-Eleven convenience store was located on the Property until approximately 2023.
According to existing drawings dated May 18, 1983, the original building was developed
for The Southland Corporation, Northeast Division, and contained approximately 2,500
square feet of interior space.
The original one-story structure consisted of masonry exterior walls supported by
masonry foundation walls on concrete strip footings (Figure C). The roof structure
consisted of wood-framed trusses spanning between the front and rear walls. The
exterior masonry side walls were non-load-bearing (Figure D). A six-foot wide trapezoidal
roof overhang provided weather protection above the main front entrance; however, this
area was not enclosed and was not part of the building footprint.
According to Building Permit No. BLDC-24-138, issued by the Town of Barnstable on
September 12, 2024, the Project scope was to “Remove roof from existing one story
building then add new floors on the exiting footprint. 18 Units.” The building code in effect
at the time of permit issuance was the Ninth Edition of the Massachusetts State Building
Code (“MSBC” or “780 CMR”) which is based on the 2015 International Building Code
(“IBC”) with Massachusetts Amendments. It is our understanding that a Special Permit
process was not required by the Town in relation to issuance of the Permit.
According to the Town of Barnstable building permit application record, the Project was
an “Addition/Alteration” that changed the use of the building from Use Group B (“Office,
Professional, or Service Type Transactions”) to Use Group R-2 (“Multi Family”).
According to Drawing A-1 dated January 21, 2025, the new four-story building was to
include 11,451 square feet of enclosed floor area, with a total volume greater than
100,000 cubic feet.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 5
According to drawings reviewed, the Architect-of-Record for the Project was Lewis
Colton, AIA, and the Architectural Drawings were produced by Soulveplus Construction
Services of Hyannis. The Structural Engineer was BuildOne Engineering Design of
Leominster, Massachusetts.
Figure A – Google Earth overhead image of the Property from June 13, 2026.
Figure B – Google Earth overhead image of the Property from October 21, 2024.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 6
Figure C – Floor Plan (Drawing A-1) from May 18, 1983, drawings.
Figure D – Roof Framing Plan (Drawing S-1) from May 18, 1983, drawings.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 7
C. APERTURE INVESTIGATION
As part of our investigation to date, Aperture reviewed and considered documents
provided by Counsel, including:
• Proposed architectural plans by Soulveplus, Drawing A-1, dated January 21,
2025.
• Proposed architectural wall section by Soulveplus, Drawing CD-W--1, dated June
20, 2025.
• Proposed Site Plan (three drawings) by Pesce Engineering & Associates, Inc.,
revision date June 12, 2025.
• Structural drawings (10 sheets) by BuildOne Engineering Design, revision date
June 30, 2025.
• ‘210 North Street - WALL LAYOUT_08-31-2025.pdf’
• Cover Sheet drawing A1, dated September 19, 2025.
• Deposition Testimony of Robert Maia, Jr. on behalf of Starbuck on April 20, 2026.
• Schematic Demolition Plans by Soulveplus, Drawing A900, dated June 20, 2025.
• Schematic Demolition Plans by Soulveplus, Drawing A900, file named July 3,
2025.
• Existing Conditions Plan by E.A.S. Survey, Inc., dated January 8, 2024.
• Permit Set (37 drawings) by Soulveplus, file named Rev6 April 14, 2025, sealed
and signed by Architect, Lewis Colton, AIA.
• ‘Photos_toExpert.docx’.
• Starbuck daily logs (‘Ex 21-Daily Log.pdf’).
• Proposed Site Plan (three drawings) by Pesce Engineering & Associates, Inc.
three sheets, revision date August 4, 2025 (‘Ex23-Agreed.pdf’).
• The Southland Corporation construction drawings dated May 18, 1983.
Codes, Standards, and Publications
Aperture relied upon applicable versions of the following codes, standards, publications,
and publicly available information, including:
• Massachusetts State Building Code, Seventh through Tenth Editions.
• 2015 International Building Code (“IBC”).
• American Society of Civil Engineers (“ASCE”) Standards 7-10 and 7-05,
Minimum Design Loads for Buildings and Other Structures.
• 2015 Massachusetts Mechanical Code.
• Building Code Requirements for Structural Concrete (ACI 318) and Commentary
(ACI 318R).
• Building Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS
402).
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 8
• Specification for Masonry Structures (ACI 530.1/ASCE 6/TMS 602).
• Town of Barnstable Section 240 Zoning Ordinance.
• Town of Barnstable Zoning Map.
• Publicly available online building permit information for the Town of Barnstable.
Aperture’s expert is Christopher S. Downey, PE, and his curriculum vitae (“CV”) is
attached as Exhibit A.
D. APERTURE FINDINGS
Aperture’s investigation to date identified the following concerns with the as-constructed
building at the Property. These concerns relate to local zoning ordinances; existing
nonconformities; the permitting process; applicable building code requirements; structural
design; and construction record-keeping, testing, and inspection.
1. Town of Barnstable Chapter 240 Zoning Ordinance (the “Ordinance”)
a. Maximum Building Stories:
Table 4 “DV Dimensional Standards” of the Ordinance for the Downtown
Village District limits the maximum building height to three stories maximum
(dimension ‘E’). Four stories were permitted and constructed.
b. Maximum Building Height:
Table 4 of the Ordinance limits the building height to 40 feet maximum
(dimension ‘F’). The building was permitted and constructed to approximately
60 feet in overall height. According to Section 240-24.1.5-A.4(b) of the
Ordinance, building height in the Downtown Village District is measured to the
highest point of the roof and includes Figure 1 which clarifies that the highest
point would be the peak of a gable roof (Figure E).
c. Required Fourth-Floor Setback:
Section 240-24.1.7-C.4 of the Ordinance regarding district DV states that “The
fourth story of any building must be recessed (‘stepped back’) from the…stories
below at least eight feet.” While this seems to conflict with Table 4 which
entirely prohibits four stories, it requires any permitted fourth floor to be stepped
back eight feet from the floors below. The permitted and constructed building
does not provide such a step-back at the fourth floor.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 9
d. Minimum Parking:
Table 2 of the Ordinance currently requires 1.5 accessory parking spaces for
each dwelling unit (“DU”) in the Downtown Village District. This requirement
was recently amended and increased from one accessory parking space per
unit.
It is our understanding that 18 dwelling units were constructed in the building
and, according to the Town of Barnstable Site Plan Review SPR-23-74, 20
parking spaces were provided.
While the provided number of accessory parking spaces met the Ordinance at
the time of permitting, the provided number of parking spaces does not meet
the current minimum required by the Ordinance, which would have required 27
parking spaces for 18 units.
If the Project was required to be re-permitted, or to go through a Special Permit
process, as a result of current Zoning Hearings related to the Project, then the
Project would not meet the current minimum parking requirements.
Figure E – Figure 1 from Section 240-24.1.5-A.4(b) of the Ordinance.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 10
2. Existing Nonconformities and the Permitting Process
a. Existing Nonconforming Structure:
According to the Ordinance, the existing building was a nonconforming
structure for several reasons, including but not limited to:
i. The primary setback (North Street) exceeds the maximum limit of 15
feet.
ii. The secondary setback (Bassett Lane) exceeds the maximum limit of
15 feet.
iii. The secondary ground floor fenestrations (e.g. window and door
openings) are less than the minimum 15 percent requirement.
b. As-of-Right Expansion:
Section 240-93 of the Ordinance, “As of right”, allows “alteration and expansion
of a preexisting nonconforming building or structure…provided that the
alteration or expansion does not increase or intensify the degree of the
preexisting nonconformity…”
c. Substantial Demolition:
Based on the extent of demolition to the original building, the “as of right” ability
to expand upon the nonconforming building may have been voluntarily
forfeited:
i. The existing roof structure was entirely demolished.
ii. The front (south) and rear (north) walls and their foundations were
entirely demolished.
iii. The east and west side walls and their foundations were the only
existing building elements that remained; however, they required
supplementation to support the additional loads. New helical piles
were installed below the existing side wall footings to support the
additional loads imposed by the new four-story building. In addition,
new wood-framed walls were constructed immediately adjacent to the
inside face of the existing masonry walls, in an apparent attempt to
avoid loading the existing walls (Figure F).
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 11
iv. Complete demolition of the superstructure would not be considered an
“alteration” or “expansion” in accordance with Section 240-93 of the
Ordinance, and it seems that the existing ground floor masonry side
walls were preserved solely in an attempt to maintain classification as
an “expansion” of the existing building. The existing masonry side
walls were non-load-bearing exterior walls. The remaining masonry
walls have been entirely bypassed in terms of the structural load path
for the new four-story building, and the exterior faces of the remaining
masonry walls have been entirely covered with new finishes, and
therefore, serve neither a structural nor aesthetic purpose (Figure G).
v. With the “as of right” ability to expand upon the existing building
forfeited, the construction of a new building on the lot with the same
nonconformities as the original building would have required a Special
Permit process, which would include notifying abutting and affected
neighbors, and related public hearings. The building was permitted,
and a Certificate of Occupancy issued, without a Special Permit.
Figure F – Photo showing new wood-framed wall constructed immediately adjacent
to existing remaining masonry side wall.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 12
Figure G – Photo of remaining masonry side wall completely covered with finishes.
d. Building Footprint Expanded:
A six-foot wide trapezoidal roof overhang provided weather protection at the
main front entrance of the original 7-11 store; however, this area was not
enclosed and was not part of the existing building footprint (Figure H).
The footprint of the new building was expanded in comparison to the existing
building due to the enclosure of this front entrance roof overhang area (Figure
J).
This is inconsistent with the approved building permit application which
indicated in two sections that the building footprint would not be increased.
The building permit application indicated that the Project would not change the
footprint of the structure (Question: “Does this proposal change the footprint of
the Structure?” Answer: “No”). In addition, the work description in the
application was to “Remove roof from existing one story building then add new
floors on the existing footprint.” [Underlining added by Aperture for emphasis.]
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 13
Figure H – Photo showing unenclosed roof overhang at front entrance of 7-11.
Figure J – Photo showing expanded building footprint at original roof overhang.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 14
e. Building Area and Volume:
The building permit application erroneously indicated that the new four-story
building contained 3,476 square feet of enclosed floor area, and the total
volume of the enclosed space was less than 35,000 cubic feet.
According to Drawing A-1, dated January 21, 2025, the new four-story building
actually includes 11,451 square feet of enclosed floor area, with a total volume
greater than 100,000 cubic feet.
The actual constructed floor area and building volume were more than three
times the quantities indicated in the building permit application.
Section 107.6.1 ‘Construction Control’ lists structures which are exempt from
Construction Control by a registered design professional. The first exception
exempts buildings containing less than 35,000 cubic feet of enclosed space.
By erroneously indicating that the building would contain less than 35,000 cubic
feet in the permit application, the requirements for Construction Control were
avoided.
3. Applicable Building Code Requirements
a. Mechanical Exhaust:
According to Section 501.3.1 of the Massachusetts Mechanical Code 2015, the
termination points of exhaust outlets and ducts discharging “environmental air”
to the outdoors shall be located a minimum of three feet from property lines.
Other types of exhaust, such as “product-conveying outlets” and “explosive or
flammable vapors, fumes or dusts” shall be located a minimum of 10 feet and
30 feet from property lines, respectively.
Based on photos reviewed, the as-constructed new building includes exhaust
outlets on the east wall which are located within one foot of the shared property
line between 210 and 200 North Street (Figure K). These outlets appear to be
“environmental air” exhausts and are in violation of the building code.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 15
Figure K – Photo showing building exhaust vents on wall along shared property line.
b. Frost Depth:
According to Section 1809.5 of 780 CMR, the bottoms of shallow building
foundations shall be located below the frost line, with certain exceptions. The
frost line is currently established as four feet below grade for all of
Massachusetts. According to the 1983 drawings for the original one-story
structure, the bottoms of footings were specified to be a minimum of either 3
feet (Note 12 on Sheet F-1) or 3.5 feet (Section 2 on F-1) below grade (Figures
L and M). Although these requirements conflict with each other, neither is in
conformance with current code requirements. There is no evidence that the
existing footings meet any exceptions to the code requirement, that the Building
Official approved the condition, or that the existing remaining footings at the
side walls were underpinned to provide the required frost depth. According to
the drawings, the bottoms of existing footings would have been at least partially
excavated and exposed to install the specified helical pile brackets, which
would have provided an opportunity to evaluate and underpin the footings as
required.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 16
Figure L – Note 12 on original Drawing F-1 indicating three-foot frost depth.
Figure M – Section on original Drawing F-1 indicating 3.5-foot frost depth and no
vertical CMU reinforcing.
4. Structural Design Deficiencies
a. Unreinforced Masonry Foundation Walls and Concrete Footings:
As detailed on the Project structural drawings, the remaining side wall
foundations were supplemented with new helical piles. Per drawing FO-100,
the piles were to be installed under the existing wall footings and spaced at 6’-
10” (six foot, ten inches) on center, maximum. As a result, the remaining
concrete masonry (“CMU”) foundations walls and/or the remaining concrete
wall footings are required to span horizontally between their supporting helical
piles.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 17
Per Note 3 on the original Drawing F-1, the specified reinforcing steel (“rebar”)
in the footing could be omitted if the allowable soil bearing pressure was
determined to be greater than 2,500 pounds per square foot (“psf”) (Figure N).
Without scanning the footing to determine the existence of rebar, a prudent
structural engineer would have to assume that no reinforcing is present in the
footings. ACI 318, Building Code Requirements for Structural Concrete, does
not permit the use of unreinforced concrete on piles, so the existing footing
cannot be relied upon to span between the piles, leaving the remaining CMU
wall as the only element possibly able to span across the piles.
Figure N – Note 3 on Drawing F-1 indicating that footing reinforcing may be omitted.
As specified on the structural drawings, the existing CMU walls were not
reinforced vertically. Note 11 on the original Drawing F-1 specified horizontal
reinforcement as “Dur-o-Wal” truss type joint reinforcement to be located at
every other course below finish floor (Figure P). Dur-o-Wal joint reinforcement
typically contains two continuous smooth steel wires, designated as W1.7 with
a diameter of 0.148-inch and an area of 0.017 square inches each. Based on
the geometry and construction of the side foundation wall as shown in Section
2 on F-1, only one joint would be expected to be reinforced. Furthermore, since
the CMU contains no vertical reinforcing and the code does not permit any axial
tension to be resisted by unreinforced masonry, only the CMU courses below
the ground floor slab could be assumed to support the new wood walls which
were constructed on the inside of the existing masonry side walls.
Based on the undersigned’s structural analysis, it is determined that the
capacity of the masonry foundation walls with the specified joint reinforcing is
not capable of spanning across the piles to support the self-weight of the new
wood-framed exterior side walls by code without supplemental reinforcing.
There is no evidence that the masonry foundation walls were reinforced during
the Project.
Figure P – Note 11 on Drawing F-1 indicating Dur-o-Wal reinforcing for CMU.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 18
b. Interior Basement Retaining Walls:
The new building includes a new partial basement as shown and detailed on
structural drawings FO-100 and FO-101. The new basement foundation is set
approximately 5 to 10 feet inboard of the exterior perimeter foundations (Figure
Q). The new basement walls support portions of the new first-floor framing and
resist lateral soil loads due to approximately 9 feet of unbalanced retained soil
(Figure R).
The lightly reinforced 10-inch thick concrete basement walls include #4 (half-
inch diameter) vertical rebar, located in the middle of the wall thickness, and
spaced at 36 inches on center. The walls act as “propped” retaining walls to
resist lateral soil loads, meaning that the wall is laterally braced by both the
basement slab-on-grade (bottom) and the first-floor structure (top).
The undersigned performed calculations to analyze the lateral soil loads on the
basement walls and determined that they are not structurally capable of
supporting the required loads.
Figure Q – Foundation/Basement Plan on Drawing FO-100 showing basement walls
set in from exterior walls.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 19
By comparison, and as a way of substantiating this finding, the undersigned
reviewed the Massachusetts Residential Code, which is not applicable to this
building, but provides prescriptive designs for similar foundations walls
retaining unbalanced soil. Per Table R404.1.2(4) of the Residential Code, the
same wall design would require #6 rebar at 37 inches on center, at a minimum,
which is more than double the wall reinforcing specified for the Project.
Depending on the soil type, it is possible that #6 rebar at 24 inches would be
required prescriptively, which is more than triple that specified for the Project
(Figure S).
Figure R – Section 3 on Drawing FO-101 showing lightly reinforced basement walls.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 20
Figure S – Excerpt from residential code Table R404.1.2(4) showing minimum
basement wall reinforcing for various soil types. [Highlighting added by Aperture]
5. Construction Record-Keeping, Testing, and Inspection
a. Helical Pile Installation Records:
It is our understanding that no installation records are available for the new
helical piles installed to support the original foundation walls that remained on
the east and west elevations.
Section 107.6 of 780 CMR requires Construction Control and Special
Inspections to be performed by Registered Design Professionals for all
buildings and structures except those specifically exempt per Section 107.6.1.
The Project at 210 North Street does not meet any of the listed exemptions to
this requirement.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 21
According to Section 1810.4.12 of 780 CMR, Special Inspections of helical piles
are required in accordance with Sections 1705.7, 1705.8, and 1705.9.
In particular, Section 1705.9 requires “Continuous special inspections…during
installation of helical pile foundations. The information recorded shall include
installation equipment used, pile dimensions, tip elevations, final depth, final
installation torque and other pertinent installation data as required by the
registered design professional in responsible charge. The approved
geotechnical report and the construction documents prepared by the registered
design professional shall be used to determine compliance.”
Structural drawing FO-101 (revision date November 5, 2024) for the Project
contains “Helical Pile Notes” which provide specific detailed requirements
regarding pile installation, monitoring, record-keeping, field load testing,
inspections, and submittals.
According to deposition testimony of Roberto Maia, Jr., provided April 20, 2026,
on behalf of the general contractor, Starbuck, he stated that “Nobody had to
certify the foundation on our side” (page 119) and that the Town of Barnstable
was responsible for making sure the foundation was constructed in accordance
with the plans (page 120). These statements are not consistent with the
requirements of the building code nor the structural drawings.
If none of the required installation records exist, and the required testing and
inspection was not performed, this is a violation of the building code, and the
capacity of the installed piles, and thus the safety of the building, is unknown.
E. CONCLUSION
Based on my investigation to date, and as detailed in Section D of this report, it is my
opinion that the building should not have been permitted without a Special Permit process
since the proposed building did not comply with several local ordinances; that the “as of
right” ability to expand upon the nonconforming building was likely forfeited due to the
extent of demolition; that the permit application contained inaccurate information, which
formed the basis for the permit approval; and that there are current structural concerns
and building code violations.
These findings and opinions are rendered within a reasonable degree of forensic
engineering certainty based on information available at this time, my investigation to date,
in concert with my experience, training, and education in the fields of engineering and
construction. I reserve the right to modify or change its observations, opinions, and
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulting & Engineering, P.C. 22
conclusions at any future time if additional information becomes available, and as our
investigation continues.
Please call if you have any questions, comments, or future requirements regarding this
matter.
Sincerely,
Christopher S. Downey, PE
Director of Engineering
Massachusetts License No. 46258
____________________________
Aperture Consultants CCA, LLC
10 Mall Road, Suite 150
Burlington, MA 01803
877-222-0665
Enclosures:
Exhibit A – Curriculum Vitae – Christopher S. Downey, PE
Exhibit B – 210 North New Building Structural Drawings
Exhibit C – Original Existing Building Drawings
Exhibit D – Select Aperture Structural Calculations
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulng & Engineering, P.C.
PRELIMINARY EXPERT REPORT
RE: 210 North Street
Hyannis, Massachusetts
Barnstable County
CCA Project No.: C002650
EXHIBIT A
Christopher S. Downey, PE
Curriculum Vitae
CHRISTOPHER S.
DOWNEY, P.E.
DIRECTOR OF ENGINEERING
10 MALL ROAD, SUITE 150 | BURLINGTON, MA 01803
OFFICE PHONE: 781.301.5221
CHRIS.DOWNEY@APERTURELLC.COM
EDUCATION
BS, Civil Engineering (Structural),
Rensselaer Polytechnic Institute,
1996
MS, Civil Engineering (Structural),
Rensselaer Polytechnic Institute,
1998
ACCREDITATIONS
Professional Engineer:
MA, NV (CE/SE), TX, CA (CE), FL,
NH, IL (SE), NC, TN, CT, WA (CE),
NY, DE, NJ, MI, PA, ME, SC, MD
CERTIFICATIONS
OSHA 10-Hour Construction Safety
and Health
Mr. Downey has been with Aperture (formerly CCA) since 2024 and has extensive
experience in civil, structural, and construction engineering.
Prior to joining Aperture, he spent over 25 years as a structural engineer in the design
and construction of building structures, utilizing all types of construction materials,
including traditional steel-framed, cast-in-place concrete, precast/prestressed
concrete, post-tensioned concrete, masonry, wood-framed, and various foundation
types.
Mr. Downey’s design and construction experience includes a wide range of project
types, including commercial and residential buildings, airport terminals, medical and
educational institutions, high-capacity parking facilities, and the renovation of existing
structures. He has been involved in the delivery of a multitude of projects as part of
true design-build partnerships.
In addition to the design of building structures, Mr. Downey has provided extensive
construction engineering support services for erectors, steel fabricators, concrete
precasters, and general contractors. Some examples include temporary shoring of
trusses and long-span plate girders during erection, evaluation of structures to support
construction loading and vehicles, foundation design for tower cranes, temporary
bridge structures, and evaluation of the stability of partially erected structures during
construction.
Since joining Aperture, in addition to providing engineering support for design projects,
Mr. Downey has primarily focused on construction defect claims, design professional
liability claims, evaluation of building envelopes and facades, property and structural
condition assessments, insurance claims, and litigation support.
Throughout his career, Mr. Downey has consistently built strong client relationships
based on responsiveness, integrity, and a practical, common-sense approach. He is
known for his ability to effectively communicate complex technical issues and deliver
innovative, value-driven solutions.
WORK EXPERIENCE
Aperture Consultants CCA, LLC (formerly CCA Construction Consultants, LLC),
Burlington, MA, May 2024 – Present, Director of Engineering
Simon Design Engineering, LLC, Wellesley, MA, September 2004 – May 2024
Senior Engineer
Hybrid Parking Solutions, Inc., Watertown, MA, October 2001 – September 2004
Project Manager
Zaldastani Associates, Inc., Boston, MA, April 1998 – October 2001
Project Engineer
The Whiting-Turner Contracting Co., Burlington, MA, May 1997– Aug 1997
Engineering Intern
Lake HVAC, Stoneham, MA, May 1996 – Aug 1996
Engineering Intern
Last revised: September 15, 2026
Christopher S. Downey, P.E.
PAGE 2 OF 6 CALIFORNIA | COLORADO | FLORIDA | TEXAS | MASSACHUSETTS |
MISSOURI NEVADA | NEW MEXICO | NEW YORK | WISCONSIN Last revised: September 15, 2026
REPRESENTATIVE PROJECT EXPERIENCE – PARTIAL LISTING
Structural Design Projects:
Dana-Farber Cancer Institute, Yawkey Center for Cancer Care, Boston, MA
Lead structural engineer and project manager for $350 million, 500,000 SF, 22-story
laboratory and research building with seven stories of below-grade parking.
Agnes Scott College, Mary Brown Bullock Science Center, Decatur, GA
Project manager and structural engineer for cast-in-place concrete science building
utilizing concrete moment frames to allow flexibility to re-configure the interior space.
University Square Parking Garage, University Heights, OH
Project manager for this 4,000-space parking structure utilizing a hybrid structural system
consisting of steel moment frames and precast, prestressed double-tee floor decks.
Christina Landing Parking Garage, Wilmington, DE
Project manager for 8-story parking structure which was built to accommodate an
adjacent 22-story residential building and included a rooftop community pool and deck.
Dana-Farber Cancer Center, Façade Inspections, Boston, MA
Performed façade inspections every five (5) years for the entire Dana-Farber campus in
accordance with the City of Boston Façade Ordinance.
10 Wyman Street Lofts, Jamaica Plain, MA
Structural engineer for this project to convert a historic brick schoolhouse into
condominiums.
Logan International Airport, Terminal B Renovation and Expansion, Boston, MA
Project manager for the Terminal B airport expansion, which included substantial
renovations and seismic upgrades, bringing the lateral-load-resisting system up to
current building code standards.
Logan International Airport, Terminal E Modernization, Boston, MA
Engineer-of-Record for the renovations of the existing international terminal at Logan
Airport as part of an $800 million modernization project.
EF Education First, North American Headquarters, Cambridge, MA
Project manager for 12-story, 300,000-square foot building, which included a 12-story
architectural glass “waterfall” consisting of a complex three-dimensional steel pipe space
frame truss.
Brigham & Women’s Hospital, Helipad Crash Deck, Boston, MA
Structural engineer for the design of a unique cable and netting system designed to
protect the existing newborn intensive care unit (NICU) from steel members that might
accidentally drop during the erection of the nearby helipad, allowing the NICU to remain
in continuous operation during construction.
Oak Row Apartments, West Roxbury, MA
Engineer-of-Record for podium building, which consisted of one level of steel-framed
parking with four (4) stories of traditional wood-framed construction above.
Edward Early Jr. Parking Facility, Lowell, MA
Led the design and detailing of both the architectural and structural components of this
total precast concrete parking garage, including drafting of the precast shop drawings.
Winooski Hotel, Winooski, VT
Project manager and structural engineer for new hotel which consisted of precast hollow-
core planks on proprietary steel D-Beams, also known as The Girder-Slab System.
Christopher S. Downey, P.E.
PAGE 3 OF 6 CALIFORNIA | COLORADO | FLORIDA | TEXAS | MASSACHUSETTS |
MISSOURI NEVADA | NEW MEXICO | NEW YORK | WISCONSIN Last revised: September 15, 2026
Construction Defect Claims Representing Defendant:
Iovanna v. S&S Construction, Marblehead, MA
Single-family home claims against General Contractor.
Tower 155 Condos v. 155 East Boca, Boca Raton, FL
Post-tensioned concrete installation claims involving 12-story 128-unit residential tower.
Avila and Bailey v. John Cannon Homes, Sarasota, FL
Single-family home claims against General Contractor.
Bradley Title v. Karam Brothers, Pompano Beach, FL
Single-family home claims against General Contractor.
Ozona Village v. Phoenix Construction, Palm Harbor, FL
Stucco and siding installation claims involving 13 residential duplexes.
Waterleigh Phase 2 v. Quality Lathe & Stucco, Winter Garden, FL
Townhome community stucco claims involving 41 buildings and 196 units.
Bexley Townhome Community v. Spazz Stucco, Land O'Lakes, FL
Stucco and siding installation claims involving 32 buildings and 98 units.
Bexley Townhome Community v Phoenix Construction, Land O'Lakes, FL
Stucco and siding installation claims involving 2 buildings and 10 units.
Woodside Trace v. Phoenix Construction, Wesley Chapel, FL
Townhome community stucco installation claims involving 7 buildings and 52 units.
Westshore Marina v. Phoenix Construction, Tampa, FL
Stucco and siding installation claims involving 5 townhome buildings and 35 units.
Elm Ridge v. Phoenix Construction, Riverview, FL
Townhome community stucco installation claims involving 23 buildings and 10 units.
Epperson North v. Phoenix Construction, Wesley Chapel, FL
Townhome community stucco installation claims involving 41 buildings and 214 units.
SMC Jax v. Live Oak v. Roof Depot, Jacksonville, FL
TPO roofing and siding installation claims involving two large 4-story wood-framed
apartment buildings with 486 total units.
Pulte v. Azteka d/b/a Atlantic Roofing, Kissimmee, FL
Asphalt shingle roofing installation claims involving 7 buildings and 52 units.
The Colonies Condos v. Valcourt, Winter Park, FL
Wood deck installation and waterproofing claims involving 55 unit balconies.
Konanec v. Millerick, Sherborne, MA
Single-family home claims against General Contractor.
Solterra Resort Homeowners v. Pulte, Davenport, FL
Townhome community stucco installation claims involving 22 buildings and 160 units.
Antonucci v. Rosewood Homes, Rockledge, FL
Single-family tile roofing and venting claims.
Ventanas I at Tiburon v. Valcourt, Naples, FL
Plaza and planter waterproofing and expansion joint claims.
Christopher S. Downey, P.E.
PAGE 4 OF 6 CALIFORNIA | COLORADO | FLORIDA | TEXAS | MASSACHUSETTS |
MISSOURI NEVADA | NEW MEXICO | NEW YORK | WISCONSIN Last revised: September 15, 2026
Terrace I at Lakewood v. Liske Enterprise, Lakewood Ranch, FL
Window installation claims involving two 4-story 30-unit buildings.
Westside Murano v. DR Horton, Kissimmee, FL
Asphalt shingle roofing installation claims involving 29 buildings and 158 units.
Sylvan Crossing v. Spazz Stucco, Lutz, FL
Stucco installation claims involving 30 buildings and 168 units.
Plymouth Harbor v. Valcourt, Sarasota, FL
Plaza waterproofing installation claims.
Blu Condos v. Coquina Isle, Fort Walton Beach, FL
Post-tensioned concrete installation claims involving 8-story 42-unit residential building.
DeLee v. Dream Finders Homes, Middleburg, FL
Single-family home stucco installation claims.
Royal Grand Condos v. Cherry Roofing, Davie, FL
Tile and TPO roofing installation claims involving 20 inter-connected buildings and 208
units.
Gentry and Krueger v Majic Mike's Door and Windows, Jacksonville, FL
Single family home window installation claims.
900 Place v. Depcor, Fort Lauderdale, FL
Construction defect claims against General Contractor.
4701 North Meridian v. Plaza Construction, Miami Beach, FL
Represented site contractor regarding construction defect claims against General
Contractor.
Aquazul Condos v. Valcourt Exterior, Lauderdale-by-the-Sea, FL
Defect claims regarding exterior waterproofing and restoration project.
Ramos v. Cayat, Miami, FL
Single-family home claims against General Contractor.
Construction Defect Claims Representing Plaintiff:
Portico at Perdido, Perdido Key, FL
Represented Plaintiff in condominium tower claims against Contractor and Developer.
Braewell Condominiums Parking Garage, Quincy, MA
On-going case regarding design and construction defects involving renovations to an
existing single-story parking deck.
Design Professional Standard of Care and Liability Claims:
BGNYAVE v. Advanced American Engineering, Huntington Station, NY
Review and assessment of structural engineer’s standard of care.
NY Marine v. Titan Engineers, New York, NY
Review and assessment of support of excavation (SOE) design and standard of care.
Merrimack v. JZN Engineering PC, New York, NY
Review and assessment of support of excavation (SOE) design and standard of care.
Christopher S. Downey, P.E.
PAGE 5 OF 6 CALIFORNIA | COLORADO | FLORIDA | TEXAS | MASSACHUSETTS |
MISSOURI NEVADA | NEW MEXICO | NEW YORK | WISCONSIN Last revised: September 15, 2026
Property and/or Structural Condition Assessments:
New Bridge Medical Center Tunnel Survey, Paramus, NY
Preliminary structural assessment of existing steam and access tunnels, involving
approximately 3,500 feet of tunnels that inter-connect the campus buildings.
Eldorado Condominium Garage, Worcester, MA
Structural investigation regarding observed distress in CMU walls of existing stand-
alone parking garage.
City Point Residences, South Boston, MA
Property condition assessment (PCA) and report for newly constructed residential
condominiums.
Atlantica Condominiums Parking Garage Leaks, Revere, MA
Investigation into on-going leaks into a below-grade parking garage located beneath a
multi-story residential apartment building.
Flintlock Village Condominiums, Wells, ME
Structural inspections of wood-framing in residential crawl spaces.
FMC Rink Roof Inspections, Various Locations
Structural inspections of existing wood-framed roof trusses at various skating rinks.
Harborside Condominiums, Scituate, MA
Evaluation of observed settlement of pavement and retaining wall.
144-146 Chester Avenue, Chelsea, MA
Assessment of existing 40-foot tall retaining wall on residential lot.
Insurance Claims:
Rumble Gym, Somerville, MA
Investigation regarding the collapse of a drop ceiling grid system.
70-64 Sea Street, Weymouth, MA
Evaluation of damage to building structure and storefront due to vehicular accident.
1676 Route 9, Stoddard, NH
Evaluation of water damaged wood flooring and repairs.
Jenni Carlson v USAA, Leicester, MA
Case involving alleged flood damage to a single-family residence.
Neighbor Access Agreements and/or Review of Support of Excavation or Underpinning:
650 and 651 Southern Boulevard, New York, NY
Review of access agreement and SOE for construction on neighboring property.
35 Central Park North, New York, NY
Review of access agreement and SOE for construction on neighboring property.
264-272 and 276 W 135th Street, New York, NY
Review of access agreement and SOE for construction on neighboring property.
885 Grand Street, Bronx, NY
Review of access agreement and SOE for construction on neighboring property.
Christopher S. Downey, P.E.
PAGE 6 OF 6 CALIFORNIA | COLORADO | FLORIDA | TEXAS | MASSACHUSETTS |
MISSOURI NEVADA | NEW MEXICO | NEW YORK | WISCONSIN Last revised: September 15, 2026
Litigation Support:
Voss v. Mobile Fencing, Somerville, MA
Personal injury case involving temporary construction fencing.
Express 7 Coin Laundry v. 6303 Miramar, Miramar, FL
Case involving damages due to alleged negligent replacement of existing roofs.
Rivera v. Holyoke High Street, Holyoke, MA
On-going case involving alleged damage to a neighboring property during demolition.
Toll v. Tocci, East Brunswick, NJ
Case involving the standard of care of the geotechnical engineer.
Trio Enterprises v. James O’Toole, Somerville, MA
Retaining wall dispute between neighboring property owners.
Cacciola v. Gobel, Watertown, MA
Retaining wall dispute between neighboring property owners.
Pimental v. Peal, Lakeville, MA
Real estate purchase dispute involving an existing failing septic tank.
Needham Residential v. Dellbrook, Needham, MA
Case involving the standard of care of the General Contractor.
Hamill v. Dickson and Thorpe, New York, NY
Neighbor dispute regarding existing rooftop HVAC units.
Mallard Square v. Ted-Co, Somerville, MA
Case involving contractor’s alleged failure to perform and their improper termination.
39 Harwood Porch Collapse, Dorchester, MA
On-going personal injury case involving the collapse of a third-story residential porch.
Construction Scope Evaluation:
6D Jacqueline Road, Waltham, MA
Evaluation of proposed scope and cost for replacement of an existing retaining wall.
PUBLICATIONS
O’Rourke, M., and Downey, C. “Rain-on-Snow Surcharge for Roof Design.” Journal of
Structural Engineering, Vol. 127, No. 1, 2001, pp. 74-79.
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulng & Engineering, P.C.
PRELIMINARY EXPERT REPORT
RE: 210 North Street
Hyannis, Massachusetts
Barnstable County
CCA Project No.: C002650
EXHIBIT B
New Building Structural Drawings
DRAWN BY CHECKED BY -FH
S-001
1 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
11/05/20241 REVISION
SHEET Nº
DRAWING TITLE:
STRUCTURAL
GENERAL NOTES
FOUNDATIONS
1. THE FOUNDATION HAS BEEN DESIGNED FOR 3,000 PSF A
ALLOWABLE SOIL BEARING CAPACITY.
2. ANY STRUCTURAL FILL OR BACKFILL FOR FOOTINGS, PIERS AND/OR
FOUNDATION WALLS SHALL BE PLACED IN UNIFORM HORIZONTAL
LIFTS HAVING A MAXIMUM LOOSE THICKNESS OF 9-INCHES AND
COMPACTED TO AT LEAST 95% OF MAXIMUM STANDARD DRY
DENSITY IN ACCORDANCE WITH ASTM D1557, UNLESS OTHERWISE
INDICATED OR SPECIFIED.
3. LOOSE, SOFT, WET, FROZEN, OR OTHERWISE UNSUITABLE SOILS
SHOULD EITHER BE RE-COMPACTED OR OVER-EXCAVATED TO A
SUITABLE SUBGRADE, AS APPROVED BY THE ON-SITE
GEOTECHNICAL ENGINEER. NO FOUNDATIONS SHALL BE PLACED
ON TOP OR UNSUITABLE SOILS.
4. VERIFY LOCATIONS AND REQUIREMENTS FOR INSERTS, SLEEVES,
CONDUITS, EMBEDMENT AND PENETRATIONS WITH RESPECTIVE
TRADES BEFORE PLACING CONCRETE.
5. DOWELS FROM FOUNDATIONS INTO PIERS, COLUMNS, BUTTRESSES
OR WALLS SHALL BE THE SAME SIZE AND NUMBER AS
REINFORCEMENT IN PIERS, COLUMNS, BUTTRESSES OR WALLS
ABOVE, EXCEPT AS OTHERWISE SHOWN.
6. CONTRACTOR SHALL PROVIDE CONTINUOUS DRAINAGE BY
MECHANICAL METHODS TO CONTROL SURFACE AND
UNDERGROUND WATER, AS REQUIRED DURING CONSTRUCTION.
7. CONTRACTOR SHALL ENSURE THAT GROUND WATER LEVELS UNDER
ADJACENT STRUCTURES AND PROPERTIES ARE NOT ALTERED.
8. ALL FOUNDATION UNITS (PIERS) SHALL BE CENTERED SUPPORT
MEMBERS, UNLESS OTHERWISE NOTED ON PLANS.
9. ALL BEARING MATERIALS SHALL BE INSPECTED BY THE
GEOTECHNICAL ENGINEER PRIOR EXECUTION AS REQUIRED BY
CODE.
10. BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BEAR A MINIMUM OF
4'-0" BELOW FINAL FINISHED GRADE FOR FROST PROTECTION.
11. FOUNDATION WALLS THAT RETAIN EARTH SHALL BE BRACED
AGAINST BACKFILLING PRESSURES UNTIL FLOOR SLABS AT TOP AND
BOTTOM ARE IN PLACE.
12. WHERE FOUNDATION WALLS ARE TO HAVE EARTH PLACED ON EACH
SIDE, PLACE FILL SIMULTANEOUSLY SO AS TO MAINTAIN A
COMMON ELEVATION ON EACH SIDE OF THE WALL.
13. ALL FOOTING EXCAVATIONS ARE TO BE FINISHED BY HAND.
14. PROTECT IN-PLACE FOUNDATIONS, SLABS AND ADJACENT
STRUCTURES, NEW CONSTRUCTION, STREET UTILITIES FROM FROST
PENETRATION OR DAMAGE FROM CONSTRUCTION ACTIVITIES
UNTIL THE PROJECT IS COMPLETED.
15. SLAB ON GRADE SHALL BEAR DIRECTLY ON A MIN. 12" THICK LAYER
OF COMPACTED STRUCTURAL FILL, OR 6" THICK LAYER OF CRUSHED
STONE, PLACED ABOVE PROOF-ROLLED UNDISTURBED NATURAL
SOIL. IF BEDROCK IS ENCOUNTERED, IT SHOULD BE EXCAVATED A
MIN. OF 12" BELOW THE BOTTOM OF PROPOSED FOOTING. LOOSE
ROCK PIECES SHOULD BE REMOVED WITHIN THE FOOTING BEARING
ZONE, AND OPEN BEDROCK JOINTS SHOULD BE CHOKED WITH
CRUSHED STONE OR FILLED WITH CONCRETE PRIOR TO PLACING
THE SOIL CUSHION.
CAST-IN-PLACE (CIP) CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE LATEST EDITIONS OF
THE ACI BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE
(ACI 318); DETAILS AND DETAILING OF CONCRETE REINFORCEMENT
(ACI-315); GUIDE TO CONCRETE FLOOR AND SLAB CONSTRUCTION
(ACI-302); STANDARD SPECIFICATION FOR DEFORMED AND PLAIN
CARBON STEEL BARS FOR CONCRETE REINFORCEMENT (ASTM A615);
AND APPLICABLE LOCAL CODE.
2. ALL CONCRETE SHALL BE CONTROLLED CONCRETE, MIXED AND PLACED
UNDER THE SUPERVISION OF AN APPROVED CONCRETE TESTING
AGENCY. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR
DESIGN OF CONCRETE MIXES AND FOR MAINTAINING STRENGTH AND
PROPER SLUMP DURING CONSTRUCTION.
3. CONCRETE SHALL BE NORMAL WEIGHT CONCRETE WITH FINE AND
COARSE AGGREGATE, TYPE I OR II PORTLAND CEMENT AND WITH A
MINIMUM 28-DAYS STRENGTH OF 3,000 PSI.
4. ALL CONCRETE EXPOSED TO THE WEATHER OR POSSIBLE FREEZE/THAW
ACTION SHALL CONTAIN AIR-ENTRAINING ADMIXTURE WITH 6% (±1%)
AT POINT OF DELIVERY.
5. CONCRETE MAY CONTAIN A WATER REDUCING, PLASTICIZING OR ANY
APPROVED ADMIXTURE. THE MAXIMUM WATER-CEMENT RATIO OF
ALL CONCRETE SHALL BE 0.5 (U.N.O.).
6. NO CALCIUM CHLORIDE SHALL BE USED IN ANY CONCRETE.
7. CONCRETE COVER PROTECTION FOR REINFORCEMENT SHALL BE AT
LEAST:
·3" WHEN CAST AGAINST OR PERMANENT EXPOSED TO EARTH
·2" CONCRETE EXPOSED TO WEATHER
8. ALL CONCRETE FOOTINGS AND WALL SECTIONS SHALL BE PLACED
WITHOUT HORIZONTAL CONSTRUCTION JOINTS. HORIZONTAL WALL
REINFORCEMENT SHALL BE CONTINUOUS THROUGH VERTICAL
CONSTRUCTION JOINTS. WIRE BRUSH AND CLEAN CONSTRUCTION
JOINTS PRIOR TO POURING NEW CONCRETE.
9. NO BARS SHALL BE CUT OR OMITTED IN THE FIELD BECAUSE OF
SLEEVES, DUCT OPENINGS OR RECESSES. BARS MAY BE ADJUSTED
WITHOUT CHANGE IN LEVEL.
10.NO CHASES, RECESSES, OPENINGS OR SLEEVES SHALL BE INSTALLED IN
CONCRETE WITHOUT APPROVAL OF THE DESIGN ENGINEER.
11.KEYS SHALL BE A MINIMUM OF 2"x4" BEVELED SIDES.
12.CHAMFER EXPOSED EDGES 3/4 INCH UNLESS OTHERWISE NOTED.
13.DETAILS NOT SHOWN SHALL BE IN ACCORDANCE WITH THE ACI
DETAILING MANUAL. ALL FORMWORK SHALL BE CONSTRUCTED SO
CONCRETE MEMBERS AND STRUCTURES ARE OF SIZE, SHAPE,
ALIGNMENT, ELEVATION, AND POSITION INDICATED WITHIN
TOLERANCE LIMITS OF ACI 117.
14.REINFORCING BAR SHALL CONFORM TO ASTM A615 GRADE 60 UNLESS
OTHERWISE INDICATED ON THIS DRAWINGS.
15.WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A1064 WITH
A MINIMUM ULTIMATE TENSILE STRENGTH OF 10,000-PSI.
16.ALL REINFORCING SPLICES SHALL BE CLASS C TENSION SPLICES IN
ACCORDANCE WITH ACI 318, UNLESS OTHERWISE NOTED.
17.WHERE REQUIRED, PROVIDE DOWELS TO MATCH SIZE AND SPACING
OF MAIN REINFORCING.
18.REINFORCING SHALL BE CONTINUOUS THROUGH ALL CONSTRUCTION
JOINTS. THE CONTRACTOR SHALL LOCATE CONSTRUCTION JOINTS AT
POINTS OF MINIMUN SHEAR.
210 NORTH STREET
Hyannis- MA
DESIGN CRITERIA
1. THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH:
a. INTERNATIONAL RESIDENTIAL CODE (IRC);
b. INTERNATIONAL BUILDING CODE (IBC)
c. ASCE MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES; ASCE/SEI 7-10;
d. AF&PA-AWC NATIONAL DESIGN SPECIFICATIONS (NDS) FOR WOOD
CONSTRUCTION;
e. STEEL CONSTRUCTION MANUAL, AMERICAN INSTITUTE OF STEEL
CONSTRUCTION, INC. AISC 13TH EDITION, 2005.; AND
f. APPLICABLE LOCAL REGULATIONS AND ORDINANCES, AND ALL
REFERENCED CODES.
2. DEAD LOADS
a. WEIGHT OF BUILDING COMPONENTS
3. LIVE LOADS: PER MASS. BUILDING CODE AND ASCE 7-10; EXPOSURE C
RISK CATEGORY II - BASIC WIND SPEED V (ult.) = 140 mph
DIRECTIONAL METHOD
HEIGHT WALL (psf) (ult.)
0' - 15' 33.17
15' - 20' 34.77
20' - 30' 36.61
30' - 40' 38.02
40' - 50' 39.18
4. EARTHQUAKE LOADS - PER MASS. CODE AND ASCE 7-10; OCCUPANCY
CATEGORY II
IMPORTANCE FACTOR I=1.0; SITE CLASS "C"
SEISMIC PERFORMANCE CATEGORY "B"
EQUIVALENT LATERAL FORCE PROCEDURE
R=6.5' Cd=4.0 (LIGHT FRAMED SHEAR WALL SHEATHED W/WOOD
STRUCTURAL PANELS)
Ss= .224; Fa=1.2; SDS= .179g
S1= .070; Fv=1.7; SD1= .079g
Cs= .028; W=440 Kips; V= Cs x W; V= 14.0 Kips (ult.)
WOOD
ALL STRUCTURAL LUMBER AND THEIR CONNECTIONS SHALL CONFORM TO
THE LATEST EDITION OF NFPA NATIONAL DESIGN SPECIFICATIONS FOR
WOOD CONSTRUCTION AND SUPPLEMENT "DESIGN VALUES FOR WOOD
CONSTRUCTION" AS WELL AS THE AMERICAN FOREST AND PAPER
ASSOCIATION GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR
ONE AND TWO FAMILY DWELLINGS.
1. UNLESS OTHERWISE NOTED ALL SAWN LUMBER FRAMING MEMBERS,
JOIST, RAFTERS, STUDS, LINTELS, PLATES, SHALL BE SPRUCE-PINEFIR
NO.2 OR BETTER, WITH THE FOLLOWING MINIMUM PROPERTIES:
Fb=1000 PSI,
Fv= 285PSI
E=1,300.00 PSI
2. ALL "MICROLAM" AND "VL" VERSALAM MEMBERS SHALL HAVE THE
FOLLOWING MINIMUM PROPERTIES:
E =2,000.000 PSI
Fb=2,800 PSI
Fv=285 PSI
3. ALL "TRUS JOIST TJI" MEMBERS SHALL HAVE THE FOLLOWING
MINIMUM PROPERTIES:
Fb=2800 PSI
Fv=280 PSI
E =2,000.000 PSI
4. WOOD SILLS SUPPORTED ON CONCRETE OR CONCRETE MASONRY
UNDER ALL INTERIOR OR EXTERIOR WALLS, AND ALL MEMBERS
EXPOSED TO WEATHER OR MOISTURE, SHALL BE SOUTHERN PINE NO. 2
OR BETTER, PRESERVATIVE TREATED IN ACCORDANCE WITH THE
"AMERICAN WOOD PRESERVERS ASSOCIATIONS STANDARD C1."
5. ALL STRUCTURAL LUMBER SHALL BE STAMPED IN ACCORDANCE WITH
THE AMERICAN INSTITUTE OF TIMBER CONSTRUCTION'S
"CONSTRUCTION MANUAL".
6. ADDITIONAL FLOOR JOISTS SHALL BE PROVIDED UNDER ALL
PARTITIONS OVER 4'-0" LONG WHICH RUN PARALLEL TO THE SPAN OF
THE FLOOR.
7. ADDITIONAL FLOOR JOISTS SHALL BE PROVIDED UNDER BATH TUBS.
8. PROVIDE CONTINUOUS 2X SOLID BLOCKING MATCHING THE STUD
SIZE, BETWEEN STUDS AT STUD MID-HEIGHT.
9. UNLESS NOTED OTHERWISE, PROVIDE AT MINIMUM DOUBLE STUDS
UNDER ALL HEADERS, OR BUILT UP BEAMS. ADDED STUDS AND ALL
POSTS SHALL CONTINUE FROM THE POINT OF LOAD APPLICATION TO
THE FOUNDATION.
10. ALL POST TO BEAM CONNECTIONS SHALL HAVE METAL POST BASE
AND POST CAP.
11. ALL FLUSH FRAMING CONNECTIONS SHALL HAVE BEAM OR JOISTS
HANGERS CAPABLE TO SUPPORT THE MEMBER REACTION.
12. ALL METAL CONNECTORS FOR WOOD CONSTRUCTION, JOISTS AND
BEAM HANGERS, POST AND COLUMN CAPS AND BASES, BRIDGING,
HOLDOWNS, HURRICANE TIES, STRAPPING AND ANY OTHER METAL
CONNECTORS, SHALL BE HOT-DIPPED GALVANIZED AS PER
MANUFACTURED BY "SIMPSON STRONG-TIE COMPANY" OR EQUAL.
ALL METAL CONNECTORS SHALL BE ATTACHED BY THE GENERAL
CONTRACTOR AS PER MANUFACTURERS SPECIFICATIONS. NAILS SHALL
BE FULLY DRIVEN IN ALL HOLES OF THE HANGERS OR ANCHORS.
13. FRAMING MEMBERS SHALL NOT BE NOTCHED, CUT OR ALTERED
WITHOUT IN FIELD THE APPROVAL OF THE ENGINEER. REFER TO
TYPICAL DETAILS FOR ALLOWED NOTHING AND HOLES IN 2X WOOD
JOISTS.
14. UNLESS OTHERWISE NOTED ON DRAWINGS, ALL STUD WALLS SHALL
BE CAPPED WITH DOUBLE TOP PLATES WITH OVERLAPPING CORNERS
AND INTERSECTIONS. SPLICE IN TOP PLATES SHALL BE ON TOP OF
STUDS AND BE OFFSET MINIMUM 4 FEET.
15. ALL TOP MOUNTED JOIST SHALL HAVE MINIMUM 3 INCH BEARING.
16. ALL EXTERIOR AND INTERIOR WALL SHEATHING SHALL BE 15/32 APA
RATED SHEATHING. AT EXTERIOR WALLS USE EXPOSURE 1 PANELS AND
USE EXTERIOR GRADE SHEATHING WHEN LONG CONSTRUCTION
DELAYS ARE EXPECTED. PROVIDE 2X HORIZONTAL BLOCKING AT LEAST
EQUAL THE SIZE OF JOIST, AT ALL UNSUPPORTED PANEL EDGES.
SHEATHING SHALL BE PROPERLY FASTENED TO THE WALL STUDS, SOLE
PLATES, TOP PLATES AND BLOCKING AS REQUIRED BY CODE, OR
SHOWN ON DRAWINGS. PANEL JOINTS SHALL OCCUR OVER STUDS AND
BLOCKING.
17.ALL ROOF SHEATHING SHALL BE 5/8" APA RATED SHEATHING
EXPOSURE 1, EXCEPT USE EXTERIOR GRADE PANELS WHEN LONG
CONSTRUCTION DELAYS ARE EXPECTED. APPLY PANELS WITH LONG
DIMENSIONS PERPENDICULAR TO THEIR SUPPORT OVER TWO OR
MORE SPANS. UNLESS OTHERWISE SHOWN ON PLANS, SHEATHING
SHALL BE NAILED WITH 8D NAILS @ 6 INCHES ON CENTER AT EACH
SIDE OF EDGE JOINTS, AND 8D NAILS @12 INCHES ON CENTER AT
INTERMEDIATE SUPPORTS.
18.FLOOR SHEATHING SHALL BE 3/4 INCH APA RATED EXPOSURE 1,
TONGUE AND GROOVE PLYWOOD PANELS. APPLY PANELS WITH THE
LONG DIMENSION PERPENDICULAR TO FLOOR JOISTS, CONTINUOUS
OVER TWO OR MORE SPANS. PANELS SHALL HAVE STAGGERED END
JOINTS IN EACH SUCCEEDING ROW AND SHALL BE GLUED AND NAILED
TO FLOOR JOISTS AS REQUIRED BY CODE AND LEAVING 1/8 INCH SPACE
BETWEEN ALL END AND EDGE JOINTS.
GENERAL NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE DESIGN WAS COMPLETED IN ACCORDANCE WITH THE CURRENT
EDITION OF THE MASSACHUSETTS STATE BUILDING CODE (MA-CODE)
INCLUDING ALL RELATED PROVISIONS AND AMENDMENTS.
ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE
MASSACHUSETTS STATE BUILDING CODE (MA-CODE) AND ALL OTHER
APPLICABLE FEDERAL, STATE AND LOCAL CODE, ORDINANCE AND/OR
REGULATION RELATED TO THE WORK SHOWN ON THESE DRAWINGS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
EXISTING CONSTRUCTION AND DIMENSIONS SHOWN ON THIS DRAWING
ARE BASED ON INFORMATION PROVIDED BY OTHERS. THE DESIGN
ENGINEER IS NOT RESPONSIBLE FOR THE ACCURACY OF THE
INFORMATION. DISCREPANCIES BETWEEN THIS DRAWING AND THOSE OF
OTHER DISCIPLINES SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER PRIOR COMMENCING THE WORK. NOTIFY THE DESIGN
ENGINEER IMMEDIATELY OF ANY ISSUE INTERFERING WITH THE
EXECUTION OF THE WORK SHOWN ON THIS DRAWING PRIOR TO
COMMENCING THE CONSTRUCTION.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
CONTRACTOR IS TO DETERMINE PROPERTY LINES AND SECURE ADJACENT
PROPERTY OWNER'S CONSENT IF WORK EXTENDS BEYOND BUILDING'S
PROPERTY LINE AS REQUIRED BY THE MA-CODE.
LEAVE NO HOLES UNPROTECTED OVERNIGHT OR OVER WEEKENDS OR
HOLIDAYS. INSPECT AND SECURE THE WORK AREA. REMOVE POTENTIAL
HAZARDS AND COMPLY WITH ALL PROVISIONS OF FEDERAL, STATE AND
LOCAL ORDINANCES INCLUDING ALL OSHA REGULATIONS.
PROVIDE STABLE AND SAFE SLOPES FOR ALL EXCAVATIONS IN
ACCORDANCE WITH APPLICABLE OSHA REQUIREMENTS. PROVIDE
ADEQUATE TRENCH SHORING AND OTHER PERSONNEL PROTECTION IN
ACCORDANCE WITH OSHA REQUIREMENTS DURING THE WORK.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
EXCAVATE TO EXPOSE RETAINING WALL SUBGRADE. SUBGRADE CAPACITY
SHALL BE VERIFIED AS REQUIRED BY THE MA-CODE. UNLESS OTHERWISE
INDICATED BY A GEOTECHNICAL ENGINEER, THE FOUNDATION SOIL SHALL
BE UNDISTURBED NATIVE SOIL OR COMPACTED STRUCTURAL FILL WITH
AN MINIMUM ALLOWABLE CAPACITY OF 4,000 PSF.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
LOCUS PLAN
NOT TO SCALE
11/19/20242 REVISION
01/24/20253 REVISION
03/31/20254 REVISION
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
LEGEND:
UNDERPINNING SEQUENCING.
UNDERPINNING NUMBER.
#
#
UP
1
A
B
2
C
ELEVATOR'S PIT ELEVATOR
CONTROL
SPACE
739 SF
MACHINE ROOM
0-1
8'-10"5'-8"7 EQ. SPACED HELICAL PILE = 43'-4"±6'-10" MAX. SPACEMENFO-101
2
FO-101
1
FO-101
2
FO-101
1
FO-101
2
EXISTING CONCRETE
FOUNDATION WALLS
TO REMAIN
HELICAL PILE
BY OTHERS
NEW CONCRETE FOUND. WALL & FOOTING
G.C. TO SHORE EXIST. ROOF FRAMING
PRIOR TO INSTALLING NEW FOUND. WALL
& FOOTING.
EXISTING FOUND. WALL &
FOOTING G.C. TO BE
DEMOLISH.2'-6"FTG.2'-6"FTG.2'-6"FTG.10"x10"x3 8" STEEL
PLATE
(4x) 3 8" Ø BOLT
EMBED. 7" IN
CONCRETE
3'x3'x1' COLUMN
CONCRETE PAD
REINF. #5 BARS AT
BOTT. @ 6" OC.
FO-101
3
STRUCTURAL FILL
COMPACTED MIN. 95% SPD
STRUCTURAL FILL
COMPACTED MIN. 95% SPD
FO-100
A
7 EQ. SPACED HELICAL PILE = 43'-4"±6'-10" MAX. SPACEMENHELICAL PILE
BY OTHERS
EXISTING CONCRETE
FOUNDATION WALLS
TO REMAIN
10"x10"x3 8" STEEL
PLATE
(4x) 3 8" Ø BOLT
EMBED. 7" IN
CONCRETE
2'x2' COLUMN
CONCRETE PAD
(TYP.)
4" Ø LALLY (TYP.)
TO UP
6'-4"5'-3"5'-2"5'-2"
2'x2' COLUMN
CONCRETE PAD
(TYP.)
4" Ø LALLY (TYP.)
TO UP
7'-4"7'-4"7'-4"7'-4"7'-4"
2'x2' COLUMN
CONCRETE PAD
(TYP.)7'-11"BEAM
POCKET
3,000PSI CONCRETE
4" THICK SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
SEE ARCH PLANS FOR
INSULATION DETAIL
NEW CONCRETE FOUND. WALL & FOOTING
G.C. TO SHORE EXIST. ROOF FRAMING
PRIOR TO INSTALLING NEW FOUND. WALL
& FOOTING.
10"x10"x3 8" STEEL
PLATE
(4x) 3 8" Ø BOLT
EMBED. 7" IN
CONCRETE
NEW FOOTING FOR
BEARING WALL
SEE DETAIL
NEW FOOTING FOR
BEARING WALL
SEE DETAIL
NEW FOOTING FOR
BEARING WALL
SEE DETAIL
4" Ø LALLY (TYP.)
TO UP
BEAM
POCKET
2'x2' COLUMN
CONCRETE PAD
(TYP.)
12'-6"11'-8"7'-2"20'-8"10'-8"
14'-8"
FO-101
5
BEAM
POCKET BEAM
POCKET
BASEMENT
UNT 03 UNIT 02
PROPOSED BASEMENT
EL. -9 '- 2"
EXISTING 1ST FLOOR
EL. 0 '- 0"
12
12
12
12
UNDISTURBED
AREAPASSIVE
ZONE
STRUCTURAL FILL
95% SPD MIN.
4" THICK CONCRETE
SLAB ON GRADE
4" THICK CONCRETE
SLAB ON GRADE
12
12
UNDISTURBED
AREA
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
DRAWN BY CHECKED BY -FH
FO-100
2 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
KEY NOTES AND FOUNDATION
PLAN VIEW
FOUNDATION/BASEMENT PLAN VIEW
SCALE: 1/4" = 1'-0"
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
FOUNDATION NOTES:
1. INFILL SOIL ARE APPROVED ENGINEERING FILL COMPACTED
THE MAXIMUM 12-INCH LAYER TO A MIN. 95% SPD UNDER
DIRECTION OF A SITE ENGINEER.
2. THE FOUNDATION CONCRETE SHALL HAVE A MINIMUM
COMPRESSIVE STRENGTH OF 4,000-PSI AT 28-DAYS.
3. FOUNDATION SOIL SHALL BE UNDISTURBED NATIVE SOIL OR
COMPACTED STRUCTURAL FILL WITH A MINIMUM ALLOWABLE
BEARING CAPACITY OF 4,000-PSF.
210 NORTH STREET
Hyannis- MA
11/05/20241 REVISION
FOUNDATION DETAIL
NOT TO SCALE
A
FO-100
11/19/20242 REVISION
5
5
01/24/20253 REVISION
03/31/20254 REVISION
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
VAPOR BARRIER 10MIL
3,000PSI 6" CONCRETE
SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
FINISHED
GRADE
STRUCTURAL FILL
95% SPD MIN.
INSULATION SEE ARCH.
MIN. 6" 3 4" CRUSHED
STONE
HELICAL PILE
BY OTHERS
EXIST. CONCRETE WALL TO
REMAIN. G.C. TO REMOVE AND
REPLACE ANY LOOSE
EXISTING. MATERIAL.
x x x x x x x x x x
1
10"
G.C. TO VERIFY
EXIST. T.O.S.
EL. V.I.F.
FOUNDATION
BRACKET
BY OTHERS
4" PERFORATED PVC PIPE
W/ FILTER SOCK IN 3 4" CRUSHED STONE
CONNECTED TO POSITIVE OUTLET.
2'-6"
MIN.1'-6"(2x) #5 CONTINUOUS
SPLICE AS REQ'D
KEY WAY
10"
FINISHED
GRADE
12" ANCHOR BOLT
EMBEDDED IN
CONCRETE MIN. 7"
EACH 36" C-C(2x) #4 CONTINUOUS
SPLICE AS REQ'D
VAPOR BARRIER 10MIL
3,000PSI 6" CONCRETE
SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
INSULATION SEE ARCH.
MIN. 6" 3 4" CRUSHED
STONE
x x x x x x x x x x
EXIST. T.O.S.
EL. V.I.F.
GRANULAR
BACKFILL STRUCTURAL FILL
95% SPD MIN.1'-6" 4'-0"MIN. EMBEDMENTA1
x x x x x x x x x x x x x x
INSULATION SEE ARCH.
MIN. 6" 3 4" CRUSHED
STONE
VAPOR BARRIER 10MIL
3,000PSI 6" CONCRETE
SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
EXIST. T.O.S.
EL. V.I.F.
STRUCTURAL FILL
95% SPD MIN.
2'-6"
MIN.1'-6"1
2 1
2
(2x) #5 CONTINUOUS
SPLICE AS REQ'D
PROVIDE DOWELS WHERE
WALLS ARE REINFORCED.
SIZE AND SPACING TO MATCH
WALL REINF. GROUT CELLS
SOLID.
8" CMU WALL
SEE PLANS
(2x) #5 TOP
(2x) #5 BOTT
#4 @ 12" STIRRUPS
(3x) #4
ON BOTTOM1'-0"2'-0"
MIN.
2,000PSF BEARING
FOUNDATION SOIL
10" THICK
4" THICK
CONCRETE
SLAB ON GRADE
VAPOR BARRIER 10MIL
4" PERFORATED
PVC PIPE
W/ FILTER SOCK IN 3 4"
CRUSHED STONE
CONNECTED TO
POSITIVE OUTLET.4" PERFORATED
PVC PIPE
W/ FILTER SOCK IN 3 4" CRUSHED
STONE
CONNECTED TO POSITIVE
OUTLET.
(2x) #4 CONTINUOUS
SPLICE AS REQ'D
3"MIN.(2x) #4 CONTINUOUS
SPLICE AS REQ'D
12" ANCHOR BOLT
EMBEDDED IN
CONCRETE MIN. 7"
EACH 36" C-C
VAPOR BARRIER 10MIL
SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
INSULATION SEE ARCH.
MIN. 6" 3 4" CRUSHED
STONE
xxxxxxxxxx
EXIST. T.O.S.
EL. V.I.F.
STRUCTURAL FILL
95% SPD MIN.
#4 VERTICAL BAR
@ 36" O.C.
FOUNDATION
WALL
JOIST
8'-11"SEE ARCH.312" SLOT TO FIT58" ANCHOR BOLT3"314" MAX.LIFTING DISTANCE412"
612"
1112"
14" WIDE BRACKET
CROSS BOLT 5 8"
DIA. BY 412" LONG
LIFTING BOLTS 7 8"
DIA. BY 8" LONG
1312" MAX. HEIGHTABOVE BOTTOM OF FOOTING7"612"
13 4" STAMP
2-7 8"
33 16"
REAR VIEW SIDE VIEW ISOMETRIC
x x x x x x x x x x x x x x
INSULATION SEE ARCH.
MIN. 6" 3 4" CRUSHED
STONE
VAPOR BARRIER 10MIL
3,000PSI 6" CONCRETE
SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
EXIST. T.O.S.
EL. V.I.F.
STRUCTURAL FILL
95% SPD MIN.
2'-6"
MIN.1'-6"1
2 1
2
(3x) #5 CONTINUOUS
SPLICE AS REQ'D
(2x) 2x6 PT SILL PL W/ 5 8"
ANCHOR BOLTS @ 24" O.C.
BEARING WALL
SEE PLANS
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
DRAWN BY CHECKED BY -FH
FO-101
3 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
KEY NOTES, FOUNDATION &
UNDERPINNING DETAIL
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
HELICAL PILE DETAIL
NOT TO SCALE
1
FO-101
FOUNDATION NOTES:
1. INFILL SOIL ARE APPROVED ENGINEERING FILL COMPACTED
THE MAXIMUM 12-INCH LAYER TO A MIN. 95% SPD UNDER
DIRECTION OF A SITE ENGINEER.
2. THE FOUNDATION CONCRETE SHALL HAVE A MINIMUM
COMPRESSIVE STRENGTH OF 4,000-PSI AT 28-DAYS.
3. FOUNDATION SOIL SHALL BE UNDISTURBED NATIVE SOIL OR
COMPACTED STRUCTURAL FILL WITH A MINIMUM ALLOWABLE
BEARING CAPACITY OF 4,000-PSF.
HELICAL PILES NOTES
1. STANDARDS AND SPECIFICATIONS
1.1. ALL WORK SHALL CONFORM TO THE PLANS, SPECIFICATIONS, AND
APPLICABLE LOCAL, STATE, AND FEDERAL REGULATIONS.
1.2. HELICAL PILE DESIGN, FABRICATION, AND INSTALLATION SHALL
COMPLY WITH THE LATEST EDITIONS OF:
- INTERNATIONAL BUILDING CODE (IBC).
- ICC-ES ACCEPTANCE CRITERIA FOR HELICAL FOUNDATION SYSTEMS
AND DEVICES (AC358).
- ASTM A29, A123, A153, OR EQUIVALENT FOR MATERIALS AND
COATINGS.
2. MATERIALS
2.1. HELICAL PILES AND COMPONENTS SHALL BE MANUFACTURED
FROM STRUCTURAL STEEL CONFORMING TO ASTM STANDARDS, WITH
PROPER HOT-DIP GALVANIZATION FOR CORROSION RESISTANCE (ASTM
A123 OR AS SPECIFIED).
2.2. MINIMUM TENSILE AND YIELD STRENGTHS FOR STEEL SHAFT AND
HELIX MATERIALS SHALL MEET THE REQUIREMENTS SHOWN ON THE
PROJECT PLANS.
3. DESIGN
3.1. HELICAL PILE CAPACITIES SHALL MEET THE ALLOWABLE
COMPRESSION, TENSION, AND LATERAL LOADS SPECIFIED IN THE
DESIGN DRAWINGS.
3.2 THE MINIMUM ALLOWABLE COMPRESSION LOAD FOR EACH PILE IS
16,000 lb (16 KIPS).
3.3. EMBEDMENT DEPTH AND TORQUE REQUIREMENTS ARE AS PER
THE PILE SCHEDULE ON PROJECT DRAWINGS.
4. INSTALLATION
4.1. INSTALLATION SHALL BE PERFORMED BY QUALIFIED
CONTRACTORS EXPERIENCED IN HELICAL PILE SYSTEMS. INSTALLERS
SHALL FOLLOW THE MANUFACTURER’S RECOMMENDATIONS AND THE
PROJECT-SPECIFIC INSTALLATION PLAN.
4.2. TORQUE MONITORING EQUIPMENT MUST BE CALIBRATED AND
CAPABLE OF MEASURING INSTALLATION TORQUE ACCURATELY.
4.3. EACH PILE SHALL BE ADVANCED TO THE REQUIRED MINIMUM
EMBEDMENT DEPTH AND FINAL INSTALLATION TORQUE SPECIFIED IN
THE DESIGN.
4.4. INSTALLATION RECORDS, INCLUDING TORQUE AND DEPTH
READINGS, SHALL BE MAINTAINED AND SUBMITTED FOR REVIEW.
5. TESTING
5.1. FIELD VERIFICATION OF INSTALLED HELICAL PILE CAPACITY SHALL
BE PERFORMED USING LOAD TESTS IN ACCORDANCE WITH ASTM
D1143 (COMPRESSION), ASTM D3689 (TENSION), OR ASTM D3966
(LATERAL).
5.2. TEST LOADS SHALL ACHIEVE AT LEAST 1.5 TO 2 TIMES THE DESIGN
LOAD UNLESS OTHERWISE SPECIFIED.
6. CORROSION PROTECTION
6.1. HELICAL PILES IN CORROSIVE ENVIRONMENTS SHALL BE
GALVANIZED OR OTHERWISE TREATED AS NOTED ON THE PROJECT
PLANS AND SPECIFICATIONS.
6.2. IF REQUIRED, SUPPLEMENTAL PROTECTIVE COATINGS (E.G., EPOXY,
BITUMINOUS) SHALL BE APPLIED IN THE FIELD AS SPECIFIED.
7. FIELD INSPECTION
7.1. A QUALIFIED ENGINEER OR INSPECTOR SHALL MONITOR AND
DOCUMENT THE HELICAL PILE INSTALLATION PROCESS TO ENSURE
COMPLIANCE WITH PROJECT SPECIFICATIONS.
7.2. INSPECTIONS SHALL INCLUDE TORQUE MONITORING, DEPTH
VERIFICATION, ALIGNMENT CHECKS, AND PILE INTEGRITY
ASSESSMENTS.
8. DEVIATION AND ADJUSTMENTS
8.1. IF PILES CANNOT ACHIEVE THE REQUIRED TORQUE OR DEPTH, THE
CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY FOR
EVALUATION AND APPROVAL OF MODIFICATIONS (E.G., PILE
RELOCATION, EXTENSIONS, OR ADDITIONAL HELIX PLATES).
8.2. MODIFICATIONS TO THE DESIGN OR INSTALLATION PLAN REQUIRE
APPROVAL FROM THE ENGINEER OF RECORD.
9. SUBMITTALS
9.1. SUBMIT SHOP DRAWINGS, MATERIAL CERTIFICATIONS, TORQUE
CALIBRATION RECORDS, AND INSTALLATION LOGS TO THE ENGINEER
PRIOR TO COMMENCING WORK.
9.2. PROVIDE FINAL INSTALLATION RECORDS AND TEST RESULTS FOR
APPROVAL BEFORE STRUCTURAL ELEMENTS RELYING ON THE PILES ARE
INSTALLED.
FOUNDATION DETAIL
NOT TO SCALE
2
FO-101
FOUNDATION DETAIL
NOT TO SCALE
4
FO-101
210 NORTH STREET
Hyannis- MA
FOUNDATION DETAIL
NOT TO SCALE
3
FO-101
11/05/20241 REVISION
FOUNDATION BRACKET DETAIL
NOT TO SCALE
HELICAL PILE PROJECT LOAD:
WORKING LOAD Pw= 16,000lb
ULTIMATE CAPACITY Pu=32,000lb
11/19/20242 REVISION
FOUNDATION DETAIL
NOT TO SCALE
5
FO-101
01/24/20253 REVISION
03/31/20254 REVISION
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
.UP
DN
1
A
B
2
UNIT 01
UNIT 02
UNIT 04
UNIT 03
C
ED
ELEVATOR
SPRINKLER
ROOM
HALLWAY
HALLWAY
MAILBOXES
C4
C8
C5
C7
C9
C1
C2
C3
C6
AT ELEV PROVIDE ADD'L
#5@12" HEF IN FOOTING.
3,000PSI CONCRETE
6" THICK SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
SEE ARCH PLANS FOR
INSULATION DETAIL
W-1W-1W-2W-1SW-2 UPW-1W-1W-2
W-2
W-2
W-1W-1W-5W-5W-3
W-5 W-32K, 2J 2K, 2J0K, 4J 2K, 2J 2K, 2J 2K, 2J0K, 4J
2K, 2J 2K, 2J0K, 4J 2K, 2J 2K, 2J0K, 4J2K, 2J2K, 2J0K, 4J2K, 2J2K, 2J2K, 2J2K, 2J2K, 2J0K, 4J(2x) 2X10 HDR (2x) 2X10 HDR
2K, 2J 2K, 2J
(2
x
)
2
X
1
0
H
D
R
(2x) 2X10 HDR(2x) 2X12 HDR
(2x) 2X10 HDR(2x) 2X10 HDR(2x) 2X10 HDR
(2x) 2X10 HDR(2x) 2X10 HDR(2x) 2X10 HDR(2x) 2X10 HDR (2x) 2X10 HDR
2K, 2J
HSS4x4X3 8" TO UPHSS4x4X38" TO UPHSS4x4X38" TO UP
3,000PSI CONCRETE
6" THICK SLAB ON GRADE
REINF W/ 6x6-W1.4xW1.4 WWF
SEE ARCH PLANS FOR
INSULATION DETAIL
2K, 2J
(2x) 2X10 HDR
W-22K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
W-2W-2 2K, 2J
(2x) 2X10 HDR
(4x) 1 3 4" x 11 14"
2.0E LVL
2x10 SPF No. 1/No.2
FLOOR JOIST @16" O.C.
(4x) 1 3 4" x 11 14"
2.0E LVL
(4x) 1 3 4" x 11 14"
2.0E LVL (3x) 1 34" x 9 14"2.0E LVL(3x) 1 34" x 11 14"2.0E LVL(3x) 1 34" x 9 14"2.0E LVL(3x) 1 34" x 9 14"2.0E LVL3 12" x 3 12" 1.8E PSL
COLUMN TO UP 3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
W-5
W-5W-5W-5CMU WALL
CMU WALLCMU WALLUNT 03EXISTING 1ST FLOOR
EL. 0 '- 0"
PROPOSED 2ND FLOOR
EL. 10 '- 8"
VERSA STUD LVL 1 12" x 5 12" @
16" O.C.
W-5
UNT 08
(2x) 2x6 @ 16" O.C.
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
DRAWN BY CHECKED BY -FH
S-100
4 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
KEY NOTES, 1ST FLOOR FRAME
PLAN VIEW AND DETAIL
1ST FLOOR FRAME PLAN VIEW
SCALE: 1/4" = 1'-0"
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
210 NORTH STREET
Hyannis- MA
LEGEND:
#K, #J INDICATES KING/JACK STUD COUNT. USE 2K2J STUDS
WHERE NOT SPECIFICALLY NOTED.
EXTERIOR WALL TYPE SCHEDULE
NOT TO SCALE
11/05/20241 REVISION
11/19/20242 REVISION
01/24/20253 REVISION
WALL NOTES:
1.ALL EXTERIOR WALL SHOWN ARE 2x6 WITH 58" ZIP SHEATHING
IS NAILED TO STUDS WITH 10d GALVANIZED COMMON NAILS
SPACED @ 3" OC. @ PANEL EDGES & @12" OC. @ INTERMEDIATE
SUPPORTS.
2.W-1 INDICATES 2x4 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
3.W-2 INDICATES 2x6 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
4.W-3 INDICATES (1x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES @, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-4 INDICATES (2x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-5 INDICATES VERSA STUD LVL 1 12" x 5 12" WITH 58" ZIP BD.
SHEATHING O(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH
SIDES , SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d
GALVANIZED COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
6.FOR ALL NON-BEARING STRUCTURAL SHEAR WALL USE 2x4@16" OC
WITH GYP BD. OR PLYWOOD NOTED ABOVE.
03/31/20254 REVISION
5
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
5
USE EVERY OTHER NAIL HOLE IN A
ROW TO PROVIDE THE
CODE-REQUIRED MINIMUM
CENTER-TO-CENTER SPACING FOR
NAILS
CUT
LENGTH
END
LENGTH
CLEAR
SPAN
END
LENGTHPROVIDE MINIMUM
7 8" END DISTANCE
EQUAL NUMBER OF
SPECIFIED NAILS IN
EACH END.DN
1
A
B
2
C
ED
ELEVATOR
UNIT 05UNIT 06
UNIT 07
UNIT 08
UNIT 09
HALLWAY
C14
C11
C13
2K, 2J 2K, 2J0K, 4J 2K, 2J 2K, 2J 2K, 2J0K, 4J2K, 2J
2K, 2J 2K, 2J0K, 4J
(2x) 2X10 HDR
2K, 2J 2K, 2J0K, 4J
(2x) 2X10 HDR
2K, 2J 2K, 2J0K, 4J
(2x) 2X10 HDR
2
K
,
2
J
2K, 2J0K, 4J(2
x
)
2
X
1
0
H
D
R 2K, 2J2K, 2J0K, 4J(2x) 2X10 HDR2K, 2J2K, 2J0K, 4J(2x) 2X10 HDR2K, 2J(2x) 2X10 HDR2K, 2J(2x) 2X10 HDR(2x) 2X10 HDR (2x) 2X10 HDR (2x) 2X10 HDR (2x) 2X10 HDR (2x) 2X10 HDR
2K, 2J
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
S.200
DET. 1
S.200
DET. 1
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
(2x) 1 3 4" x 9 1 4" 2.0E LVL
(2x) 1 3 4" x 9 1 4" 2.0E LVL
HSS4x4X3 8" TO UPHSS4x4X38" TO UPHSS4x4X38" TO UP
(2x) 1 3 4" x 9 1 4" 2.0E LVL
LU28
HANGER
(3x) 1 3 4" x 9 1 4" 2.0E LVL
3 12" x 3 12" 1.8E PSL
COLUMN TO UP 3 12" x 3 12" 1.8E PSL
COLUMN TO UP
(2x) 1 3 4" x 9 1 4" 2.0E LVL
(3x) 1 3 4" x 9 14" 2.0E LVL
(3x) 1 34" x 9 14" 2.0E LVL(3x) 1 3 4" x 9 14" 2.0E LVL
" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO DN
SW-2 UP
W-3W-3W-3 W-3
W-3
W-3
W-3
W-2 W-2
W-2
W-2W-2
W-1W-1W-1W-1W-2W-2
CMU WALL
CMU WALLCMU WALLW-1W-116" FLAT TRUSS
FLOOR TRUSS @16" O.C.
16" FLAT TRUSS
FLOOR TRUSS @16" O.C.
UNT 13
PROPOSED 2ND FLOOR
EL. 10 '- 8"
PROPOSED 3RD FLOOR
EL. 21 '- 4"
W-5
UNT 08
(2x) 2x6 @ 16" O.C.
W-4
2x6 @ 16" O.C.
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
DRAWN BY CHECKED BY -FH
S-200
5 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
KEY NOTES, 2ND FLOOR FRAME
PLAN VIEW AND DETAIL
2ND FLOOR FRAME PLAN VIEW
SCALE: 1/4" = 1'-0"
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
S.200
DET. 1 HIGH WIND STRAP DETAIL
NOT TO SCALE
210 NORTH STREET
Hyannis- MA
EXTERIOR WALL TYPE SCHEDULE
NOT TO SCALE
LEGEND:
#K, #J INDICATES KING/JACK STUD COUNT. USE 2K2J STUDS
WHERE NOT SPECIFICALLY NOTED.
11/05/20241 REVISION
11/19/20242 REVISION
01/24/20253 REVISION
WALL NOTES:
1.ALL EXTERIOR WALL SHOWN ARE 2x6 WITH 58" ZIP SHEATHING
IS NAILED TO STUDS WITH 10d GALVANIZED COMMON NAILS
SPACED @ 3" OC. @ PANEL EDGES & @12" OC. @ INTERMEDIATE
SUPPORTS.
2.W-1 INDICATES 2x4 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
3.W-2 INDICATES 2x6 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
4.W-3 INDICATES (1x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES @, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-4 INDICATES (2x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-5 INDICATES VERSA STUD LVL 1 12" x 5 12" WITH 58" ZIP BD.
SHEATHING O(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH
SIDES , SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d
GALVANIZED COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
6.FOR ALL NON-BEARING STRUCTURAL SHEAR WALL USE 2x4@16" OC
WITH GYP BD. OR PLYWOOD NOTED ABOVE.
03/31/20254 REVISION
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
5
5
USE EVERY OTHER NAIL HOLE IN A
ROW TO PROVIDE THE
CODE-REQUIRED MINIMUM
CENTER-TO-CENTER SPACING FOR
NAILS
CUT
LENGTH
END
LENGTH
CLEAR
SPAN
END
LENGTHPROVIDE MINIMUM
7 8" END DISTANCE
EQUAL NUMBER OF
SPECIFIED NAILS IN
EACH END.1
A
B
2
C
ED
ELEVATOR
UNIT 10UNIT 11UNIT 12
UNIT 13 UNIT 14
HALLWAY C15
C16
C17
S
W
-
2 SW-2SW-2 UP
16" FLAT TRUSS
FLOOR TRUSS @16" O.C.
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
2K, 2J2K, 2J0K, 4J(2x) 2X10 HDR(2x) 2X10 HDR2K, 2J2K, 2J(2x) 2X10 HDR2K, 2J 2K, 2J0K, 4J
(2x) 2X10 HDR
2K, 2J 2K, 2J0K, 4J
(2x) 2X10 HDR
2K, 2J 2K, 2J0K, 4J
(2x) 2X10 HDR
2
K
,
2
J
2K, 2J0K, 4J(2
x
)
2
X
1
0
H
D
R 2K, 2J2K, 2J0K, 4J(2x) 2X10 HDR2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
S.300
DET. 1
S.300
DET. 1
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
WIND BLOKING@ 4'-0" MAX.(2x) 1 3 4" x 9 14" 2.0E LVL
(3x) 1 3 4" x 9 14" 2.0E LVL
HSS4x4X3 8" TO UPHSS4x4X38" TO UPHSS4x4X38" TO UP
(2x) 1 3 4" x 9 14" 2.0E LVL
LU28
HANGER
(2x) 1 3 4" x 9 14" 2.0E LVL
(2x) 1 3 4" x 9 14" 2.0E LVL
3 12" x 3 12" 1.8E PSL
COLUMN TO UP 3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
(2x) TRUSSW-3W-3W-3 W-3
W-3
W-3
W-3
W-2 W-2
W-2
W-2W-2
W-1W-1W-1W-1W-2W-2
CMU WALL
CMU WALLCMU WALLW-1W-116" FLAT TRUSS
FLOOR TRUSS @16" O.C.
UNT 13
UNT 17
PROPOSED 3RD FLOOR
PROPOSED 4TH FLOOR
EL. 32 '- 0"
2x6 @ 16" O.C.
W-3
2x6 @ 16" O.C.
W-3
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
DRAWN BY CHECKED BY -FH
S-300
6 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
KEY NOTES, 3RD FLOOR FRAME
PLAN VIEW AND DETAIL
3RD FLOOR FRAME PLAN VIEW
SCALE: 1/4" = 1'-0"
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
S.300
DET. 1 HIGH WIND STRAP DETAIL
NOT TO SCALE
210 NORTH STREET
Hyannis- MA
EXTERIOR WALL TYPE SCHEDULE
NOT TO SCALE
LEGEND:
#K, #J INDICATES KING/JACK STUD COUNT. USE 2K2J STUDS
WHERE NOT SPECIFICALLY NOTED.
11/05/20241 REVISION
11/19/20242 REVISION
01/24/20253 REVISION
03/31/20254 REVISION
WALL NOTES:
1.ALL EXTERIOR WALL SHOWN ARE 2x6 WITH 58" ZIP SHEATHING
IS NAILED TO STUDS WITH 10d GALVANIZED COMMON NAILS
SPACED @ 3" OC. @ PANEL EDGES & @12" OC. @ INTERMEDIATE
SUPPORTS.
2.W-1 INDICATES 2x4 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
3.W-2 INDICATES 2x6 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
4.W-3 INDICATES (1x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES @, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-4 INDICATES (2x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-5 INDICATES VERSA STUD LVL 1 12" x 5 12" WITH 58" ZIP BD.
SHEATHING O(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH
SIDES , SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d
GALVANIZED COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
6.FOR ALL NON-BEARING STRUCTURAL SHEAR WALL USE 2x4@16" OC
WITH GYP BD. OR PLYWOOD NOTED ABOVE.
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
5
5
USE EVERY OTHER NAIL HOLE IN A
ROW TO PROVIDE THE
CODE-REQUIRED MINIMUM
CENTER-TO-CENTER SPACING FOR
NAILS
CUT
LENGTH
END
LENGTH
CLEAR
SPAN
END
LENGTHPROVIDE MINIMUM
7 8" END DISTANCE
EQUAL NUMBER OF
SPECIFIED NAILS IN
EACH END
.
1
A
B
2
C
ED
ELEVATOR
UNIT 15UNIT 16
UNIT 17
UNIT 18
HALLWAY
C20
C19
C18
16" FLAT TRUSS
FLOOR TRUSS @16" O.C.
W-2SW-1 UPSW-1 UP2K, 2J 2K, 2J0K, 4J2K, 2J 2K, 2J0K, 4J
2K, 2J 2K, 2J0K, 4J2K, 2J 2K, 2J0K, 4J
(2x) 2X10 HDR (2x) 2X10 HDR
(2x) 2X10 HDR (2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR2K, 2J(2x) 2X10 HDR2K, 2J(2x) 2X10 HDR2K, 2J(2x) 2X10 HDR2K, 2J
(2x) 2X10 HDR
2K, 2J
(2x) 2X10 HDR
(2x) 1 3 4" x 9 14" 2.0E LVL
(3x) 1 3 4" x 9 14" 2.0E LVL
16" FLAT TRUSS
FLOOR TRUSS @16" O.C.
S.400
DET. 1
S.400
3 12" x 3 12" 1.8E PSL
COLUMN TO DN
3 12" x 3 12" 1.8E PSL
COLUMN TO DN
WIND BLOKING@ 4'-0" MAX.W10x68 STEEL (A992)
3 12" x 3 12" 1.8E PSL
COLUMN TO DN
(2x) 1 3 4" x 9 14" 2.0E LVL
LU28
HANGER
(2x) 1 3 4" x 9 14" 2.0E LVL
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
3 12" x 3 12" 1.8E PSL
COLUMN TO UP
HSS4x4X3 8"
TO DW
ROOF TRUSS
BY TRUSS MANUFACTURERW-3W-3W-3
W-3
W-3
W-3
W-3
W-3
W-3W-3
W-3
W-3
W-2 W-2
W-2
W-2W-2
W-1W-1W-1W-1W-2W-2
CMU WALL
CMU WALLCMU WALLUNT 17
PROPOSED 4TH FLOOR
EL. 32 '- 0"
PROPOSED ATTIC
EL. 42 '- 8"
HVAC
EL. 46 '- 2"
ELEVATOR O.H.
EL. 44 '- 7"
A A1
2x6 @ 16" O.C.
W-3
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
DRAWN BY CHECKED BY -FH
S-400
7 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
KEY NOTES, 4TH FLOOR FRAME
PLAN VIEW AND DETAIL
4TH FLOOR FRAME PLAN VIEW
SCALE: 1/4" = 1'-0"
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
S.400
DET. 1 HIGH WIND STRAP DETAIL
NOT TO SCALE
210 NORTH STREET
Hyannis- MA
EXTERIOR WALL TYPE SCHEDULE
NOT TO SCALE
LEGEND:
#K, #J INDICATES KING/JACK STUD COUNT. USE 2K2J STUDS
WHERE NOT SPECIFICALLY NOTED.
11/05/20241 REVISION
11/19/20242 REVISION
01/24/20253 REVISION
03/31/20254 REVISION
WALL NOTES:
1.ALL EXTERIOR WALL SHOWN ARE 2x6 WITH 58" ZIP SHEATHING
IS NAILED TO STUDS WITH 10d GALVANIZED COMMON NAILS
SPACED @ 3" OC. @ PANEL EDGES & @12" OC. @ INTERMEDIATE
SUPPORTS.
2.W-1 INDICATES 2x4 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
3.W-2 INDICATES 2x6 @ 16" O.C WITH 12" GYP BD. SHEATHING ON
BOTH SIDES (@INTERIOR WALLS) OR 12" PLYWOOD ON BOTH SIDES,
SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
4.W-3 INDICATES (1x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES @, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-4 INDICATES (2x) 2x6 @ 16" O.C WITH 58" ZIP BD. SHEATHING
(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH SIDES, SHEAR
WALL SHEATHING IS NAILED TO STUDS w/ 10d GALVANIZED
COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
5.W-5 INDICATES VERSA STUD LVL 1 12" x 5 12" WITH 58" ZIP BD.
SHEATHING O(@EXTERIOR WALLS) OR 58" PLYWOOD ON BOTH
SIDES , SHEAR WALL SHEATHING IS NAILED TO STUDS w/ 10d
GALVANIZED COMMON NAILS @4" OC. @PANEL EDGES & @12" OC.
@INTERMEDIATE SUPPORTS.
6.FOR ALL NON-BEARING STRUCTURAL SHEAR WALL USE 2x4@16" OC
WITH GYP BD. OR PLYWOOD NOTED ABOVE.
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
5
5
1
A
B
2
C
ED 6" / 1'-0"6" / 1'-0"9" / 1'-0"6" / 1'-0"2 3/4" / 1'-0"2 3/4" / 1'-0"1/4" / 1'-0"1/2" / 1'-0"1/4" / 1'-0"ROOF TRUSS
BY TRUSS MANUFACTURER
ROOF TRUSS
BY TRUSS MANUFACTURER
ROOF TRUSS
BY TRUSS MANUFACTURER
W-3W-32x12 PT
ROOF DECK JOIST @12" O.C.
(3x) 1 3 4" x 11 7 8" 2.0E LVL
HGUS5.50/10
HANGER
(3x) 1 34" x 11 78" 2.0E LVL(3x) 1 34" x 11 78" 2.0E LVL(3x) 1 3 4" x 11 7 8" 2.0E LVL
LU28
HANGER
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
DRAWN BY CHECKED BY -FH
S-500
8 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
KEY NOTES, ROOF FRAME
PLAN VIEW AND DETAIL
ROOF FRAME PLAN VIEW
SCALE: 1/4" = 1'-0"
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
ROOF NOTE:
1. MEMBRANE ROOF UNDERLAY PER PRODUCT SPECIFICATIONS.
CONTRACTOR SHALL FOLLOW MANUFACTURER
RECOMMENDATIONS.
2. ICE AND WATER SHIELD 5/8" T&G ROOF SHEATHING.
3. SEE ARCHITECTURAL PLANS FOR ROOF SLOPE
4. RUBBER ROOF PITCHED TO FRONT GUTTER.
5. SEE ARCHITECTURAL PLANS FOR INSULATION
210 NORTH STREET
Hyannis- MA
11/05/20241 REVISION
11/19/20242 REVISION
01/24/20253 REVISION
03/31/20254 REVISION
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
L
DOWELS TO MATCH
VERTICAL REINF
VERTICAL WALL
REINF #5@32"
PROVIDE MIN OF 2 ADDL
VERT BARS @8" OC
EACH SIDE OF OPNG
UNLESS NOTED OTHERWISE
#9 GA WIRE
@16" OC
(DURO-WALL
OR EQUAL)
BOND BEAM REINF
WITH 2-#5 CONT
FLOOR
FLOOR
LINTEL
#3
SEE SCHED
END BEARING
SECTION
ELEVATION 778"58"2-#3
SEE SCHED
SEE SCHED
CONC BLOCK LINTEL
SPANS UP TO 5'-0"
CONC BLOCK LINTEL
SPANS OVER 5'-0" TO 9'-0"
#4@16"
SEE SCHED5
78"52-2x10 PT LEDGER
w/3 4"Ø EXPANSION
BOLTS @16" OC INTO
SOLID GROUTED CELLS
JOISTS
FINISH
3 4"T&G PLYWOOD
FINISH
3 4"T&G PLYWOOD
JOISTS
2-2x10 PT LEDGER
w/3 4"Ø EXPANSION
BOLTS @16" OC INTO
SOLID GROUTED CELLS
8" CMU w/ #5@24" V
+ #9 GAGE WIRE
LADDERS @16" OC
8" CMU w/ #5@24" V
+ #9 GAGE WIRE
LADDERS @16" OC
Foundation
bearing wall
Rim board
or beam
bearing wall
or beam
Foundation,
Typical
blocking
Wood beam
Hanger*
min. 1/8" space
9 1/2" and 11 7/8"
14" et 16"
joists - 3 nails
joists - 4 nails
Nails (0.120" x 3")
Clinch nails if necessary
Wood filler:
2 x 1/2" wood
sheeting x 3 1/2"
min. 2" from end
sheeting x 3 1/2"
1/2" wood
Wood Filler:
Wood Filler:
sheeting x 3 1/2"
2 x 1/2" wood
Only required if the hanger does not provide lateral support for the joist's top chord
Strongback
Joint cover: 32" of length, same
thickness and depth as strongbacks,
centered on splice.
Use gun nails 0.122" x 3.25" or 3" screws to secure strongbacks(s) at mid span of joist. If two strongbacks are specified, install the second one adjacent to the next closest diagonal
web bay.
OPTION 2(Better)
Attached to block
Reinforcements (may be required): See «Reinforcement» section of the
Analyzer software's report to have all material requirements (sizes,
quantities, etc.)
Rim board
Joist blocking for lateral wall
building code
bracing if required by localFoundation
wall or Beam
or bearing
or beam
Bearing wall
Rim board
2x6 flat
Never notch, cut or drill a joist member.
DRAWN BY CHECKED BY FH-
S-600
9 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
TYPICAL DETAILS AND NOTES
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
210 NORTH STREET
Hyannis- MA
CONCRETE LINTELS & TYP REINF ARRANGEMENT FOR CMU WALL
NOT TO SCALE
FLOOR JOIST CONNECTION AT CMU WALL TYP DETAIL
NOT TO SCALE
FLOOR TRUSS TYP. DETAIL
NOT TO SCALE
11/05/20241 REVISION
11/19/20242 REVISION
01/24/20253 REVISION
03/31/20254 REVISION
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
HEADER HANGER
HANGER
SISTER JOIST
(FULL LENGTH)
WOOD JOIST
SHEATHINGSHEATHINGNOTES:
1. CONNECT SISTER TO ADJOINING JOIST
WITH 2-ROWS OF 16d RING-SHANK NAILS
AT 16" ON CENTER, FULL LENGTH.
2. CONNECT ENDS OF SISTER JOISTS TO
SUPPORT TO MATCH ADJOINING JOISTS.
3. HEADER DEPTH AND NUMBER SHALL
MATCH ADJOINING FRAMING.
HEADER CRIPPLE STUDS
DOUBLE 2x TOP
PLATE
2x BLOCKING AT
PLYWOOD EDGES
JACK
STUDS
TYPICAL WALL
STUDS
JAMB
STUDS
P.T. 1-2x
SOLE PLATE
NOTES:
1. REFER TO HEADER SCHEDULE FOR
HEADER, JACK AND JAMB SIZES.
2. REFER TO ARCHITECTURE DRAWINGS
FOR SIZE AND LOCATION OF OPENINGS.
3. FOR ANCHOR BOLT SIZE AND SPACING
REFER TO NOTES AND SECTIONS.
HEADER CRIPPLE STUDS
DOUBLE 2x TOP
PLATE
2x BLOCKING AT
PLYWOOD EDGES
JACK
STUDS
TYPICAL WALL
STUDS
JAMB
STUDS
P.T. 1-2x
SOLE PLATE
NOTES:
1. FOR HEADER, JACK AND JAMB SIZE AND
NUMBER REFER TO HEADER SCHEDULE.
FOR # OF STUDS REFER
TO PLAN AND/OR
SECTIONS, TYP.
SIMPSON HOLD DOWN
OR SIMILAR
12" ANCHOR BOLT
EMBEDDED IN
CONCRETE MIN. 7"
EACH COLUMN
PLYWOOD SHEATHING
REFER TO HEADER
SCHEDULE FOR SIZE
2x6 STUD WALL
2x6 PLATE
12" PLYWOOD
SPACERS
2x6 PLATE
4'-0"
MIN. STUD SPLICE
15"16"
TYP.15"16"TYP.1
1
DOUBLE 2X TOP PLATE
MINIMUM AT ALL WALLS
STUD WALL, FOR SIZE
AND SPACING REFER
TO PLANS
LAP TOP PLATE AT ALL
CORNERS AND
INTERSECTIONS
3 STUD MIN. AT
ALL CORNERS
WOOD BEAM
WOOD COLUMN
SIMPSON ECC POST CAP
OR SIMILAR
FLOOR
SHEATHING
BEAMSIMPSON HANGER
OR SIMILAR
EACH JOIST
JOIST JOIST
FACE MOUNT
HANGER
TOP MOUNT
HANGER PROTECT UNTREATED WOOD
FROM DIRECT CONTACT WITH
CONCRETE
BEARING FOR DOOR
OR WINDOW HEADER
STRAP PER CODE IF TOP
PLATE IS NOT CONTINUOUS
OVER HEADER
BEAM TO BEAM
CONNECTION
BEARING AT
CONCRETE WALL
COLUMN
BEARING AT WALL
118" TJ® RIM BOARD OR
114" OR 1 12" OR BLOCKING FOR
LATERAL SUPPORT
STRAP PER CODE IF TOP
PLATE IS NOT CONTINUOUS
OVER COLUMN
ASSEMBLY A
2 PCS.
ASSEMBLY B
3 PCS.
ASSEMBLY C
4 PCS.0"0"0"0"0"0"3" MIN.
CONCRETE
SIMPSON CBS FOR
CONCRETE OR ABU FOR
WOOD POST BASE
OR SIMILAR
WOOD COLUMN
1'-0"
TYPICAL
1'-0"
TYPICAL 0"0"NOTES:
1. ABOVE NAIL PATTERN APPLIES TO ALL
BEAMS (3 PLY AND LESS).
2. ALL NAILS TO BE 16d SINKERS.
3. CENTER ROW OF NAILS MAY BE OMITTED
FOR BEAM DEPTHS OF 9-1/2" AND LESS.
4. THE NAIL PATTERN SHOWN APPLIES TO
BOTH SIDES PF A THREE MEMBER BEAM.
5. CONSTRUCTION ADHESIVE TO BE USED
BETWEEN PLIES.
PSPN516Z MSTC
NS1
RPS28Z
PSPN58Z
NS2
NS2 SS1.5
NS1
HSS2-
SDS1.5
PSPN516Z
ELECTRICAL
WIRING
HSS2-3-SDS3
LOAD BEARING WALL
(WITH HVAC CHASE)
RPS28
CTS218
1
4
4
3
2
4
6
4
5
2
7
8
1
HVAC CHASE
(2)
ADJACENT
STUD BAYS
3-16d
FASTENERS
EVERY 16"
9
SUPPLY LINES
WATER OR
VENT PIPE
TO 2ND
FLOOR
WIDE FLANGE BEAM
SEE PLANS
FLOOR
JOISTS
SEE PLANS
SILL PLATE
W/ 58" CROSS
BOLT @ 12"
OC.
JOIST
WIDE FLANGE
BEAM
SEE PLANS
SILL PLATE
AS REQ'D
3 8" BOLTS
FLOOR
SHEATHING
HSS COLUMN
SEE PLANS
10"x10"x38"
STEEL PLATE
(4x) 3/8" Ø BOLT
EMBED. 7" IN CONCRETE
E70xx
14
BOTH SIDES (TYP.)
FOUNDATION
SEE PLANS
(4x) 3/8" Ø BOLT
EMBED. 7" IN CONCRETE
HSS COLUMN
214"214"512"134"134"634"E70xx
1 4
DRAWN BY CHECKED BY FH-
S-601
10 OF 10DATEAUG 21 2024
PROJECT NAME:
No. REVISION DATE
SHEET
SHEET Nº
DRAWING TITLE:
STRUCTURAL
TYPICAL DETAILS AND NOTES
FRAMING AROUND
OPENINGS
NOT TO SCALE
WOOD FRAMING FOR
DOOR OPENING
NOT TO SCALE
WOOD FRAMING FOR
WINDOW OPENING
NOT TO SCALE
HOLD DOWN DETAIL AT
SHEAR WALL
NOT TO SCALE
TYPICAL DOOR/WINDOW
HEADER DETAIL
NOT TO SCALE
TYPICAL CORNER STUD LAYOUT
AND TOP PLATE SPLICE
NOT TO SCALE
BEAM CONNECTION
DETAIL
NOT TO SCALE
KEY NOTES
THE DRAWING REPRESENT CONSTRUCTION IN SCALE BUT DO NOT "SCALE"
DRAWINGS TO OBTAIN MISSING INFORMATION OR TO INTERPRET ANY
INFORMATION NOT SPECIFICALLY DIMENSIONED FOR EXACT DETAILING,
FABRICATION OR CONSTRUCTION PURPOSES. CONTACT THE DESIGN
ENGINEER FOR ANY REQUIRED MISSING DIMENSIONS.
THE CONTRACTOR SHALL OBTAIN ALL PERMITS FROM THE BUILDING
DEPARTMENT PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD
PRIOR TO COMMENCING WORK. VERIFY AND CONFIRM ALL DIMENSIONS,
ELEVATIONS AND LOCATIONS OF EXISTING BUILDINGS AND OTHER
STRUCTURES PRIOR COMMENCING THE WORK. DISCREPANCIES SHALL BE
REPORTED TO THE DESIGN ENGINEER IMMEDIATELY, BEFORE
PROCEEDING.
THE CONTRACTOR ARE RESPONSIBLE FOR ACCURATE COORDINATION OF
ALL RELATED PROJECT DRAWINGS, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, STRUCTURAL, CIVIL AND UTILITIES DRAWINGS. THE
CONTRACTOR SHALL VERIFY ALL DETAILS, DIMENSIONS AND SYSTEMS
PRIOR WORK OR ORDERING ANY ITEM AND COORDINATE WITH THE
ARCHITECT OR THE RELATED ENGINEER. DO NOT COMMENCE WORK
UNTIL CONDITION IS RESOLVED AND MODIFICATION IF NEEDED IS
APPROVED. ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES THAT
MAY EXIST PRIOR TO COMMENCING THE WORK.
THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND
BRACING REQUIRED FOR PLUMPNESS, STRUCTURAL STABILITY AND
SAFETY WHENEVER REQUIRED TO SUPPORT LOADS AS MAY BE IMPOSED
UPON THE STRUCTURE AND ITS COMPONENTS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE SAFETY
OF ADJACENT STRUCTURES, PROPERTY, HIS WORKMEN, AND THE PUBLIC,
AS AFFECTED BY THE CONSTRUCTION OF THIS PROJECT.
THESE DRAWINGS ARE INTENDED TO BE USED ONLY BY EXPERIENCED
CONTRACTOR WITH KNOWLEDGE ON THIS TYPE OF WORK. CONTRACTOR
SHALL UNDERSTAND THE COMPLEXITIES OF THE PROJECT AND THE
CONSTRUCTION SEQUENCE . THE CONTRACTOR ASSUMES TOTAL
RESPONSIBILITY FOR ANY CONSEQUENCE OF THAT ACTION.
NOTE:
SOME FEATURES ARE NOT SHOWN FOR CLARITY.
SEE ALL PROJECT PLANS, SECTIONS AND DETAILS FOR
COMPLETE UNDERSTANDING. CONTACT ENGINEER FOR
CLARIFICATIONS IF NECESSARY.
WOOD BEAM CONNECTION DETAIL
NOT TO SCALE
MULTIPLE LVL FASTENING SCHEDULE
MULTIPLE
ASSEMPLY
NAILED CONNECTION THROUGH BOLTED CONNECTION
2 ROWS 16D (3 12")
COMMON WIRE
@12" C-C
3 ROWS 16D (3 12")
COMMON WIRE
@12" C-C
2 ROWS 12"
BOLTS
@24" C-C
2 ROWS 12"
BOLTS
@12" C-C
UP TO 8"A & B - - -
8" TO 12" A B C -
12" TO 18" - A & B - C
NOTE:
1. BOLTS ARE TO BE MATERIAL CONFORMING TO ASTM STANDARD A307 (MACHINE BOLTS).
BOLT HOLES ARE TO BE THE SAME DIAMETER AS THE BOLT, AND LOCATED 2" FROM THE TOP
AND BOTTOM OF THE MEMBER. WASHERS SHOULD BE USED UNDER HEAD AND NUT.
2. FOR A THREE PIECE MEMBER, THE NAILING SPECIFIED IS FROM EACH SIDE.
3. VALUES IN TABLE ARE FOR DRY SERVICE CONDITIONS ONLY. FOR SERVICE LEVEL 2
CONDITIONS MULTIPLY TABLE VALUES BY 0.7.
POST BASE & CAP DETAIL
NOT TO SCALE
BEAM NAILING PATTERN DETAIL
NOT TO SCALE
OPENINGS ASSEMBLY
NOT TO SCALE
NOTE:
1. RPS28 (16 GAUGE) TO REINFORCE TOP PLATE, AND RPS28Z (16
GAUGE ZMAXTM) TO REINFORCE SILL PLATE. INTERNATIONAL
RESIDENTIAL CODE - 2015/2018 R602.6.1. INTERNATIONAL
BUILDING CODE - 2015/2018 2308.5.8.
2. PSPN516Z (16 GAUGE ZMAX
TM) AT TOP OR BOTTOM PLATES
INTERNATIONAL RESIDENTIAL CODE- 2015/2018 P2603.2.1,
R602.6.1 AND M1308.2. INTERNATIONAL BUILDING CODE -
2015/2018 2308.5.8. INTERNATIONAL PLUMBING CODE -
2015/2018 305.8. INTERNATIONAL MECHANICAL CODE -
2015/2018 305.5
3. PSPN58Z (16 GAUGE ZMAX
TM) AT TOP OR BOTTOM PLATES
INTERNATIONAL RESIDENTIAL CODE - 2015/2018 P2603.2.1 AND
M1308.2. INTERNATIONAL PLUMBING CODE - 2015/2018 305.8.
INTERNATIONAL MECHANICAL CODE - 2015/2018 305.5.
4. NS - NAIL STOPS TO PROTECT PIPING FROM DRYWALL NAILS
OR SCREWS. INTERNATIONAL RESIDENTIAL CODE - M1308.2
AND P2603.2.1. NATIONAL ELECTRIC CODE - 2014/2017 300.4.
INTERNATIONAL PLUMBING CODE - 2015/2018 305.8.
INTERNATIONAL MECHANICAL CODE - 2015/2018 305.5
5. SS1.5 (16 GAUGE) STUD SHOES REINFORCE AND PROTECT
PLUMBING IN 2X. INTERNATIONAL RESIDENTIAL CODE -
2015/2018 R602.6 AND M1308.2 INTERNATIONAL BUILDING CODE
- 2015/2018 2308.5.8, 2308.5.9 AND 2308.5.10 INTERNATIONAL
PLUMBING CODE - 2015/2018 305.8. INTERNATIONAL
MECHANICAL CODE - 2015/2018 305.5
6. HSS2-SDS1.5 (16 GAUGE) HEAVY STUD SHOES TO REINFORCE
AND PROTECT SINGLE 2X STUDS WHERE PIPE IS LOCATED.
USES (12) SDS 14" x 112" SCREWS (INCLUDED). INTERNATIONAL
RESIDENTIAL CODE - 2015/2018 R602.6 AND M1308.2
INTERNATIONAL BUILDING CODE - 2015/2018 2308.5.8, 2308.5.9
AND 2308.5.10 INTERNATIONAL PLUMBING CODE - 2015/2018
305.8 IINTERNATIONAL MECHANICAL CODE - 2015/2018 305.5
7. HSS2-3-SDS3 (16 GAUGE) HEAVY STUD SHOE FOR TRIPLE 2X
STUD. USES (12) SDS 14" x 3" SCREWS (INCLUDED).
INTERNATIONAL RESIDENTIAL CODE - 2015/2018 R602.6 AND
M1308.2. INTERNATIONAL BUILDING CODE - 2015/2018 2308.5.8,
2308.5.9 AND 2308.5.10. INTERNATIONAL PLUMBING CODE -
2015/2018 305.8. INTERNATIONAL MECHANICAL CODE -
2015/2018 305.5.
8. MSTC (16 GAUGE) AT TOP PLATE INTERNATIONAL RESIDENTIAL
CODE - 2015/2018 R602.6.1. INTERNATIONAL BUILDING CODE -
2015/2018 2308.5.8.
9. CTS218 (14 GAUGE) TO REINFORCE TOP-PLATE FOR BOTH
COMPRESSION AND TENSION FORCES SPECIAL DESIGN
PROVISIONS FOR WIND AND SEISMIC-2015 4.1.4.
INTERNATIONAL RESIDENTIAL CODE - 2015/2018 R602.6.1.
INTERNATIONAL BUILDING CODE - 2015/2018 2308.9.8
210 NORTH STREET
Hyannis- MA
STEEL BEAM CONNECTION DETAIL
NOT TO SCALE
COLUMN BASE PLATE DETAIL
NOT TO SCALE
11/05/20241 REVISION
11/19/20242 REVISION
01/24/20253 REVISION
03/31/20254 REVISION
Engineering Design
+1 (978) 870-6327 | info@buildoneeng.com
06/30/20255 REVISION
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulng & Engineering, P.C.
PRELIMINARY EXPERT REPORT
RE: 210 North Street
Hyannis, Massachusetts
Barnstable County
CCA Project No.: C002650
EXHIBIT C
Original Building Drawings
P-00039
P-00040
P-00041
P-00042
P-00043
P-00044
P-00045
P-00046
P-00047
P-00048
P-00049
P-00050
P-00051
P-00052
P-00053
P-00054
CO | FL | MA | NY | TX WWW.CCACO.COM
Engineering Services in NY will be provided by CCA Consulng & Engineering, P.C.
PRELIMINARY EXPERT REPORT
RE: 210 North Street
Hyannis, Massachusetts
Barnstable County
CCA Project No.: C002650
EXHIBIT D
Select Aperture Structural Calculations