February 14, 2001
Edward Pesce
Horsley & Witten, Inc.
90 Route 6A, Unit 1
Sandwich, MA 02563
RE: 19 Great Bay Road, Osterville
Dear Mr. Pesce:
Your request for a variance to install a soil absorption system only four (4) feet .
above the maximum adjusted groundwater table at 19 Great Bay Road,
Osterville, is'not granted.
The engineered plan shows a proposed pump chamber after the 1,500 gallon
capacity septic tank. Therefore, it is feasible to raise the soil absorption system
one more foot in order to achieve five (5) feet above the maximum adjusted
groundwater table as required.
The applicant expressed concern .over the aesthetics of raising the system and
the removal of some trees if the soil absorption system is required to be raised
one more foot. The Board of Health members are of the opinion that the plan
must be revised, regardless of aesthetics, to meet the maximum feasible
compliance standards contained within the State Environmental Code, Title V.
Sincerely yours,
Susan G. Rask, R.S.
Chairman
Board of Health
Town of Barnstable
SGR/bcs
bayroad
� � I
RECEI r E —] DATz, 1/12/01
i
L N 16 2001 1 FEB:
>~AM Town
0
rEa�y A� 0 L.'1�- � Ie RAC. BY
.i�.i~:JLI
Board of Health
367 Main Street, Hyannis MA 02601
Ofriiee: 508-790-6265 Susan 0.Rask.R.S.
FAX: 508-790-6304 Sumner Kaufman,M.S.P.H.
Ralph A.Murphy,M.D.
VARIANC
.+.
LOCATION -
Property Address: 19 Great Bay Road
Assessor's Map and Parcel Number: Map 93, Parcel'1 ,2 Size of Lot: 19,762 S.F.
Wetlands Within 300 Ft. Yes Subdivisjon Name:
No X
Business Name:
APPLICANT CONTACT PERSON
Name: Paul Ocglesby Name: John Churchill, Ho=le & W'y itten, Inc.
Address:10 IaT"cod 1-k., , N1 02090 Address: 90 Rt. 6A, Ulit 1, SaIrMch, M -02563
Phone: Phone: (508) 833-6
FAX: FAX: (508) 833-315f;
VARIANCE,FROM REGULATION(Lin Reg.) REASON.FOR VARIANCE(May attach ifmore space needed)
A varience from 310 CMR
15 . 212 is allowed under Maximum FPaGihlP Cc)mnlianr-P
310 CMR 15. 4Q4
Clrecklisl(to be completed by office staff-person receiving variance request application)
Four(4)copies of plan submitted(including septic system.plans and/or restaurant floor plans)
Applicant understands that the abutters must be notified by certified mail at least ten days prior to meeting
date at applicant's expense(for Title V and/or local sewage regulation variances only)
Full menu submitted(for grease trap variances only)
Variance request application fee collected{nareererxregoare ne . ,t�, .;,r,�,,.a„nft„AW%hj MC ,+e„ae9*L,w,WC
dining variance renewab(came o wner/lemes amiyl end vujaa a to repair rolted imp dhpc-+al aptcruq(aoly 1trm orpmulm to*4 bnlAng psmpondD
Variance request submitted at least.15 days prior to meeting date
VA CB APPROVE Susan G. Rask,M.,Chah-man
T APPROVED Sumner Kaufhwa,M.S.P.N.
REASON FOR DISAPPROVA S RaJ h A.Murphy,Zrl.D.
0 1/WP/VARIREQ
January 12, 2001
Mr. Thomas McKeon TOWN OF BARrv,;IABI E
Barnstable Board of Health HEALTH DEPT.
376 Main Street
Horsley&Witten, Inc. Hyannis, MA 02601
Svrtnnt Hill
90 Route 6A Re: 19 Great Bay Road, Osterville, Massachusetts
Sandwich,MA
02563 Dear Mr. McKeon,
(508)833-6600 Please find enclosed,four copies of the design plans and associated tide
Fax(508)833-3150 fluctuation calculations for 19 Great Bay Road for your review and approval.
Also, this project requires an approval of a variance by the Board of Health.
The subject property is located on a peninsula in the village of Osterville. The
estimated seasonal high groundwater was determined based upon recorded
tidal fluctuations for this area. The definition for groundwater influenced by
tidal action, as stated in 310 CMR 15.002,is "the average of the monthly spring
tide high groundwater level as recorded over the most recent consecutive 19-
year period." Using the definition of high groundwater elevation for coastal
areas, we developed the attached calculation.
Thank you for your assistance with this project, and please call if you have any
questions.
Sincerely,
HORSLEY &WITTEN,INC. .
ward L. Pesce, P.E.
Senior Environmental Engineer
JLC
oEtt+� RECE DATE: 1/12/01
� l
• uwvereaiz.
` 59. °�' Town o o ,¢,
1Dlep�yA ,.,atele RISC. BY
I
Board ®f Health
367 Main Street, Hyannis MA 02601
Once: 508-790-6265 Susan 0.Rask,R.S.
FAX: 508-790-6304 Sumner Kaufhtan,M.S.P.H.
Ralph A.Murphy,M.D.
VARIANCE REQUEST FORM.
LOCATION
Property Address: 19 Great Bay Road
Assessor's Map and Parcel Number: Map 93, Parcel 1 ,2 Size of Lot: 19,762 S.F.
Wetlands Within 300 Ft. Yes Subdivision Name:
No X
Business Name:
APPLICANT CONTACT PERSON
Name: Paul Oglesby Name: John Churchill Horsley & Witten, Inc.
Address:10 La4ccd Dr., , PA 02090 Address: 90 Rt. 6A, Lhit 1, S��Ch, MA 02563
Phone: Phone: (508) 833-6600
FAX: FAX: (508) 833-3150
VARIANCE FROM REGULATION(Ust Reg.) REASON.FOR VARIANCE(May attach if more space needed)
A varience from 310 CMR
15. 212 is allowed under Maximum Feasible Comn1ianra
310 CMR 15. 404
Checkli'sl(to be completed by office staff-person receiving variance request application)
Four(4)copies of plan submitted(including septic system plans and/or restaurant floor plans)
Applicant understands that the abutters must be notified by certified mail at least ten days prior to meeting_
date at applicant's expense(for Title V and/or local sewage regulation variances only)
Full menu submitted(for grease trap variances only)
Variance request application fee collected(.reeib,Hrq wmanmdoe a &Kva., pmiNwe„ b["me0"W,k„«,uy,(,MOW
dining variance renewah fume owwfieaue only),and vulaam to mpalr Palled aewap d'spmd rjtWm(only Ireo oxparW=b do twibdmp propmed))
Variance request submitted at least 15 days prior to meeting date
VARIANCE APPROVED Susan G.Rask,R,S.,Chairman
NOT APPROVED Sumner➢Gateman,
REASON FOR DISAPPROVAL Ralph A.Murphy,M.D.
�r/t�QlvaxaRs4
January 12, 2001 a
JAN, � �;it13 �
i.
Mr. Thomas McKeon TOWHE�LTH CEP7A8!E
Barnstable Board of Health
376 Main Street
Horsley&Witten, Inc. Hyannis, MA 02601
Saxtant Hill
90 Route 6A Re: 19 Great Bay Road,Osterville, Massachusetts
Sandwich,MA
02563 Dear Mr. McKeon,
(508)833-6600 Please find enclosed,four copies of the design plans and associated tide
Fax(508)833-3150 fluctuation calculations for 19 Great Bay Road for your review and approval.
Also,this project requires an approval of a variance by the Board of Health.
The subject property is located on a peninsula in the village of Osterville. The
estimated seasonal high groundwater was determined based upon recorded
tidal fluctuations for this area. The definition for groundwater influenced by
tidal action, as stated in 310 CMR 15.002, is "the average of the monthly spring
tide high groundwater level as recorded over the most recent consecutive 19-
year period." Using the definition of high groundwater elevation for coastal
areas,we developed the attached calculation.
Thank you for your assistance with this project, and please call if you have any
questions.
Sincerely,
HORSLEY.&WITTEN,INC.
w r .-
d L. Pesce,P.E.
Senior Environmental Engineer
JLC
,
j
Septic System Upgrade
. 19 Great Bay Road
Osterville, Mass. 02655
� Previous 19_Year Sprmba
Tide Fluctuations
HyannisPort, Mass.
I
Jun-82 4.76
Jan-83 4.72
Oct-84 4.71
Nov-85 4.81
May-86 4.71
Jan-87 4.61_
Oct-88 4.58
Oct-89 4.76
i
Apr-90 4.74
Jan-91 4.63
Jan-92 4.7
Oct-93 4.84
Apr-94 4.89
Dec-95 4.86
Jan-96 4.82
Feb-97 4.81
j Nov-98 4.91
May-99 4.88 .
Jul-00 '4.7.6
Average.Tide-
Flucuations ,;:, . 4.76
I `
, j
j Estimated High Groundwater Elevation= Average Tidal Flucuation/2
= 2.38 feet above mean sea level
3
6 2001 11
.;rfi
Horsley&Witten, Inc.
Septic System Upgrade
19 Great Bay Road
Osterville, Mass. 02655
Previous 19-Year Spring Tide Fluctuations
HyannisPort, Mass.
11 ewmh
g w
mh
Jun-82. 4.76
Jan-83 4.72
Oct-84 4.71
Nov-85 4.81
May-86 4.71
Jan-87 4.61
i Oct-88 4.58
Oct-89 4.76
Apr-90 4.74
Jan-91 4.63
Jan-92 4.7
Oct-93 4.84
Apr-94 4.89
Dec-95 4.86
Jan-96 4.82
Feb-97 4.81
j Nov-98 4.91
May-99 4.88 ,
Jul-00 4.76
Average Tide
Flucuations 4:76
i
I
Estimated High Groundwater Elevation= Average Tidal Flucuation/2
= 2.38 feet above mean sea level
II !R:.timr
N, i6"i
Horsley& Nitten,
Inc.
Town of Barnstable P# qb(;I-)
Department of Health,Safety,and Environmental Services
�1HE} Public Health Division Date )111q)C0
, 0. 367 Main Street,Hyannis MA 02601
R
• BARNsrABLK
6 9 Date Scheduled NoV--erJ b. r /19 r`2060 Time' 10=y0 Fee Pd.
ATFD 1 M't�
Soil'Suitability Assessment for Sewage Disposal
Performed By: do}1!1 L6UrfG�I ( 1 f Witnessed By: Do an IL /''ll0 r q nd 1 ,
LOCATION & GENERAL INFORMATION
.
Location Address o Owner's Name
1I Cyrcm} 6%Y FOQJ (�8#tsby Piz,
Oslw-4''4c jAA 02bI65 Address 10 Lon9WocJ Dnv-G0 W e6tw--J
MA a-iogo
Assessor's Map/Parcel: 43 Engineer's Name a Oohn_ L'. Chwch i 11�_jc _
NEW CONSTRUCTION REPAIR Telephone# ( $O$) -y-2.3 — L'Goo
Land Use V,3,f Slopes(%) "!p Surface Stones 1
Distances from: Open Water Body WO O ft Possible Wet Area 0 0 ft Drinking Water Well ft 1
Drainage Way ft Property Line Z ft Other It
SKETCH:(Street name,dimensions of lot,exact locations of test holes&pert tests,locate wetlands in proximity to holes)
Tf#3. 401
w0 i
41
A
o cA .
~C 00
.1 N
0
roe c.8
igo.ao
N326Of 0 j°E LIer,
• IY�o�eQ
GrRE A T 94� Q,oA
Parent material(geologic) Oc.e 05Y1__, Depth to Bedrock 10
1
Depth to Groundwater: Standing Water in Hole: 1A 1 Weeping from Pit Face
Estimated Seasonal High Groundwater cL 2396 AS
... .. .. ..
METER Tt1�iA 'ION> O�SEA 'NAB � H wNr9k`Y'ABL
- .. V. :'..: .. ...:: :i ...
Method Used. haIA6 t11�PhiP S�sen9 'fide, Flue µa ton�
Depth Observed standing oniding bs hole: 4A in. Depth to soil mottles: in.
Depth to weeping from side of obs.hole: in. Groundwater Adjustment frSS ft.
Index Well# __-,. Rrading Date:.___._-_ Index Well level Adj.factor Adj.Groundwater Level
»pEROLATION TEST : Datr;al'. Vine lc � J
Observation
Hole# Time at 9"
Depth of Perc 36 i �7 j/ ` Time at 6"
x
Start Pre-soak Time @ 1030 Time(9"-6")
End Pre-soak lo3
Rate Min./Inch rn,n b 1 h
Site Suitability Assessment: Site Passed Site Failed: Additional Testing Needed(Y/N)
Original: Public Health Division Observation Hole Data To Be Completed on Back j
Copy: Applicant
DEED' OBSERVATION HOLE LOG Mote##; _
..... ... . .
Depth from Soil Horizon Soil Texture Soil Color Soil Other
Surface(in.) (USDA) (Munsell) Mottling (Structure,Stones,Boulderes.
Consistency.%Gravel
(3li-12- A Lackmg So J
30't-l2o' -�.. �Pdium �orr� •1,5 >�, r1�b
I,
r
DEEP OBSlERVATION HOIaE LOG Hole#
Depth from Soil Horizon I Soil Texture r
p � Soil Color Soil _ Other ,
Surface(in.) t _ (USDA) (Munsell) Mottling (Structure,Stones,Boulderes.
" Consistencv.° Gravel)
DEEP OBSERVATION HOLE LO;C Hole#
.
Depth from Soil Horizon Soil Texture Soil Color` Soil Other"
Surface(in.) (USDA) (Munsell) Mottling (Structure,Stones,Boulderes,
n i tenc ° Gravel
- r
I
I �
DEEP OBS;�ERV,ATION HOLE LOiG Mole
�.
Depth from Soil Horizon Soil Texture Soil Color Soil Other
Surface(in.) ((USDA) (Munsell) Mottling (Structure,Stones,Boulderes.
Consistency. Gravel)
Flood Insurance Rate.N apq
Above 500 year flood boundary No— Yes
Within 500 year boundary No— Yes
Q Within 100=yearTood boundary No_ Yes
Depth of Naturally Occurring Pervious Material
fP
Does at least four feet of naturally occurring pervious material exist in all areas observed throughout the
area proposed for the soil absorption system? S
If not,what is the depth of naturally occurring pervious material?
Certification
I certify that on 'q 7 (date)I have passed the soil evaluator examination approved by the
Department of Environmental Protection and that the above analysis was performed by me consistent with
the required training,expertise appd expprience described in 310 CMR 15.017.
Signature Date z o
TOWN OF BARNSTABLE
LOCATION 1�?—(;X eAf R Dr SEWAGE #
VILLAGE Q me. y-lzz P ASSESSOR'S MAP & LOT P '3 —00/
INSTALLER'S NAME&PHONE NO. -7 7S 3 3 3 8-
SEPTIC TANK CAPACITY o-f®0 g CIZA4,QeR A O
LEACHING FACILITY: (type)C UL �P C (size)
NO. OF BEDROOMS 3
BUILDER OR WNER
PERMITDATE: `` 2'���I COMPLIANCE DATE: _3 ,J�
Separation Distance Between the:
Maximum Adjusted Groundwater Table and Bottom of Leaching Facility Feet
Private Water Supply Well and Leaching Facility (If any wells exist
on site or within 200 feet of leaching facility) Feet
Edge of Wetland and Leaching Facility(If any wetlands exist
within 300 feet of leaching facility) Feet
Furnished by
fy
6
No. � THE COMMONWEALTH OF MASSACHUSETTS FEE $ 50.00
BOARD OF HEALTH
Town OF Barnstable
APPLICATION FOR DISPOSAL SYSTEM CONSTRUCTION PERMIT
Application for a Permit to Construct ( ) Repair (X) Upgrade ( ) Abandon ( ) -#]Complete System ❑Individual Components
19 Great Bay Road � � Paul Oglesby
MAP 93, Parcel 1 ,2 Location 10 Ia7LJDDOd Drive, Wn ` ; 02090
6 Map/Parcel# Address
Lot# Telephone#
.T Macomber & Sony Horsley & Witten, Inc.
Name Name
P.O. Box 66, Centellrville, MA 02632 90 Route 6A, Unit 1S, Sandwich, MA 02563
Address Address
(508) 775-3338 (508) 833-6600
° Telephone# Telephone#
Type of Building: Single Family Home Lot Size 19,762 Sq.feet
Dwelling—No.of Bedrooms 3 Garbage Grinder ( )
Other—Type of Building No.of persons 4 Showers ( ), Cafeteria ( )
Other fixtures
Design Flow(min.required) 330 gpd Calculated design flow gpd Design flow provided 344.5gpd
Plan: Date 12/27/00 Number of sheets 1 Revision Date
Title Proposed Septic System Uperade
Description of Soils)_ Textural Class I
Soil Evaluator Form No.P-9884 Name of Soil EvaluatorJohn Churchill Date of Evaluation 11 14 00
DESCRIPTION OF REPAIRS OR ALTERATIONS This proj ect is necessary for the upgrade
of an existing failed septic system. r
The undersigned agrees to install the above described Individual Sewage Disposal System in accordance with the provisions of
TITLE 5 and further agrees not place the system no lion until a Certificate of Compliance has been issued by the Board of Health
Signed / Date ?
I s
FORM t - APPLICATION FOR DSCP DEP APPROVED FORM 5/96
No. �� � THE COMMONWEALTH OF MASSACHUSETTS FEE $ 50.00
.� Ra BOARD OF HEALTH ..
TAM - OF 1 a tabie 7
APPLICATION FOR DISPOSAL,SYSTEM C:ONSTRUCTION PERMIT
y Application for Permit to Construct ( ) Repair (�'X) Upgrade ( ) Abandon (" ) - t Complete System ❑Individual,Components
19 Great Bali Road, �c-,"��, Paul Oglesby
Location Nark 0��
MAP 93,,- Parcel_,l., L�fdood Drive, W�s�, LVA
x
`'-Mtap/Par'cel#G f y•d Address
-'t36t4 Telephone#
J-P- Maconber-A Sons Horsley_ & Witten, Inc.
` . Installer's Name Designer's Name
P. Box 66, Centerville, MA 02632 90 RdUtet.6A, Unit 1, Sandwich, MA 02563
(508) 775-3338 Address Address
Telephone# Telephone#
Type of Building: Single Family Home Lot Size 19,762 Sq.feet
Dwelling—No.of Bedrooms 3 Garbage Grinder ( )
Other—Type of Building No.of persons ; 4 Showers ( ), Cafeteria ( )
Other fixtures
Design Flow(min.required) 330 gpd Calculated design flow gpd Design flow provided 344.5gpd
Plan: Date 12/27/00 Number of sheets 1 Revision Date
Title Proposed Septic System Upgrade
Description bf°'Soil(s)_ Textural Class I
Soil Evaluator Form No.P-9884 Name of Soil EvaluatorJOhn GhurChill Date of Evaluation 11/14 00-
DESCRIPTION OF REPAIRS OR ALTERATIONS This project is necessary f6r,,the upgrade
l of an existing failed septic system.
• t �inJ ✓a?/� ' z 7 0
The undersigned agrees to install the above%described Individual Sewage Disposal System in accordance with the provisions of
li TITLE 5 and fu era agrees not lace the s stem'n o`' tion until a Certificate of Compliance has been issued by the Board of Health
9 P y P
I
Signed l Date 1-%
s
I s
FORM t - APPLICATION FOR DSCP w ..DEP APPROVED FORM 5/96
_ p -
- �No. �� -' THE COMM- N- E5ALTH OF MASSACHUSETTS FEE
r BOARD OF HEALTH
CERTIFICATE OF COM LIANCE
Description of Work: ❑ Individual Component(s) omplete System --
The undersigned hereby c rtify that the Sewage,-Disposal System;Constructed( );Repaired( ),Upgraded( ),Abandoned( )
A
by Ao
{ at
has been installed in accord ce with the rovisions of 310 CMR 1 .00 (Title 5) and the approved design lans/as-built
plans relati to applicatiotal ,�f� lei ated /,�r 4,/p proved Design Flow � (gpd) '
Install
Desig r:J � /T Inspector - Date ? 141
i. The issuance of is certificate shall not be construed as a guarantee that the system will function as-designed.
FORM 3 - CERTIFICATE OF COMPLIANCE DEP APPROVED FORM 5/96 16v 3/n/o/
I
No. i0 i HE COMMONWEALTH OF MASSACHUSETTS FEE ,
BOARD OF HEALTH
DISPOSAL SYSTE ONSTRUCTION PERMIT
Permission is hereb gr . ted to Constr ct ( ) pair ') upgrade ( )t Abandon )' an individual sewage
disposal system at, s. as described t
in the application for Disposal System Construction Pyermit No.;Fael dated
Provided: Construction shall be completed within three years:-of the date of this'periaij.All local conditions must be met.
Date �-" �� ..r- ��/`5r'S • -; Board of HealtL
FORM 2 - DSCP DEP APPROVED FORM 5/96
TM
FORM 1255 (REV 5/96) H&V✓ HOBBS&WARREN PUBLISHERS- BOSTON
e
i-
r
- TOWN OF BARNSTABLE
LOCATION 1/ G ieeA1 624 SEWAGE #
VILLAGE Q Sre.& V LL e ASSESSOR'S MAP & LOT Qq3 —poi
INSTALLER'S NAME&PHONE N0. } /illa-w-,
SEPTIC TANK CAPACITY J`_ G�(1� C#A.� /2? � / O 0! LEACHING FACILITY:-(type)? V/- C (size) / 0 0 R
i NO. OF BEDROOMS r3
_BUILDER OR
PERMIT DATE: j_ ZS °! COMPLIANCE DATE: 3
Separation Distance Between the:
_.:..: Maximum Adjusted Groundwater Table and Bottom of Leaching Facility. - Feet
Private Water Supply Well and Leaching Facility (If any wells exist
on site or within 200 feet of leaching facility) Feet
Edge of Wetland and Leaching Facility(If any wetlands exist
within 300 feet of leaching facility) Feet .
Furnished by
ry C �.
RISER TO WITHIN 6" 5" DIA. OUTLET(S) a FINISH GRADE OVER LEACHING FIELD= 8.75'-8.60'
4" SCHEDULE 40 PVC MIN. SLOPE 1 /o GENERAL NOTES
OF FINISHED GRADE FOR REMOVABLE COVER SLOPE @ 2% MIN. OVER SYSTEM
INLET AND OUTLET 3/4"TO 1-1/2" DOUBLE WASHED STONE TO CROWN OF PIPE
° 2"SCH.40 FINISH GRADE OVER D-BOX= 8•6�
j FINISH GRADE @FND. EL.= 6.8'-7.1' FINISH GRADE OVER TANKS EL.= 7.2' - 6.6' TO D-BOX 2"OF 1/8"TO 1/2" DOUBLE WASHED STONE
j UNLESS OTHERWISE NOTED, ALL SYSTEM COMPONENTS AND CONSTRUCTION
e 20"MIN.ACCESS COVER I36"MAX. 1 CULTEC#410 FILTER FABRIC METHODS SHALL BE IN ACCORDANCE WITH TITLE 5 OF THE STATE
f (TYPICAL FOR 31
_ t 36"MAX. 7 59' ENVIRONMENTAL CODE AND ANY APPLICABLE LOCAL RULES.
TOP OF SAS -
L, ° 4" SCH. 40 PVC j 4" scH. ., 2" PVC TEE 4" PVC OUT TO
9"MI
36"MAX.
ti SLOPE ® 1% min. 6. 3 3" DROP MIN. 911 40 PVC LEACHING FACILITY 88' 2. ANY CHANGES TO THIS PLAN MUST BE APPROVED BY THE BOARD
° 6. OF HEALTH AND THE DESIGN ENGINEER.
OPE ® 1% min. • ° •, • //7
"
INV. I N- 10 14" ' L = 1.55'
4.55' 48 INV. OUT= ALARM ON 1 ,* 3.
TIGHTHEDULE 40 PVC PIPE WITH WATER JOINTS SHALL
LIQUID + BE USED IN DISPOSAL SYSTEM UNLESS OTHERWISE NOTED.
4.30'
° LEVEL , PUMP ON SLOPE ® 1% min. o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 - -
° EXIST. INV. 4.25 INLET TEE a L - s' ' 1 6., EFFECTIVE 4. 4"SCHEDULE 40 PVC PERFORATED PVC PIPE SHALL BE USED
ELEV. VARIE 2 5
'PUMP 6" o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o a o DEPTH
.. .. . : OUTLETOFFINSIDE LEACHING TRENCHES OR LEACHING FIELDS.
7.07' -�-. 6.90 3 3' 3'
°$ 22"ZABEL FILTER TEE �. ,. ... = 38'
BOTTOM OF TRENCH TO BE LEVEL EL. 6.
MODEL#A1801 HIP(GAS 6" CRUSHED STONE - Ln 4.00' �`--• STARTER UNIT= 7.67' 6.33'TYP. FOR ADDTIONAL UNITS g� 5. SLOPE ALL SOLID PIPE AT 1.0% MINIMUM.
BAFFLE ON BOTTOM) OVER MECHANICALLY 6' CRUSHED STONE
COMPACTED BASE -/� OVER MECHANICALLY 6. THIS SYSTEM IS NOT DESIGNED FOR A GARBAGE DISPOSAL.
° BAFFLE COMPACTED BASE 45.65' FOR 7 UNITS
°
LENGTH 10'-6" WIDTH 5'-8" DEPTH 5'-7" LENGTH 8'-6" WIDTH 4'-10" DEPTH 5-7� 3 OUTLET DISTRIBUTION BOX 7. LOCAL BOARD OF HEALTH AND DESIGN ENGINEER TO BE NOTIFIED
1500 GALLON SEPTIC TANK 1000 GALLON PUMP CHAMBER TO BE INSTALLED ON A LEVEL STABLE ADJUSTED GROUND WATER ELEV.= 2.38' PRIOR TO BACKFILLING WHEN SYSTEM IS NEARLY COMPLETE AND
(SEE DETAIL BELOW) BASE. FIRST TWO FEET OF OUTLET READY FOR INSPECTION. SYSTEM IS NOT TO BE BACKFILLED
PIPES TO BE LAID LEVEL. 4 MIN. WITHOUT FIRST OBTAINING APPROVAL FROM BOARD OF HEALTH
TYPICAL TRENCH PROFILE AND DESIGN ENGINEER.
TANKS SHALL BE INSTALLED ON A LEVEL STABLE BASE CROSS SECTION VIEW TYPICAL TRENCH END VIEW
8. ELEVATIONS BASED ON NGVD ELEVATION 7.04'MSL OBTAINED
PROPOSED 1500 GALLON SEPTIC TANK & FROM TOP OF CONCRETE BOUND AS INDICATED ON PLAN.
1000 GALLON PUMP CHAMBER DISTRIBUTION BOX DETAIL TRENCH DETAILS (CULTEC 100) 9. CONTRACTOR SHALL VERIFY ALL UTILITY LOCATIONS PRIOR TO CONSTRUCTION
THROUGH DIG-SAFE AT LEAST 72 HOURS PRIOR TO COMMENCING WORK ON SITE
NOT TO SCALE NOT TO SCALE NOT TO SCALE AT 1-888-DIG-SAFE AND ANY OTHER APPLICABLE AGENCIES. REPORT ANY
DISCREPANCIES TO THE DESIGN ENGINEER.
TEST
I DATA
s 10. NON-SHRINK GROUT TO BE USED AT ALL POINTS WHERE PIPES ENTER OR
Donna Miorandi BOH
INSPECTOR: ( )
t' ' IIhI I LEAVE ALL CONCRETE STRUCTURES IN ORDER TO PROVIDE WATER TIGHT SEALS.
t SOIL EVALUATOR: John L. Churchill Jr.
/* DATE: November 14,2000 11. NO DETERMINATION HAS BEEN MADE AS TO COMPLIANCE WITH DEEDED OR
fr ZONING REGULATIONS. OWNER/APPLICANT IS TO OBTAIN
TESTPIT#: ( P-988�;� 1
LOC � SUCH DETERMINATION FROM APPROPRIATE AUTHORITY.
ELEV TOP 6.50 12. ALL SEPTIC SYSTEM COMPONENTS SHALL WITHSTAND H-10 LOADING UNLESS
ELEV WATER= 2.38'* LOCATED UNDER PAVEMENT, DRIVES OR TRAVELED WAYS IN WHICH
CASE THEY SHALL WITHSTAND H-20 LOADING.
° "� PERC RATE _ < 2 MIN/IN
.y
* r + 13. WASHED CRUSHED STONE SHALL BE FREE OF ALL DIRT, UST AND
40 �• ,� rr ■ •"' ,• DEPTH OF PERC= 36"-54" DOUBLE DUST
Wy �tiy r
Rr
T LASS 14. WHERE REQUIRED, CONTRACTOR SHALL REMOVE ALL LOAM AND
LC 1
UNSUITABLE MATERIAL BELOW ELEVATION 6.88'AND FOR AN AREA 5 FT. ON ALL SIDES
} - a ,a'� .-_ D� Elev. OF LEACHING FACILITY. REPLACE ALL UNSUITABLE MATERIAL WITH CLEAN
1: ( -- " 4�# 0 6.5' COARSE SAND FREE FROM CLAY, FINES OR OTHER UNSUITABLE MATERIAL IN
lit
A Loamy Sand ACCORDANCE WITH 310 CMR 15.255(3).
10 YR 3/1
N �,, 12" 5.5'
15. CONTRACTOR SHALL NOTIFY DESIGN ENGINEER OF ANY DISCREPANCIES
8.6 p0 0 LT, �`�° ', " _ '�` FOUND IN SITE CONDITIONS FROM THOSE SHOWN PRIOR TO
Medium Sand
CONTINUATION OF WORK.
B 10 YR 5/6
ws'('
Li:Sj
ti
PARCEL 2 ! ` - x� ',> ; 4ti ! 30" 4•0' 16. PROPOSED PROJECT IS LOCATED WITHIN:
7.6 ' �C.B6 "
C.B x �' ''�`I (FND.) � I "* �� ` " 36 ASSESSORS MAP# 93 PARCEL# 1,2 LOT# 6
j°42 rbo i. 'A`; , `` z ,` I Perc Location
PROP. CULTEC LEACHING (FND.) WOODED g12 ;,
•� 25•p OWNER OF RECORD: PAUL OGLESBY
SYSTEM WITH STONE AROUND / l REMOVE MATERIAL 5 FEET IN ALL DIRECTIONS TO TOP OF B-HORIZON (ELEV. 5.5) 68" Groundwater Observed .83'
PERIMETER (SEE DETAIL) ci� �-J AND REPLACE WITH TITLE 5 SAND. (SEE NOTE 14) IN ACCORDANCE WITH DEP @ 68" ADDRESS: 10 LONGWOOD DRIVE #322
rn �,g5.65 r t0 X 6 POLICY. THE B-HORIZON CAN BE USED FOR THE FOUR FEET OF NATURALLY LOCUS PLAN ° C WESTWOOD, MA 02090
OCCURING PERVIOUS MATERIAL. Medium Sand i
pp SCALE: 1" = 1000' 2.5 Y 7/6 17. TO PREVENT BREAKOUT, THE PROPOSED FINISH GRADE SHALL NOT BE LESS
/�S 49,pp 6x5 EXISTING CESSPOOL TO BE PUMPED S 120" -3.5' THAN ELEVATION = 7.59' FOR A DISTANCE OF 15'AROUND THE PERIMETER OF THE SAS.
AND FILLED WITH CLEAN SAND FOR TIDAL AREAS, USE THE AVERAGE OF THE
PROP. MONTHLY SPRING TIDE HIGH GROUNDWATER
"D" BOX 29.4' $ ELEVATION OVER PAST 19 YEARS.(SEE 18. IN ACCORDANCE WITH 310 CMR 15.404, WHERE FULL COMPLIANCE IS NOT FEASIBLE, WE ARE
ATTACHED CALCULATIONS) REQUESTING A 'I'VARIANCE (5'-4') FOR THE SEPARATION DISTANCE BETWEEN BOTTOM OF
CULTEC CHAMBERS AND ESTIMATED SEASONAL HIGH GROUNDWATER.
PROP. 1000 GAL. rn_ INSTALL 1"PVC CONDUIT TO HOUSE FOR WIRING
PUMPING CHAMBER 7.6 WITH WATERTIGHT JOINTS.WIRE HIGH WATER ALARM TO
FLOAT TO GP 2000 HIGH WATER ALARM PANEL.
PROP. 1500 GAL.
SEPTIC TANK --,--_.
O NEMA 4 JUNCTION BOX CORROSION RESISTANT HOISTING CABLE 7 x 19 STAINLESS STEEL LEGEND
EXISTING CESSPOOL TO BE PUMPED &LIQUID-TIGHT CABLE CONNECTORS SUPPORTED 1/8" DIA./ 1,760 LB. STRENGTH i
l ''� , AND FILLED WITH CLEAN SAND " I�'+;� ,I 6 LUU�
EXISTING CESSPOOL TO BE PUMPED � O CONNECTORS SUPPORTED BY 1-1/4 PVC
(� SILL= (APPROXIMATE LOCATION) CONDUIT, JOI TS TO BE MADE WATERTIGHT 2"BALL VALVE w/UNIONS SCH. 80 PVC EXISTING CONTOURS
AND FILLED WITH CLEAN SAND -- - - 8.31 / ° GEORGE FISHER CO. MODEL NO. 560 TowH o NTH DEFT BLE
19.5' y 15 PROPOSED CONTOURS
6" 3" � 2"SCH.40 TO D-BOX
- -�-2"SCH.40 TEE w/CLEAN-OUT CAP EXISTING SPOT GRADE
SILL= - w 5' 7" 10„ ALARM ON x.6
PROPOSED SPOT GRADE
Cn N 7.83 4'-6" I'.:-.PUMP ON
O TEST PIT LOCATION
o PATIO uMP �`� 2" BALL CHECK VALVE SCH. 80 PVC
0 100 P.S.I. FLOWMATIC MODEL No. 208S Q Q PROPOSED 1500 GALLON SEPTIC TANK
U
#19 PROVIDE 2-WIDE ANGLE FLOATS: 0 1/4"WEEP HOLE IN DISCHARGE PIPE =0 ?
PROPOSED 1000 GALLON PUMP CHAMBER
PARCEL 1 FLOAT NO. 1: PUMP ON/OFF(BARNES 073618)
EXISTING 3 FLOAT NO. 2: ALARM ACTIVATION (BARNES 073612) 2"SCH.40 PVC DISCHARGE PIPE
BEDROOM DWELLING B.M. BARNES SE411 PUMP A H.P. 115 V ❑ DISTRIBUTION BOX
TOP C.B. 2" DISCHARGE PASSING 1-1/2"SOLIDS
ELEV.-7.04 PUMP CHAMBER, PUMP&ACCESSORIES AVAILABLE AS A UNIT OR EQUAL CULTEC 100 CHAMBER
THROUGH WIGGEN PRECAST CORP., BOURNE MA. (800)564-6774
N.G.V.D.
PUMP&ACCESSORIES AVAILABLE THROUGH WILLIAMSON ELECTRIC(781)444-6800 4"SOLID SCHEDULE 40 PVC PIPE
1000 GALLON PUMP CHAMBER 2"SOLID SCHEDULE 40 PVC PIPE
LOT 6 (PARCELS - DESIGN DATA
AREA= 19,762± S.F. NUMBER OF BEDROOMS: 3
NUMBER OF PERSONS: 4
C.B DESIGN FLOW 110 GAUDAY/BEDROOM DOSING & STORAGE REQUIREMENTS
REV. DATE BY APP'D. DESCRIPTION
(FND.) !. 130.00 -. C.B TOTAL DESIGN FLOW 330 GAUDAY ----
DESIGN FLOW: 330 GPD
N32002'30"E (FND.) - ��uu PROPOSED SEPTIC SYSTEM UPGRADE
SEPTIC TANK: DOSING REQUIRED: 4 CYCLES /DAY ��J�'� .;r fts
c r PREPARED FOR:
330 GPDA = 82.5 GAUCYCLE :''.��
330 GAL. X 200% =660 GALS. DESIGN CAPACITY �=y` i=owF,ROL �GJ PAUL OGLESBY
�.
USE 1500 GALLON SEPTIC TANK DISTANCE REQUIRED BETWEEN PUMP > viva
GREAT BAY ROAD (MINIMUM PER TITLE 5) ON AND PUMP OFF FLOATS: No.32.001E LOCATED AT _
INSTALL 7 CULTEC CHAMBERS
82.5 GAUCYCLE = 250 GAUFT = .33 FT/CYCLE
SIDEWALL CAPACITY (USE .50'TO PROVIDE FOR BACKFLOW) NA � 19 GREAT BAY ROAD
(LENGTH +WIDTH)x (INVERT HEIGHT)x (2 SIDES) =S.F. STORAGE REQUIRED ABOVE WORKING LEVEL: 330 GAL. �"
' OSTERVILLE MA 02655
(45.65' + 9') x (.5)x (2) = 54.65 S.F. STORAGE PROVIDED ABOVE WORKING LEVEL:625 GAL.
(54.65 S.F.)x (.74 GPD/S.F.) = 40.44 GPD BUOYANCY CALCULATIONS SCALE: 1 INCH = 20 FT. DATE: DECEMBER 27,2000
0 10 20 40 80 FEET
BOTTOM CAPACITY PUMP CHAMBER:
(LENGTH x WIDTH) (.74 GPD/S.F.) = GPD HIGH GROUNDWATER EL.= 2.38' BOTTOM OF PUMP PREPARED BY: -
(45.65'x 9') (.74 GPD/S.F.) = 304.03 GPD CHAMBER EL. =-0.25'
WATER DISPLACED = (2.38' - (-0.25'))x 4.8 x 8.5= 107.3 C.F. HORSLEY & WITTEN, INC.
TOTALS: WEIGHT OF DISPLACED WATER= 107.3 C.F. X 62.4 LB/C.F. 90 ROUTE 6A
-- --- - -- --- - - - - TOTAL LEACHING AREA= 465.50 S.F. = 6,696 LBS.
--- -- - - --- SANDWICH MA 02563
SITE PLAN- TOTAL LEACHING CAPACITY= 344.47 GPD WEIGHT . H-10 1000 GAL. PUMP CHAMBER=8,300 LBS. 508.833.6600
8,300 LBS. > 6,696 LBS. (ACCEPTABLE)
SCALE: 1 20' Also, chamber will maintain a 1' septage level below pump-off float. Drawn By: JLC Designed By: JLC Checked By: ELP JOB No. 1074
"=
RISER TO WITHIN 6" 5" DIA. OUTLET(S) 4" SCHEDULE 40 PVC MIN. SLOPE 1% FINISH GRADE OVER LEACHING FIELD= 9•75'-9.60' A GENERAL NOTES
OF FINISHED GRADE FOR REMOVABLE COVER SLOPE @ 2% MIN. OVER SYSTEM
INLET AND OUTLET I
2"SCH. 40
FINISH GRADE OVER D-BOX 9.6' 3/4"TO 1-1/2" DOUBLE WASHED STONE TO CROWN OF PIPE
FINISH GRADE @ FND. EL.= 6.8'-7.1' FINISH GRADE OVER TANKS EL.= 8.0' - 6.6' TO D-BOX 2" OF 1/8"TO 1/2" DOUBLE WASHED STONE
_�_ __-__._�.._ _. --------------- -- 1. UNLESS OTHERWISE NOTED, ALL SYSTEM COMPONENTS AND CONSTRUCTION
20" MIN. ACCESS COVER I36"MAX. i CULTEC#410 FILTER FABRIC METHODS SHALL BE IN ACCORDANCE WITH TITLE 5 OF THE STATE
(TYPICAL FOR 3 36"MAX. TOP OF S.A.S. = 8 59� ENVIRONMENTAL CODE AND ANY APPLICABLE LOCAL RULES.
9" MI
° . . . 2" PVC TEE 4" PVC
4" SCH. 40 PVC 4" SCH.
C OUT TO 36 MAX
SLOPE ® 1% min. F-7
3" 1 40 PVC LEACHING FACILITY 2. ANY CHANGES TO THIS PLAN MUST BE APPROVED BY THE BOARD
3" DROP MIN. g" 7.88 OF HEALTH AND THE DESIGN ENGINEER.
" °. .� OPE C� 1% min. :♦., ��
a
_
_
I L 1.55'
- 14" 'INV. IN- 3.
4" SCHEDULE 40 PVC PIPE WIT WATERALARM ON . - .,. .4.55' 48 INV. OUT- i TIGHT JOINTS SHALL
LIQUID 4.30' f BE USED IN DISPOSAL SYSTEM UNLESS OTHERWISE NOTED.
a LEVEL PUMP ON O SLOPE C� 1% min, o 0 0 0 0 0 0 0 0 o a o 0 0 0 0 0 0 0 0 0 0 0 0 0
r
EXIST. INV. 4.25 INLET TEE L = 6 "' 12 5 <- ¢r r 6„ EFFECTIVE 4. 4" SCHEDULE 40 PVC PERFORATED PVC PIPE SHALL BE USED
` o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
ELEV. VARIL I PUMP DEPTH
-:. OUTLET o F 7' :. 7.90' s'� INSIDE LEACHING TRENCHES R LEACHING FIELDS.
C G SO S
22"ZABEL FILTER TEE �.... •. : : .... :.. 8.O . _ BOTTOM OF TRENCH TO BE LEVEL EL. = 7.38' 3 3 3
MODEL#Al801 HIP (GAS 6" CRUSHED STONE 4.00' • A .", STARTER UNIT=7.67' 6.33'TYP. FOR ADDTIONAL UNITS 91 5. SLOPE ALL SOLID PIPE AT 1.0% MINIMUM.
BAFFLE ON BOTTOM) OVER MECHANICALLY
�6 CRUSHED STONE
° COMPACTED BASE -� OVER MECHANICALLY
a ° COMPACTED BASE 45.65' FOR 7 UNITS 6. THIS SYSTEM IS NOT DESIGNED FOR A GARBAGE DISPOSAL.
° BAFFLE
LENGTH 10'-6" WIDTH 5'-8" DEPTH 5'-7" LENGTH 8'-6" WIDTH 4'-10" DEPTH 5'-7" 5 OUTLET DISTRIBUTION BOX 7. LOCAL BOARD OF HEALTH AND DESIGN ENGINEER TO BE NOTIFIED
1500 GALLON SEPTIC TANK 1000 GAL_LON_P_UMP CHAMBER TO BE INSTALLED ON A LEVEL STABLE ADJUSTED GROUND WATER ELEV= 2.38' PRIOR TO BACKFILLiNG WHEN SYSTEM IS NEARLY COMPLETE AND
BASE. FIRST TWO FEET OF OUTLET READY FOR INSPECTION. SYSTEM IS NOT TO BE BACKFILLED
(SEE DETAIL BELOW) 4' MIN. WITHOUT FIRST OBTAINING APPROVAL FROM BOARD OF HEALTH
PIPES TO BE LAID LEVEL.
' TYPICAL TRENCH PROFILE AND DESIGN ENGINEER.
- TANKS SHALL BE INSTALLED ON A LEVEL STABLE BASE CROSS SECTION VIEW TYPICAL TRENCH END VIEW
8. ELEVATIONS BASED ON NGVD ELEVATION 7.04' MSL OBTAINED
PROPOSED 1500 GALLON SEPTIC TANK & i FROM TOP OF CONCRETE BOUND AS INDICATED ON PLAN.
1000 GALLON PUMP CHAMBER DISTRIBUTION BOX DETAIL TRENCH DETAILS (CULTEC 100) ` CONTRACTOR SHALL VERIFY ALL UTILITY LOCATIONS PRIOR TO CONSTRUCTION
THROUGH DIG-SAFE AT LEAST 72 HOURS PRIOR TO COMMENCING WORK ON SITE
NOT TO SCALE NOT TO SCALE NOT TO SCALE AT 1-888-DIG-SAFE AND ANY OTHER APPLICABLE AGENCIES. REPORT ANY
I HE DESIGN ENGINEER.
Pt
------ - - TEST PIT DATA
10. NON-SHRINK GROUT TO BE USED AT ALL POINTS WHERE PIPES ENTER OR
s INSPECTOR: Donna Miorandi (BOH)
Isabella � ; $ �` � LEAVE ALL CONCRETE STRUCTURES IN ORDER TO PROVIDE WATER TIGHT SEALS.
SOIL EVALUATOR: John L. Churchill Jr.
* `'• November 14, 2000 11. NO DETERMINATION HAS BEEN MADE AS TO COMPLIANCE WITH DEEDED OR
,�r�, • DATE: ZONING REGULATIONS. OWNER/APPLICANT IS TO OBTAIN
' ;;• + TEST PIT#: 1 (REF.# P-9$84) SUCH DETERMINATION FROM APPROPRIATE AUTHORITY.
Loc S J r
+. ELEV TOP= 6.50'
12. ALL SEPTIC SYSTEM COMPONENTS SHALL WITHSTAND H-10 LOADING UNLESS
ELEV WATER= 2.38' LOCATED UNDER PAVEMENT, DRIVES OR TRAVELED WAYS IN WHICH
If" CASE THEY SHALL WITHSTAND H-20 LOADING.
PERC RATE - < 2 MIN/IN
" 13 WASHED CRUSHED STONE SHALL BE FREE OF ALL DIRT, UST AND
DOUBLE T, D
r DEPTH OF PERC= 36„ ` „ FINES.
d
TEXTURAL CLASS: 1 14. WHERE REQUIRED, CONTRACTOR SHALL REMOVE ALL LOAM AND
Depth Elev. UNSUITABLE MATERIAL BELOW ELEVATION 6.88'AND FOR AN AREA 5 FT. ON ALL SIDES
't OF LEACHING FACILITY. REPLACE ALL UNSUITABLE MATERIAL WITH CLEAN
0 6.5' COARSE SAND FREE FROM CLAY, FINES OR OTHER UNSUITABLE MATERIAL IN
: s * 1 �,: M .. q Loamy Sand ACCORDANCE WITH 310 CMR 15.255(3).
10 YR 3/1
94' µ�. "' t �� , 12 15. CONTRACTOR SHALL NOTIFY DESIGN ENGINEER OF ANY DISCREPANCIES
,.. ° � FOUND IN SITE CONDITIONS FROM THOSE SHOWN PRIOR TO
I / Medium Sand
' 4 `` t� CONTINUATION OF WORK.
' PARCEL 2 '. i ._ . r 7 a;{ r, ;. B 10 YR 5/6
x C.B Birk = °
s � y, '��
30"
C.B 8'6 6�• p0� �(FND.} 4.0' 16. PROPOSED PROJECT IS LOCATED WITHIN:
(FND.) �2°� �," �► 36" ASSESSORS MAP# 93 PARCEL# 1,2 LOT# 6
PROP. CULTEC LEACHING WOODED / O "` -
* Perc Location
SYSTEM WITH STONE AROUND N , 26 REMOVE MATERIAL 5 FEET IN ALL DIRECTIONS TO TOP OF B-HORIZON (ELEV. 5.5') RECORD
( �- - - - - - - OWNER OF OGLESBY PAUL
PERIMETER (SEE DETAIL) w \-( 9 AND REPLACE WITH TITLE 5 SAND. (SEE NOTE 14) IN ACCORDANCE WITH DEP 68 Groundwater Observed 83' -
rn .6x POLICY. THE B-HORIZON CAN BE USED FOR THE FOUR FEET OF NATURALLY /l� @ 68�� ADDRESS: 10 LONGWOOD DRIVE #322
' p OCCURING PERVIOUS MATERIAL. LOCUS PLAN
�NESTWOOD, MA 02090
C Medium Sand
!� 3 01j '�N x5 EXISTING CESSPOOL TO BE PUMPED 2.5 Y 7/6 17. TO PREVENT BREAKOUT,THE PROPOSED FINISH GRADE SHALL NOT BE LESS
S17°�g00 AND FILLED WITH CLEAN SAND SCALE: 1" = 1000' s 120 -3.5'
PROP. / THAN ELEVATION = 8.59' FOR A DISTANCE OF IIS AROUND THE PERIMETER OF THE SAS.
"D" BOX 29 4' g // FOR TIDAL AREAS,USE THE AVERAGE OF THE
6)66 III
� ^� �., � � � MONTHLY SPRING TIDE HIGH GROUNDWATER
f ELEVATION OVER PAST 19 YEARS.(SEE
PROP. 1000 GAL. $ ATTACHED CALCULATIONS)
PUMPING CHAMBER 8.6 0
7 INSTALL 1" PVC CONDUIT TO HOUSE FOR WIRING
PROP. 1500 GAL. 0 WITH WATERTIGHT JOINTS. WIRE HIGH WATER ALARM TO
SEPTIC TANK FLOAT TO GP 2000 HIGH WATER ALARM PANEL.
0 6.8 17.0 EXISTING CESSPOOL TO BE PUMPED
AND FILLED WITH CLEAN SAND NEMA 4 JUNCTION BOX CORROSION RESISTANT HOISTING CABLE 7 x 19 STAINLESS STEEL LEGEND
EXISTING CESSPOOL TO BE PUMPED 0 SILL- / (APPROXIMATE LOCATION) &LIQUID-TIGHT CABLE CONNECTORS SUPPORTED 1/8 DIA. / 1,760 LB. STRENGTH
AND FILLED WITH CLEAN SAND _ CONNECTORS SUPPORTED BY 1-1/4'" PVC
8.31 CONDUIT, JOI TS TO BE MADE WATERTIGHT 2"BALL VALVE w/UNIONS SCH. 80 PVC EXISTING CONTOURS
GEORGE FISHER CO. MODEL NO. 560
_..- - ��' 'a ♦ 15 PROPOSED CONTOURS
6" 3" 2"SCH. 40 TO D-BOX
6,66 EXISTING SPOT GRADE
SILL= / \ "SCH.40 TEE w/CLEAN-OUT CAP x
U 7.83 ( n 1 rj'-7" 10"
ALARM ON
N 7.6 PROPOSED SPOT GRADE
w „
"- N PATIO 4-6 I;.PUMP ON O
p TEST PIT LOCATION
uMP N 2" BALL CHECK VALVE SCH. 80 PVC
rn o F 100 P.S.I. FLOWMATIC MODEL No. 208S O O O PROPOSED 1500 GALLON SEPTIC TANK
♦ . i a
,t #19 �
PARCEL 1 PROVIDE 2-WIDE ANGLE FLOATS: p 1/4"WEEP HOLE IN DISCHARGE PIPE O O O PROPOSED 1000 GALLON PUMP CHAMBER
EXISTING 3 FLOAT NO. 1: PUMP ON/OFF (BARNES 073618) 2" SCH. 40 PVC DISCHARGE PIPE
BEDROOM DWELLING B.M. FLOAT NO. 2: ALARM ACTIVATION (BARNES 073612)
TOP C.B. BARNES SE411 PUMP A H.P. 115 V ❑ DISTRIBUTION BOX
ELEV.=7.04 2" DISCHARGE PASSING 1-1/2" SOLIDS
PUMP CHAMBER, PUMP &ACCESSORIES AVAILABLE AS A UNIT OR EQUAL Q CULTEC 100 CHAMBER
N.G.V.D. THROUGH WIGGEN PRECAST CORP., BOURNE MA. (800)564-6774
PUMP &ACCESSORIES AVAILABLE THROUGH WILLIAMSON ELECTRIC (781)444-6800 4"SOLID SCHEDULE 40 PVC PIPE
F EXISTING 2" SOLID SCHEDULE 40 PVC PIPE
LOT 6 (PARCELS 1 & 2) ? WATERLINE 1000 GALLON PUMP CHAMBER
AREA= 19,762± S.F. W ,/ NUMBER OF BEDROOMS: _ 3 - DESIGN DATA
C.B I°� NUMBER OF PERSONS: 4 1 2/08/01 JLC ELP BOH COMMENTS
(FND.) !� 130.00 METER PIT C.B DOSING & STORAGE REQUIREMENTS
DESIGN FLOW 110 GAL/DAY/BEDROOM REV. DATE BY APP'D. DESCRIPTION
N32°02'30"E (FND.) TOTAL DESIGN FLOW 330 GAUDAY ----_E__. __,_ -- - ------ -- ON -
DESIGN FLOW: 330 GPD PROPOSED SEPTIC SYSTEM UPGRADE
w
WS DOSING REQUIRED: 4 CYCLES /DAY .��° �4r�
SEPTIC TANK: . �� Y PREPARED FOR:
330 GPD/4 = 82.5 GAUCYCLE OGLESBY PAUL
330 GAL. X 200% =660 GALS. DESIGN CAPACITY c! EDWARDL. vN�►
GREAT BAY ROAD �! pF.ce is
USE 1500 GALLON SEPTIC TANK DISTANCE REQUIRED BETWEEN PUMP .�� crvlt n . --------
(MINIMUM PER TITLE 5) ON AND PUMP OFF FLOATS: p w0 a C - LOCATED AT
INSTALL 7 CULTEC CHAMBERS 82.5 GAL/CYCLE ' 250 GAL/FT = .33 FTICYCLE +.,~Fs�JNALECI 19 GREAT BAY ROAD
SIDEWALL CAPACITY (USE .50'TO PROVIDE FOR BACKFLOW) ` �•� � Ate.
(LENGTH +WIDTH)x(INVERT HEIGHT)x(2 SIDES) =S.F. STORAGE REQUIRED ABOVE WORKING LEVEL: 330 GAL. OSTERVILLE, MA 02655
(45.65' + 9')x (.5')x(2) = 54.65 S.F. STORAGE PROVIDED ABOVE WORKING LEVEL: 625 GAL.
(54.65 S.F.)x(.74 GPD/S.F.) = 40.44 GPD BUOYANCY CALCULATIONS SCALE: 1 INCH = 20 FT. DATE: DECEMBER 27, 2000
0 10 20 40 80 FEET
BOTTOM CAPACITY PUMP CHAMBER:
(LENGTH x WIDTH) (.74 GPD/S.F.) = GPD HIGH GROUNDWATER EL.= 2.38' BOTTOM OF PUMP PREPARED BY:
(45.65' x 9') (.74 GPD/S.F.) = 304.03 GPD CHAMBER EL. =-0.25' F
WATER DISPLACED = (2.38' - (-0.25'))x 4.8 x 8.5= 107.3 C.F. HORSLEY & WITTEN, INC.
TOTALS: WEIGHT OF DISPLACED WATER = 107.3 C.F. X 62.4 LB/C.F. 90 ROUTE 6A
-- --------- - -- ---- -- ------ --- -- ---- - -- TOTAL LEACHING AREA= 465.50 S.F. 6,696 LBS. SANDWICH MA 02563
TOTAL LEACHING CAPACITY= 344.47 GPD WEIGHT OF H-10 1000 GAL. PUMP CHAMBER=8,300 LBS. '
SITE PLAN- 8,300 LBS. > 6,696 LBS. (ACCEPTABLE) 508.833.6600
Also, chamber will maintain a 1' septage level below pump-off float. Drawn By: JLC Designed By: JLC Checked By: ELP JOB No. 1074
SCALE: 1" =20'