December 3, 2018
aQ
o. rn
6
Town of Barnstable
Mr. Brian Florence—Building Commissioner
200 Main Street
Hyannis, MA 02601
RE: Cell tower at 1047 Falmouth Road-T-Mobile Request to Install a 7.5kw Generator
T-Mobile Site#4HY0558A
Crown Site#875054/App#404103
Dear Commissioner Florence;
We had spoken on the phone a few weeks ago in regard to a T-Mobile request to install a new 7.5kw natural gas
generator for the purpose of backup power to their existing radio equipment base station at 1047 Falmouth
Road, Hyannis.
This request, with your consideration, is to apply for a building permit only as this proposal is within the
guidelines of the 2012, 2014 &2015 Federal Mandate, 6409 (The Spectrum Act). The 2015 Federal Register
Part IV, page 1269, subpart CC, section 1.40001 (ii) does allow backup power supplies such as T-Mobile's
request here as long as it does not substantially change the physical dimensions of such tower or base station. A
substantial change would be to increase the towers height or width by 10% or 20' and by adding more than four
radio cabinets to the base station. This request does neither.
The size of the proposed generator is 25.1"x 41"x 40.1" and is equipped with attenuated insulated housing that
traps and muffles sound when in use. Also, the generator will be installed on an existing concrete pad so.there
will be no excavation or an expansion of the compound required. The generator does comply with decibel (dB)
levels in the Town of Hyannis. Please refer to sheets C-1, C-2 and C-3 of the attached CD's for details.
On May 10, 2000, almost 19 years ago a variance was approved and issued to Sprint to increase the existing cell
tower by 5' in height from 115 to 120' AGL. Prior to 2000 the tower was constructed in 1975 by the land
owner. The process of approval then is detailed in the variance. The purpose of the variance in 2000 was to
approve the new height of the tower, proper coverage, visual screening and following the town zoning process
so that Sprint could install new antennas. The Telecommunication Act of 1996 was used because without the
approval Sprint would have suffered substantial hardship.
r t
Page 2
T-Mobile Proposed Generator
December 3 2018
Here,the proposal for T-Mobile is to seek building and electric permits to install a 7.5kw generator, about the
size of some residential generators. The Spectrum Act states "regardless of the circumstances under which a
provider obtained permission to build a facility, now that it has been built, any expansion proposals are
reviewed only to determine whether it will substantially increase the physical dimensions". T-Mobile is
only proposing to install a backup powered generator on an existing concrete pad. This is not a substantial
change to the tower sites dimensional use as stated in the Spectrum Act.
Wireless Communication in the USA continues to evolve at an extremely rapid pace with the expansion to 5G
for all the Nation's carriers. As the tower sites services are used and depended upon more by wireless
customers, the radio equipment requires reliability. T-Mobile is licensed by the FCC to transmit and provide
customers with continued normal or emergency service even if weather prevents a power outage. T-Mobile's
proposed generator as explained in this letter, will provide customers with uninterrupted service.
Please consider this proposed generator installation as building and electric permits only and feel free to contact
4ce
tio or additional information.
Ja
781-970-0053
`wSAkD,RECp��s
A MANE 9
ANEI O
�bN 1985
FED ER AL REGISTER
Vol. 80 Thursday,
No. 5 January 8, 2015
t Part IV
Federal Communications Commission
47 CFR Parts 1 and 17
Acceleration of Broadband Deployment by Improving Wireless Facilities
Siting Policies; Final Rule
II
Federal Register/Vol. 80, No. 5/Thursday, January 8, 2015/Rules and Regulations 1269
(iii)Comparable equipment from pre- that directly mitigate or prevent effects, (iii)The term includes any structure
existing wireless deployments on the such as camouflage or concealment other than a tower that,at the time the
structure; requirements; relevant application is filed with the
(3)The deployment will involve no (4)The deployment of the new State or local government under this
new ground disturbance;and antenna involves no new ground section,supports or houses equipment
(4)The deployment would otherwise disturbance;and described in paragraphs(b)(1)(i)through
require the preparation of an EA under (5)The deployment would otherwise (ii)of this section that has been
paragraph(a)(4)(i)of this section solely require the preparation of an EA under reviewed and approved under the
because of the age of the structure;or paragraph(a)(4)of this section solely applicable zoning or siting process,or
(B)The mounting of antennas because of the age of the structure. under another State or local regulatory
(including associated equipment such as Note to paragraph(a)(4)(ii):A non-visible review process,even if the structure was
wiring,cabling,cabinets,or backup- new antenna is in the"same vicinity"as a not built for the sole or primary purpose
power)on buildings or other non-tower pre-existing antenna if it will be collocated of providing such support.
structures where the deployment meets on the same rooftop,faeade or other surface. '(iv)The term does not include any
the following conditions: A visible new antenna is in the"same structure that,at the time the relevant
(1)There is an existing antenna on the vicinity"as a pre-existing antenna if it is on application is filed with the State or
building or structure; the same rooftop,faeade,or other surface and local government under this section,
(2)One of the following criteria is the centerpoint of the new antenna is within does not support or house equipment
met: ten
antenna A deploymentct causint of es no new fisting described in paragraphs(b)(1)(i)—(ii)of
- (i)Non-Visible Antennas.The newthis section.
antenna is not visible from any adjacent Found disturbance when the depth and
streets or surrounding public spaces and width of previous disturbance exceeds the (2) Collocation.The mounting or
proposed construction depth and width by at installation of transmission equipment
is added in the same vicinity as a pre- least two feet. on an eligible support structure for the
existing antenna; purpose of transmitting and/or receiving
(ii) Visible Replacement Antennas. radio frequency signals for
The new antenna is visible from ■4.Add Subpart CC to part 1 to read communications purposes.
adjacent streets or surrounding public as follows: (3)Eligible facilities request.Any
spaces,provided that
(A)It is a replacement for a pre- Subpart CC—State and Local Review request for modification of an existing
existing antenna, of Applications for Wireless Service tower or base station that does not
(B)The new antenna will be located Facility Modification substantially change the physical
in the same vicinity as the pre-existin dimensions of such tower or base
antenna, .40001 Wireless Facility Modifications. station,involving:
(C)The new antenna will be visible (a)Purpose.These rules implement (i)Collocation of new transmission
only from adjacent streets and section 6409 of the Spectrum Act equipment;
surrounding public spaces that also (codified at 47 U.S.C.1455),which (ii)Removal of transmission
afford views of the pre-existing antenna, requires a State or local government to equipment;or
(D)The new antenna is not more than approve any eligible facilities request (iii)Replacement of transmission
3 feet larger in height or width for a modification of an existing tower equipment.
(including all protuberances)than the or base station that does not (4)Eligible support structure.Any
pre-existing antenna,and substantially change the physical tower or base station as defined in this
(E)No new equipment cabinets are dimensions of such tower or base section,provided that it is existing at
visible from the adjacent streets or station, the time the relevant application is filed
surrounding public spaces;or (b)Definitions.Terms used in this with the State or local government
(iii)Other Visible Antennas.The new section have the following meanings. under this section.
antenna is visible from adjacent streets (1)Base station.A structure or (5)Existing.A constructed tower or
or surrounding public spaces,provided equipment at a fixed location that base station is existing for purposes of
that enables Commission-licensed or this section if it has been reviewed and
(A)It is located in the same vicinity authorized wireless communications approved under the applicable zoning
as a pre-existing antenna, between user equipment and a or siting process,or under another State
(B)The new antenna will be visible communications network.The term or local regulatory review process,
only from adjacent streets and does not encompass a tower as defined provided that a tower that has not been
surrounding public spaces that also in this subpart or any equipment reviewed and approved because it was
afford views of the pre-existing antenna, associated with a tower. not in a zoned area when it was built,
(C)The pre-existing antenna was not (i)The term includes,but is not but was lawfully constructed,is existing
deployed pursuant to the exclusion in limited to,equipment associated with for purposes of this definition.
this subsection wireless communications services such (6)Site.For towers other than towers
(§1.1307(a)(4)(ii)(B)(2)(iii)), as private,broadcast,and public safety in the public rights-of-way,the current
(D)The new antenna is not more than services,as well as unlicensed wireless boundaries of the leased or owned
three feet larger in height or width services and fixed wireless services property surrounding the tower and any
(including all protuberances)than the such as microwave backhaul. access or utility easements currently
pre-existing antenna,and (ii)The term includes,but is not related to the site,and,for other eligible
(E)No new equipment cabinets are limited to,radio transceivers,antennas, support structures,further restricted to
visible from the adjacent streets or coaxial or fiber-optic cable,regular and that area in proximity to the structure
surrounding public spaces; backup power supplies,and comparable and to other transmission equipment
(3)The new antenna complies with equipment,regardless of technological already deployed on the ground.
all zoning conditions and historic configuration(including Distributed (7)Substantial change.A
preservation conditions applicable to Antenna Systems and small-cell modification substantially changes the
existing antennas in the same vicinity networks). physical dimensions of an eligible
1270 Federal Register/Vol. 80, No. 5/Thursday, January, 8, 2015/Rules and Regulations
support structure if it meets any of the (8)Transmission equipment. moratorium on the review of
following criteria: Equipment that facilitates transmission applications.
W For towers other than towers in the for any Commission-licensed or (i)To toll the timeframe for
public rights-of-way,it increases the authorized wireless communication incompleteness,the reviewing State or
height of the tower by more than 10% service,including,but not limited to, local government must provide written
or by the height of one additional radio transceivers,antennas,coaxial or notice to the applicant within 30 days
antenna array with separation from the fiber-optic cable,and regular and of receipt of the application,clearly and
nearest existing antenna not to exceed backup power supply.The term specifically delineating all missing
twenty feet,whichever is greater;for includes equipment associated with documents or information.Such
other eligible support structures,it wireless communications services delineated information is limited to
increases the height of the structure by including,but not limited to,private, documents or information meeting the
more than 10% or more than ten feet, broadcast,and public safety services,as standard under paragraph(c)(1)of this
whichever is greater; well as unlicensed wireless services and section.
(A)Changes in height should be fixed wireless services such as GO The timeframe for review begins
measured from the original support microwave backhaul. running again when the applicant
structure in cases where deployments (9)Tower.Any structure built for the makes a supplemental submission in
are or will be separated horizontally, sole or primary purpose of supporting response to the State or local
such as on buildings'rooftops;in other any Commission-licensed or authorized government's notice of incompleteness.
circumstances,changes in height should antennas and their associated facilities, (iii)Following a supplemental
be measured from the dimensions of the including structures that are constructed submission,the State or local
tower or base station,inclusive of for wireless communications services government will have 10 days to notify
originally approved appurtenances and including,but not limited to,private, the applicant that the supplemental
any modifications that were approved broadcast,and public safety services,as submission did not provide the
prior to the passage of the Spectrum well as unlicensed wireless services and information identified in the original
Act. fixed wireless services such as notice delineating missing information.
(ii)For towers other than towers in microwave backhaul,and the associated The timeframe is tolled in the case of
the public rights-of-way,it involves site. second or subsequent notices pursuant
adding an appurtenance to the body of e th procedures identified in this
the tower that would protrude from the (c)Review of applications.A State or to P
edge of the tower more than twenty feet, local government may not deny and paragraph(c)(3).Second or subsequent
f
shall approve any eligible facilities notices of incompleteness may not
or more than the width of the tower
structure at the level of the request for modification of an eligible specify missing documents or
support structure that does not information that were not delineated in
other eligible support structures
appurtenance,whichever greater;for substantially change the physical the original notice of incompleteness,
,it dimensions of such structure. (4)Failure to act.In the event the
involves adding an appurtenance to the government
reviewing State or local
body of the structure that would (1)Documentation requirement for o g
protrude from the edge of the structure review.When an applicant asserts in fails to approve or deny a request
g a writing that request for modification is seeking approval under this section
by more than six feet;(iii)For any eligible support structure, covered by this section,a State or local within the timeframe for review
it involves installation of more than the government may require the applicant (accounting for any tolling),the request
standard number of new equipment to provide documentation or shall be deemed granted.The deemed
cabinets for the technology involved, information only to the extent grant does not become effective until the
but not to exceed four cabinets;or,for reasonably related to determining applicant notifies the applicable
towers in the public rights-of-way and whether the request meets the reviewing authority in writing after the
base stations,it involves installation of requirements of this section.A State or review period has expired(accounting
local government may not require an for any tolling)that the application has
any new equipment cabinets on the g Y q
ground if there are no pre-existing applicant to submit any other been deemed granted.
ground cabinets associated with the documentation,including but not (5)Remedies.Applicants and
structure,or else involves installation of limited to documentation intended to reviewing authorities may bring claims
ground cabinets that are more than 10/o e nee wireless o illustrate the for such wirel related to Section 6409(a)to any court
urisdiction.etent f competent'
larger in height or overall volume than facilities or to justify the business o P 1
any other ground cabinets associated decision to modify such wireless PART 17—CONSTRUCTION,
with the structure; facilities. MARKING,AND LIGHTING OF
(iv)It entails any excavation or (2) Timeframe for review.Within 60 ANTENNA STRUCTURES
deployment outside the current site; days of the date on which an applicant
(A It would defeat the concealment submits a request seeking approval i 5.The authority citation for part 17
elements of the eligible support under this section,the State or local continues to read as follows:
structure;or government shall approve the Authority:Sections 4,303,48 Stat.1066,
(vi)It does not comply with 'application unless it determines that the 1082,as amended;47 U.S.C.154,303.
conditions associated with the siting application is not covered by this Interpret or apply sections 301,309,48 Stat.
approval of the construction or section. 1081,1085 as amended;47 U.S.C.301,309.
modification of the eligible support (3)Tolling of the timeframe for ■6.Amend§17.4 by revising
structure or base station equipment, review.The 60-day period begins to run paragraphs(c)(1)(v)and(c)(1)(vi),and
provided however that this limitation when the application is filed,and may adding paragraph(c)(1)(vii)to read as
does not apply to any modification that be tolled only by mutual agreement or follows: -
is non-compliant only in a manner that in cases where the reviewing State or
would not exceed the thresholds local government determines that the §17.4 Antenna structure registration.
identified in§1.40001(b)(7)(i)through application is incomplete.The
(iv). timeframe for review is not tolled by a (c)
Federal Register/Vol. 80, No. 5/Thursday, January 8, 2015/Rules and Regulations 1271
(11 * * * structure where another Federal agency (E)Will either involve no excavation
(v)For any other change that does not has assumed such responsibilities or involve excavation only where the
alter the physical structure,lighting,or pursuant to a written agreement with depth of previous disturbance exceeds
location the Commission
geographic n of an existing (see§1.1311(e)of this the proposed construction depth
structure; chapter);or (excluding footings and other anchoring
(vi)For construction,modification,or (vii)For the construction or mechanisms)by at least two feet.An
replacement of an antenna structure on deployment of an antenna structure that applicant that relies on this exception
Federal land where another Federal will.( must wait 30 days after removal of the
agency has assumed responsibility for days,)
Be in place for no more than 60 antenna structure before relying on this
evaluating the potentially significant (B)Requires notice of construction to exception to deploy another antenna
environmental effect of the proposed the FAA structure covering substantially the
antenna structure on the quality of the (C)Does not require marking or same service area.
human environment and for invoking lighting under FAA regulations,
any required environmental impact (D)Will be less than 200 feet in height (FR Doc.2014-28897 Filed 1-7-15;8:45 aml
statement process,or for any other above ground level,and BILLING CODE 6712-01-P
• M
.ess.
oMf3*
Town of Barnstable
Zoning Board of Appeals
Decision and Notice .
Sprint Spectrum, LP Appeal Number 2000.31
arianc�S�ection 3-1.1(5)Bulk Regulations-Maximum Building Height
Summary: Granted with Conditions
Petitioner: Sprint Spectrum,LP
Property Address: 1047 Falmouth Road/Route 28,Hyannis
Assessor's Map/Parcel: Map 250,Parcel 004
Area: 0.83 acre
Zoning: RD-1 Residential D-1 Zoning District
Groundwater Overlay: GP Groundwater Protection District
Background:
The property consists of a 0.83 acre lot that is improved with an office building of approximately 5,611 sq.ft., and a
115 foot self supported radio tower. The existing building consists of two levels; an exposed finished basement and
a first floor level.
The applicant is proposing to replace the existing tower with a 120 foot monopole structure and associated base
equipment for use as a wireless communications facility. To allow the proposed facility, the applicant has applied
for the following zoning relief:
•• Appeal Number 1999.147-Special Permit pursuant to Section 4-4.4(2)Nonconforming Building or Structure
Not Used as Single or Two-Family Dwellings, to permit the replacement of an existing 115 foot radio tower with
a 120 foot monopole structure and associated base equipment station.
• Appeal Number 1999-148- Special Permit pursuant to Section 4-4.5(2) Expansion of a Pre-Existing
Nonconforming Use,to permit the replacement of an existing 115 foot radio tower with a 120 foot monopole
structure and associated base equipment station for use as a wireless communications facility.
• A—PP eal-Number 2000i31�.,V_r�ancexfromySecton 3--1.1.(5)- ulk Regulations-Maximum Building Height to
permit the tower to exceed the 30 foot height limitation on structures and allow 120 foot tower.
Procedural Summary:
This appeal was filed at the Town Clerk's Office and at the Office of the Zoning Board of Appeals on March
200 . A public hearing before the Zoning Board of Appeals was duly advertised and notices sent to all abutters in
accordance with MGL Chapter 40A. The Applicant and Board Chairman executed an extension of time to file the
decision. A copy of which is contained in the file.The hearing was opened on April 26,2000, and continued to May
10,2000 at which time the Board granted the variance with conditions.
Hearing Summary:
Board Members deciding this appeal were Gene Burman, Richard Boy,Tom DeRiemer, and Dan Creedon, and Gail
Nightingale, Acting Chairman. During the hearings, Attorney E-diard D. Pare,Jr. represented the applicant.
Attorney Pare reviewed the appeals. He noted that when the applicant was previously before the Board with
reference to Appeal 1999- 147 & 148,there was some concern regarding the uses on this site. On March 29,2000,
the Zoning Board of Appeals granted relief to the owner of the property and the property is now in compliance with
the-uses currently on the site.
Attorney Pare noted that at the previous hearing,the Board questioned the legal non-conforming structural status of
the tower, so- in the alternative-the applicant submitted this Variance request to bulk regulations, maximum
�uilding height. He also st
ated that since, the tower is already there, the use of this new antennae is allowed as-of-
right under t aI Wir�l o e
proposa needs a dimensional variance for the additional height. They will be rebuilding the tower for safety
reasons.
i
Town of Barnstable-Planning Department-Staff Report
Sprint Spectrum,LP-Appeal Number 2000731
Variance-Section 3-1.1(5)Bulk Regulations-Maximum Building Height
*Attorney Bruce Gilmore who represented the owner of the property(Randy Childs)at a previous hearing of Appeal
No. 2000-24 for a modification of an existing Special Perm itsNariances for the use of the locus, explained that the
existing tower was mentioned at the March 29, 2000 hearing of the appeal and cited in the Board's findings The
tower was:an accessory use,first by Childs Electric, and then by its successor Associated Alarm. -
William Hastings, RF Engineer Specialist, explained that Sprint needs to be up high on the monopole(120 feet high)
in order to separate them from Associated Alarm antennas. The height is also needed to cleacbe-trees,and at w
coverage of Hyannis. Sprint and Associated Alarm will be the only users o etFettower.
Kevin Washburn, an engineer from Clough, Harbour&Associates, LLP,explained the GPS antenna is very small in
size(about the size of a small drinking cup)and placed on the antennae to allow the signal to locate other Sprints
antennas. The tower is designed to accofnmodate one other use, but they are not now seeking a co-locator.
Attorney Pare reiterated that Sprint's use will be legal because communication antennas are allowed, under certain
conditions pursuant to'Section 4-8, in every zoning district. The variance request is for height, not use variance.
Ralph Crossen, Building Commissioner noted that the current tower does not have a building permit.
Public Comment: No one spoke in favor or in opposition to this appeal.
The Board asked the applicant to demonstrate variance conditions. Attorney Pare stated that since there is already
a tower on the site, this is a unique condition only to this site and not the neighborhood affected., The relief is for
only an ad ' ' nd as such not a detriment since here is currently a 115 foot tower on the site. If the
re ief is not granted it will be a rcishio to Sprint as they are required by the C o provide telecommunication
services throughout the StatP_They have to comply with the Telecommunlca i o 996 and without this relief
Sprint would suffer a substantial hardship. The immediate area is largely commercial and the relief can be granted
without substantial de riment to the public good or the neighborhood affected.
The Board was concerned with the nature of relief needed. They determined to request the Town Attorney review
the case and advise on the relief needed. The Board continued the appeal to May 10, 2000.
eAt the May 10, 2000, continuance Acting Chairman Gail Nightingale expressed concern for the tower as an existing
communication tower as defined in the Personal Wireless Communications Section of the Ordinance. Town
Attorney Robert Smith responded that defining the tower in that context would not have a bearing in this particular
case. The relief needed for Sprint Spectrum can be granted by means of a dimensional variance. Part one of
Section 4-8(3), Personal Wireless Communications,deals with communication devices, antennas and appliances
on existing structures. The"use'-"wireless communication"is permitted everywhere in Town of Barnstable on
existing structures. It is only the height of the structure that needs relief in this case. That can be done through a
dimensional Variance.
Fillings of Fact: -
��+ �%t the hearing of May 10,2000,the Board found the following findings of fact as related to Appeal No.2000-31:
� 1. The applicant, Sprint Spectrum LP, is seeking a Variance from Section 3-1.1(5)Bulk Regulations-Maximum
�j Building Height.
2. The property address is 1047 Falmouth Road/Route 28, Hyannis, MA,as shown on Assessor's Map 250, Parcel
004 and located in the RD-1 Residential D-1 Zoning District and the GP Groundwater Protection Overlay
District.
(S '� 3. The petitioner is seeking to replace an existing 115 foot-tall tower structure with a 120 foot-tall monopole.
1U 4. The applicant originally proposed to accomplish this segment of the plan through a request for a Special Permit
(Appeal Number 1999-147)pursuant to Section 4-4.4(2)Nonconforming Building or Structure Not Used as
e Single or Two-Family Dwellings
lie� As to MGL Chapter 40A, Section 10 Variance Conditions,the topography of the site is burdened with a great
(0 slope which is unique t E p perty. This monopole could add visual pollution to the area,but there is a need
to take care of the people in the town who need cell phones. It would be a hardship for the applicant to locate
outside t is area which would lead to a gap in service and p ace the applicant in jeopardy of penalty from the
< FCC. There are conditions on the site that warrant the grant of a variance.
�( The neighborhood is surrounded by commercial businesses across the street and down the road.
The relief may be granted without substantial detriment to the public good. There may be visual pollution,
however proper screening and painting would help.
8. The relief may be granted without nullifying or substantially derogating from the intent or purpose of the Zoning .
Ordinance as there is a need in the town for this type of service.
r01\cam' �5 2s C `� cv r i��-^'�-( 2
Town of Barnstable-Planning Department-Staff Report
Sprint Spectrum,LP-Appeal Number 2000-31
Variance-Section 3-1.1(5)Bulk Regulations-Maximum Building Height
•9. During the course of these proceedings there was no opposition voiced by any abutters.
The vote was as follows:
AYE: Gene Burman, Richard Boy,Tom DeRiemer, and Dan Creedon
NAY: Acting Chairman Gail Nightingale
Ms.Nightingale voted in the negative because she felt this was not within the spirit and intent of the Zoning Ordinance.
Decision:
Based on the findings of fact, a motion was duly made and seconded to grant the relief being sought in Appeal No.
2000-31 subject to the following terms and conditions:
1. The property shall be developed in accordance with the approved site plan titled"Sprint Spectrum, LP Site I.D.#
BS13XC661 B4 Associated Alarm System 1047 Falmouth Road Hyannis, MA 02601", prepared by Clough,
Harbour&Associates LLP and dated March 2000.
2. The proposed monopole, including all antennas, shall not exceed a height of 120 fe@t.
The cglciLo tte monopole shall be earthtone to lessen the visual impact.
4. If use of the monopole is abandoned or not used for a period of one (1)year, the pole shall be removed within
30 days and the site resto—red. This is to be done by the petitioner.
5. If transmissions from this pole or its antennae interfere with any local television, radio,telephone, alarm system,
or other electronic equipment, Sprint Spectrum, o l s successor shall have 20 days to rectify the situation. If
not rectified within those 20 days,the Building Commissioner shall order the communication devices to be shut
down immediately.
6. There shall be no further development of the subject property without Zoning Board of Appeals, Board of Health
and Site Plan eview approval.
7. The petitioner shall post a Performance Bond acceptable to the Legal Department or its Designee for removal
of the monopole.
8. There shall be no more than nine(9)antennas from Sprint Spectrum, LLP and two whip antennas which is in
accordance with the plan submitted.
The vote was as follows:
AYE: Gene Burman, Richard Boy,Tom DeRiemer,and Dan Creedon
NAY: Acting Chairman Gail Nightingale
Ms. Nightingale voted in the negative because she felt the granting of the Variance was not in compliance with the
Zoning Ordinance.
Order:
Uar nce-N.umberr20.0.0. 3-1_has=been_granted with conditions.
Appeals of this decision, if any, shall be made pursuant to MGL Chapter 40A, Section 17,within twenty(20)days
after the date of the filing of this decision in the office of the Town Clerk.
Acting Chairman Gail Nightingale Date Signed
I Linda Hutchenrider, Clerk of the Town of Barnstable, Barnstable County, Massachusetts, hereby certify that twenty
(20)days have elapsed since the Zoning Board of Appeals filed this decision and that no appeal of the decision has
been filed in the office of the Town Clerk.
Signed and sealed this day of under the pains and penalties of perjury.
Linda Hutchenrider,Town Clerk
3
PARCEL •ID 260 '004 �: GR687AGE"ID
'ADDR98 1047 F LMQ Fmp � 26 j
PrHONE• `
R.3 ' 14YANNIS
DLOCp: .. .,, raT :Sr7u
DROMP DI TR CT HY°
` PERMIT 48H18
i DEscAi0tib
P
ERMIT TYPE BMISC TXTLB
CONTRACTORS: .J.A.WOODS � °•` Department of Heal h; Safely
ARCEiITECT5
and environmental.Services
TOTAL FE$S: s8a4.50
Im
BOND $.00
�;CCINSTRUCTION COSTS $145,.000.00 -
3
763 MISC. 90T CODED -ELSEWHERE Y PRIVATS P
.,By. ,
DATE I.SMW .` ,0� , C!%2t t1 BX?lRATIpN DATE' ,h 1:Yxi.: b
U ',
Y .
x '3.`,. ,f:;:ti.�� +y.:•�+'`,�y�y. ' ;�.:. �.�: yy),.p ,y,... ;�µ.:� ':a� �-:wo_t.•�.
_ .;+ '��, '�T. ,'sir::,•, t"s�>.,tit'i+.°, r
�• i - 'S'3. . !'v at`� � ..s.. :•.tn 2' Z-'.J'{?..`0. •^ '1 v '• '' `..:T •'x y::15..0 aq .7'- ��;x.'{+•x.St r4y:;.f�'a Y.�..r �3, t
a %."..•+'- � i3 y. J-.. .•r'.qi. i•• } ' -n�i•.'.:.�.�rj.Y R. .h�1�'.�'1�.
h 'tH18 0ERMIT Ct?NVEY3 NO RIGHT YO OOCWPII ANY STREET ALLEY OR SIDE'WALk OR:l4�it'PART THEREOF ERHEA TEMPOF"ILY OR;PERMA i4TIi EN•
: PROACd4MENTS ON PUBUCPROPERTX NO SPEGFICAI:1.Y R,ERMITT.ED"UNDER THE'0 DIN4 CODE,MUST BE APPROVED SYTI•IE'Wii;tus ICmON;STRE,ETOR;
{lit EY GRAf3E5 AS WEi;L A3 DE#'TFfAND LOCATIQAI OF,t�Uk C.I FWtAS MAYBE OBTNNI[)FfiOMTHE DEf ARTMENT OF PUBLIC NjORKS,lffiE ISSUAQlCEOFTHIS
E
oOESRELEASE THEAPPL(CANT FFtt}Iil tF1EGQNbIT[f3NSOFANYAPPLICABLESUBDIVISIONRESTRICTIONS UM OF FOUR CALL INSPECTIONS'REQUIREO ;x, ,.OALL.CONSTRUCTION WORK: 'APPAO/0)"i'LANS MUST BE RETAINED ON�IOBAND �.170 UNDATIONS OR FOOTINGS: THIS CARD KEPT PASTED,UNTIL FINAI;INSRECTIt)N; WRERE:APPLICABLE,;$EPARATE: '
!PERMITS :AiIE'REOLII.2.PRIOR TO COVERING STRUCTURAL MEMBERS,' �BEEN MADM..WIikRIi:W GMRTIFICATE 6F OCCU-•a � IiMO •F¢fI
{READYTO LATH}. PANC .IS REC2LIAm-SUCH$UImD p SliAj( t1171.5E. ECTAICAL,'PLUM ING ANP MFCH.,
-3.INSULATION.
'4.FINAL W _ UNTiI:F{NAL INSPI;GTION I�A f BId MA>}E. 'ANIGIII lNtg1ALLA NS': ':s: -
SPECTION BEFORE OCCUPAN 1(
l °BUILDING INSPECTION APPROVALS 1RLUMBING INSPECTION APPROVALS: EL,ECTR.ICAL WSPEGTiON APPROVALS
f r Ctx^£'- •&. }hP' <`y .�g. ,.. .. • "J , ',b. - •'34.'L a"F�.:Y.:t�.-y.f, ;, .; • :`try'i y 'L.•, r
ilk
Ali
S ' 1 HEATING INSPECTION APPROVALS ENGINEERING DEPARTMENT-
2 BOARD OF HEALTH
OTHER: SITE PLAN REVIEW APPROVAL
WORK SHALL NOT PROCEED UNTIL. PERMIT WILL BECOME NULL ANo VOID IF CON. INSPECTIONS INDICATPP ON THIS.
THE INSPECTOR HAS APPROVED THE STRUCl ION WORK IS NOT STARTED WITHIN SIX CARD CAN BE ARRANGED FOR BY
VARIOUS STAGES OF CONSTRUC- MONTHS OF_OATE THE PERMIT IS ISSUED As TELEPHQNEOR'WRIT-rEN NOTIFICA.
TION. Ni?TED.ABOVE.
TION. ,
3 2 q �d
• Town of Barnstable
Planning Department 0-@?Ct j
Staff Report
eal-Number 20Q0-24
y-Modittcatte - #`-Var-t'ance�{.o. 1975-93 f+
-..,., A .
Date: March 23,2000
To: Zoning:Board of Appeals
From:
Approved By: Robert chernig,A1CP, Planning Director
Art Traczyk, Principal Planner
Applicant: Randy Childs
Address: 1047 Falmouth Road/Route 28,Hyannis,MA
Assessor's Map/Parcel: Assessors Map 250,Parcel 004
Area: 0.83 acre
Zoning: RD-1 Residential RD-1 Zoning District
Groundwater Overlay: GP Groundwater Protection District
Filed:February 26,2000 Hearing:March 29,2000 Decision Due:June 7,2000
Background:
The property consists of'a 0.83 acre lot that is improved with an office building of approximately 5,611 sq. It.'
a 115 foot radio tower. The existing building consists of two levels; a finished basement and a first floor
level. Due to the grade of the site,which slopes toward the rear of the roe the
p p rty, basement is exposed on
,and
the back side.
As the Board Members may recall, the issue before them originated at the December 01, 1W9 hearing
involving Appeal Nos. 1999-147 and 148 as related to a proposed`rebuilding of the colmmunication tower.by
Sprint Spectrum, LP. During that hearing questions were raised a6 to the.uses on the,site and Compliance
with the conditions of Variance No. 1975-93(see attached Variance No. 1975-93). That Variance is very
specific in terms of the permitted uses. The conditions Imposed were as follows;
1) There shall be only two businesses on locus
a) The Electric Lighting Company in conjunction with the Alarm Company
b) A bookstore
2) The bookstore shall be limited to:
a) the location in the building as shown on the plans submitted
b) the sale of books only-not newspapers or periodicals
3) There shall be one sign of no larger than 12 square feet each
a), for the Electric Lighting portion of the joint use
b) for the Alarm System portion of the joint use
c) for the bookstore
4) The grant of the modification of the variance does not allow for and does not imply three separate
uses differing in the use. The Electric Lighting Company and the Alarm Company are to be
considered as one,joint use. The bookstore is the second use. '
Today,the applicant is seeking to modify those conditions to permit four(4),office Units. At present those
units are occupied by Elkman Bookkeeping, Briggs&ROM Plumbing &Heating, Hyannis.Chlropractic and
associated Alarm System, Inc. Sprint Spectrum, LP is considering locating also on the silo; only with respect
rebuilding of the existing tower and locating its antennas In combination with:existing communications.
Source-Assessor's records dated 1122/99 ,( r of
6 1 � ,'_ } .
Town of Barnstable-Planning Department-Staff Report "
Childs-Appeal Number 2000-24
Modification of Variance No.1975-93
• This issue however is the subject of Appeal Nos. 1999-147 and 1999-148 and are not before the Board
today. This applicant is requesting only to legitimize those uses that are there today.
Prior ZBA Action:
Appeal Number 1968-105
The Board granted a Use Variance to permit the construction of a 36'x 64'building to be used as an
electrical contracting business and rental offices in a Residence A-1 District. At that time,the only principal
permitted uses were detached one family dwellings and the renting of rooms for not more than 6 lodgers by a
family resident in the dwelling.
Appeal Number 1971-23
The Board granted permission for the construction of a 1,976 sq. ft addition to the existing building to be
used for 4 additional offices and storage. There.is a discrepancy between the Facts and Decision for this
appeal,the legal notice and the application. The Facts and Decision states that a Special Permit was
granted for the expansion of a nonconforming use. The legal notice states this appeal is an appeal of the
Building Inspector as well as a request for a Variance. The application for this appeal requests a Variance to
Section I, Paragraph 2-Residence Al District. The original building was permitted by a Use Variance to a
Special Permit for the expansion of a nonconforming use would not have been appropriate relief.
Appeal Number 1975-93
The Board granted a modification of the previously approved Variances to permit a change of use from office
space to retail space. Appeal Numbers 1968-105 and 1971-23 allowed a retail lighting shop and 2,500 sq.ft.
• of office space. The Board granted this modification with the following conditions:
1) There shall be only two businesses on locus
a) The Electric Lighting Company in conjunction with the Alarm Company
b) A bookstore
2) The bookstore shall-be limited to:
a) the location in the building as shown on the plans submitted
b) the sale of books only-not newspapers or periodicals
3) There shall be.one sign of no larger than 12 square feet each
a) for the Electric Lighting portion of the joint use
b) for the Alarm System portion of the joint use
c) for the bookstore
4) The grant of the modification of the variance does not allow for and does not imply three separate uses
differing in the use. The Electric Lighting Company and the Alarm Company are to be considered as
one,joint use. The bookstore is the second use.
Appeal Number 1978-19-_Withdrawn-Not Applicable
This was a request to allow the construction of a 24'x 40'addition to the rear of the existing building and a
Variance from the signboard regulations. This appeal was withdrawn because the application, and
subsequently the legal advertisement, stated it was a request for a Special Permit when.it should have been
for a Variance.
Appeal Number 1978-42-Withdrawn-Not Applicable
This appeal was a request for a Variance to allow an addition to the existing building and a Variance from the
sign code regulations(similar to the relief requested in Appeal No. 1978-19). At the request of the applicant,
it was withdrawn without prejudice due to the absence of the applicant's attorney.
Appeal Number 1978-53-Denied-Not Applicable
The Board denied a request for a Variance from the sign code regulations.
2
Town of Barnstable-Planning Department-Staff Report
Childs-Appeal Number 2000-24
Modification of Variance No.1975-93
Appeal Number 154:Denied--Not Applicable
M&_B_w-d-deQied.arevue___ s� t fora Variance/Speeiall-Permit to permit the construction of a 24'x 40"addition to
the rear of the existing building.
Staff Review;
The applicant was before the Site Plan Review Committee on February 17, 2000 and was approved pending
a revised plan indicating that;
1. the perimeter fencing along Blackberry Lane is within or on the property line and,
2. the parking lot•is re-configured and re-striped to meet today's requirements.
Those change have been incorporated and the revised approved site plan has been submitted to the file.
The site is located within a GP Groundwater Protection Overlay District. The applicant has cited that on-site
wastewater disposal is handled by 6 cesspools and 1 precast leaching pit. At the request of the Health
Agent, those systems were inspected on February 23,2000, and it was determined that they are in proper
working order. The Health Agent was satisfied with the existing on-site wastewater disposal.
Variance Findings:
In consideration for the modification of the condition enumerated in 1975 Variances, the applicant must
substantiate those conditions unique to this lot that justify modification of the conditions.
Suggested Conditions:
If the Board should find to grant,the requested modification, they may wish to consider the following
• conditions:
1. There shall be no more than 4 office suite located within the building. No medical offices that receive or ^
give patients care are permitted except that, the existing chiropractic office shall be allowed to operate
until it moves or ceases. At that time, the space shall revert to an office use only and shall not be reused
for chiropractic medical care.
2. Within one year of the issuance of this modification,the site shall be improved as represented to Site
Plan Review and as shown on wplan titled"Comprehensive Site Plan"for Reld Corporation, drawn by
Clough, Harbour&Associates and as approved by the Site Plan Review Committee dated February 24,
2000.
3) There shall be only one sign permitted of the site that shall not exceed 36 square feet.
Attachments: Applications Copies: Petitioner/Applicant
Approved,Site Plan
Assessor's Field Cards
GIS Map
Subsurface Sewage Disposal System Inspection
3
• TOWN OF BARNSTABLE - ZONING BOARD OF APPEALS
Excerpts from the minutes of December 01,1999
Appeal Number 1999-146 and Appeal Number 1999-147 Sprint Spectrum,LP
Board Members hearing these appeals were Gene Burman,Richard Boy,Gail Nightingale,Ralph Copeland,and
Chairman Emmett Glynn. Both Alternate Board Member Tom DeRiemer and Dan Creedon were present and can
replace any Board Member(s)if necessary. Attorney Edward D.Pare,Jr.represented the applicant. Supporting
staff present included Matthew Fallon,Site Acquisition Consultant;Kevin Washburn,Project Engineer;and Steve
Desmarais,R.F.Engineer. Attorney Pare previously submitted a memorandum to the file which all Board Members
have received.
The Board asked the applicant to show standing. A lease agreement with the-owner was submitted. In addition,the
owner of the property,Randolph E.ChiIds,was present and reported the applicant has his permission to seek the
requested relief.
Attorney Pare explained that Sprint Spectrum proposes to replace an existing 115 foot-tall tower structure with a
120 foot-tall monopole and install associated base equipment on the land. This is an additional five feet from the
original structure. As background,Attorney Pare reported that the Applicant,Sprint Spectrum and Wireless Co,
L.P.,are wholly owned subsidiaries of Sprint Corporation,the long distance telephone company. Wireless Co,L.P.
is a subsidiary of Sprint Spectrum. In 1995,Wireless Co,L.P.was issued a Radio Station Authorization by the
Federal Communications Commission(FCC)for PCS wireless broadcast with respect to the Massachusetts area. At
this time,Sprint Spectrum is actively building-out its PCS system on a nationwide basis and began providing
service to Massachusetts customers in November of 1997. PCS is the next generation of wireless
telecommunications which utilizes digital technology to provide substantially improved clarity,privacy,and all-in-
one communications. In contrast to existing analog systems,digital PCS technology provides a much clearer signal
(by eliminating interference with computer technology)and allows for the delivery of fax,computer,and other data
transmissions without the need for telephone lines. Most importantly,as the digital signal cannot be intercepted
with common radio scanners,PCS communications are confidential and secure. A copy of the FCC license to
Sprint was submitted in the memorandum.
The licensing process was reviewed by Attorney Pare. In 1996,the Telecommunications Act of 1996,deregulated
the telecommunications industry to provide for competition. Carriers were sought with the ability to locate
4tantennas,and provide telecommunication services through the construction of towers and co-location on existing
towers. Sprint Spectrum is one of a limited number of companies licensed by the FCC to provide PCS to the
residents and businesses of the Town of Barnstable. As a licensee of ih&FtC,Sprint Spectrum is mandated to
build-out and operate its system such that adequate wire ess service is provided to the general public.
The site selection process includes the idea of co-Iocating on existing towers. This is usually easier and costs less
money and does not impact the general area of the tower. The existing tower must have sufficient height and
strength to be able to handle the additional antenna and wires. Another alternative is to rebuild or extend and
strengthen existing towers. Lastly,would be new tower construction. The applicant seeks to dismantle the existing
tower and replace it with a monopole structure 5 feet higher than the current tower. Thus,the applicants are seeking
a Special Permit to expand the non-conforming structure and a Special Permit to expand the non-conforming use on
this site.
At this time,the Board asked the applicant if he had proof that the current tower on this site is a legal pre-existing
nonconforming structure and a legal pre-existing nonconforming use. In Attorney Pare's opinion,the existing
tower structure constitutes a pre-existing nonconforming use because it was constructed pursuant to a license issued
by the FCC on October 10, 1975. There is no building permit on file in the town. The owner of the site,Randolph
Childs,addressed the Board and explained that he conferred with the building inspector at the time of installation of
the existing tower structure and was advised to seek the approval of th_ Pam[' the FAA(Federal Aviation
Administration),-and the Barnstable Municipal Airport He then erected the tower structure pursuant to that FCC
license. He was told it could not have—lights-and it does not have any lights. Mr.Childs never filed for a building
permit because he was led to believe one was not needed. The tower was constructed in plain view of the town and
0he has never been told he was in violation. The tower is not in the flight path of the airport.
` ILul�i`i
e
The Board was still concerned about procedure. They questioned how the applicant can propose to change a \\
• nonconforming use if it is not a legal nonconforming use. Attorney Pare felt this could be allowed under MGL ®
Chapter 40A,Section 7 grandfather rights,however the Board did not agree with him. That section states the U
violation can not be enforced after a certain number of years-not-that after a certain number of years the use
becomes legal. The Board stated the applicant must prove the use is legal. Attorney Pare read from the Mass.
Zoning Manual,Section 6-29,which refers to Section 7 protection and the allowance of certain minor changes to a
structure if the cha n Attorney Pare'.s opinion,the Board has the authority to grant
additional height to this tower as a grandfathered nonconforming structure. The replacement of the tower with a
new tower makes sense because the existing tower would not be able to hand e t eir antennas or cables an w
tower will be structur d The area already w the visu impact of a tower as a tower already exists on this
site. The base of the proposed tower is 5 feet and the base _existing tower isTfeet.
e Board explained to the applicant that other telecommunication carriers have been before the Board and were -Z>o e.S moo .
granted approval on other sites within the town. 'However,on this site because of the relief being reguested..ix-is- ►"'% -N-Qr h`
the burden of the a licant to prove this tower is ale al re-existin nonconforming use and re-exishn
nonconforming structure. ey so e t that since the applicant is putting up a new tower it was not an expansion
of an existing Iower. The Board did not want to continue until the legality of the tower and the use could be
verified..
The applicant has Site Plan Review approval but without the Building Commissioner present this evening,the
Board could not ask him if this issue of a legal pre-existing nonconforming use/structure was brought up at Site
Plan Review.
The Board noted that this site was before them for numerous requests for zoning relief but the tower was never
mentioned in any of the files. A tower was never shown on any plans. The site was granted a modification in 1975
for two business uses only. According to the Staff Report,on a recent site visit conducted on 11/22/99,it appears
the terms and conditions of Appeal Number 1975-93 are not being met in that there are more than 2 businesses on
the premises. The signs at this location indicate that there are five separate businesses. The Board asked the
applicant if he could address the uses on the site and he indicated he could not comment as he did not know what
was there because he was only interested in the tower. The Board indicated they would like the Building
Commissioner to look into any possible violations of the current Variances and questioned if the owner should seek ��
a modification of these Variances. ` . 111 1
Attorney Pare stressed that the tower was constructed pursuant to an FCC license. Perhaps at that time,a building
permit was not required for the tower if the FCC issued a license. Mr.Childs thought the tower was-and has n
-` egal ail t r
Until certain issues could be resolved the Board chose to continue these appeals. The Board requested and/or still
needed clarification of the following:
• a report from the Building Commissioner regarding these appeals,
• does this appeal need to go back to Site Plan Review?,
• the legality of the tower structure and the use of the tower,
• the different uses on the site-are they legal?,
• would this use of the site by Sprint be considered a new use on this site?,
• should the existing Variance(s)be modified since there are more uses on the site,
• if this is a lawful accessory use,how can it now become a pre-existing nonconforming use?,and
• if the existing tower is dismantled and a new tower is built how can this be considered an expansion?
Attorney Pare indicated he would like to talk to the Town Attorney regarding the issue of grandfathering and the
issue of a legal pre-existing nonco
Appeal Number 1999-147 and Appeal Number 1999-148 are continued to February 02,2000 at 8:30 PM.
i
I
I
Chapter 240: ZONING
[HISTORY:Adopted by the Town of Barnstable 4-7-1987 STM by Art.4; readopted 9-27-1990 by Order No.90-
65 Editor's Note:The readoption of the Zoning Ordinance on 9-27-1990 was its conversion from bylaw adopted by the former Town Meeting
. to an ordinance adopted by the present Town Council.The amendment dates noted in the text of the chapter include amendments to the
original bylaw.(Art. III of Ch. III of the General Ordinances, as updated through 4-10-2003). Amendments noted
where applicable.]
GENERAL REFERENCES
Noncriminal disposition— See Ch.1,Art.I.
Affordable housing— See Ch.9.
Building construction— See Ch.51.
Hazardous materials— See Chs.108 and 381.
Historic properties— See Ch.112.
Outdoor businesses— See Ch.141.
Signs— See Ch.192.
Wetlands protection— See Ch.237.
Food establishments— See Ch.322.
On-site sewage disposal systems— See Ch.360.
Wells— See Ch.397.
Marinas— See Ch.405.
Junk dealers-- See Ch.502.
Subdivision Rules and Regulations— See Ch.801.
ARTICLE I Introduction
§240-1.Title.
This chapter shall be known and may be referred to as the "Zoning Ordinance of the Town of Barnstable,
Massachusetts."
§240-2. Purpose.
The purpose of this chapter is to promote the health, saf_ e_ ty. convenience, morals and general welfare of the
inhabitants of the Town of Barnstable,to protect and conserve the_vaueof the prope y wn,to
increase the amenities of the Town, and to secure safety from seasonal or periodic flooding,fire,congestion or
confusion, all in accord with the General Laws, Chapter 40A, as amended. For this purpose,the height, number
of stories, size of buildings and structures, size and width of lots,the percentage of lot that may be occupied, the
size of yards, courts'and other open spaces, the density of population and the location and use of buildings,
structures and land for trade, marine business, industry, agriculture, residence or other purposes are regulated
within the Town of Barnstable as hereinafter provided.
§240-3. Interpretation.
The provisions of this chapter shall be held to be the minimum requirements for the promotion of the purposes
herein stated, and shall be interpreted and applied in accordance with the following:
A- Overlapping/contradictory regulations. Except as otherwise provided herein,this chapter shall not interfere
with-or annul any other ordinance, rule, regulation or permit, provided that, unless specifically excepted,
where this chapter is more stringent, it shall control.
B. Cumulative provisions. The provisions of this chapter shall be construed as a continuation thereof and not
as new enactments.
§240-4.Severability.
The provisions of this chapter are severable. If any court of competent jurisdiction shall invalidate any provision
herein, such invalidation shall not affect any other provisions of this chapter. If any court of competent jurisdiction
shall invalidate the application of any provision of this chapter to a particular case, such invalidation shall not
affect the application of said provision to any other case within the Town.
ARTICLE 11 General Provisions
§240-5. Establishment of districts.[Amended 7-15-1999; 10-26-2000; 2-1-2001; 11-18-2004 by Order No.
2004-113; 1-20-2005 by Order No. 2005-038; 1-20-2005 by Order No. 2005-039]
In order to carry out the purpose of this chapter, the following districts are hereby established:
• Residential Districts
RB Residence B District
RB-1 Residence B-1 District
RC Residence C District
RC-1 Residence C-1 District
RC-2 Residence C-2 District
RD Residence D District
RD-1 Residence D-1 District
RF Residence F District
RF-1 Residence F-1 District
RF-2 Residence F-2 District
RG Residence G District
RAH Residence AH District
Office Districts
PR Professional Residential District
HO Highway Office District
OR Office District
• 0-1, O-2 Office Districts
and O-3
Commercial Districts
B Business District
BA Business A District
BL-B Business Limited B District
MB-Al Marine Business Al District
MB-A2 Marine Business A2 District
MB-B Marine Business B District
VB-A Village Business A District
VB-B Village Business B District
HB Highway Business District
UB Urban Business District
S&D Service and Distribution District
SD-1 Service and Distribution District
B-1. Business.District
MA-2 Business District
MA-1 Business District
• Industrial Districts
IND LIMITED Industrial Limited District
IND Industrial District
§240-105. Required procedures for site plan review.
A. At least six copies are required of all site plan sheets, drawings and written information. Submissions shall
be delivered to the Building Department.
B. Within five working days of receiving a site plan,the Building Commissioner or his designee shall distribute
copies of the site plan to the Department of Planning and Development, the Department of Public Works
and the Board of Health.
C. Upon receipt of a site plan from the Building Commissioner or his designee,the agencies as noted in
Subsection B shall respond in writing, by notations on the site plan,or both, as to the propriety of the
proposed development, within the context of each agency's jurisdiction. Such response shall be made to the
Building Commissioner or his designee within 10 working days of each agency's receipt of the site plan.
D. The Building Commissioner or his designee may solicit the advice of any other Town agency or department
he deems necessary to properly make the determinations required by this article.
E. Site plans shall be reviewed for consistency with zoning and other applicable regulations and standards,
and within 20 working days of receiving a site plan, the Building Commissioner or his designee,shall notify
the applicant of any approval, conditional approval or disapproval, stating reasons.
F. One copy of the approved site plan shall be provided each to the applicant, the Department of Planning and
Development, the Department of Public Works and the Board of Health. One copy of the approved site plan
shall remain in the records of the Building Department.
G. Upon completion of all work, a letter of certification, made upon knowledge and belief according to
professional standards, shall be submitted to the Building Commissioner or his designee by a registered
engineer or registered land surveyor, as appropriate to the work involved,that all work has been done
substantially in compliance with the approved site plan, except that the Building Commissioner or his
designee may certify compliance.
ARTICLE X Personal Wireless Communication [Added 6-3-1999 by Order No. 99-074A]
§240-106. Purpose and intent.
It is the intent of this article to provide for the location and siting of wireless service communication facilities and
their accessory structures in accordance with the Telecommunications Act of 1996, to provide for the orderly
provision of facilities; ensure public safety; and to minimize adverse visual impacts upon both residential and
nonresidential areas.
§240-107. Requirements for all personal wireless facilities in all zoning districts. j
A. Installation and construction of all personal wireless service facilities, including but not limited to antennas,
mounts, equipment shelters and structures,shall be subject to Article IX Site Plan Review, and shall require
issuance of a building permit.
B. The applicant shall provide site plan review with evidence that they are a licensed carrier, authorized by the
Federal Communications Commission(FCC)to construct and operate personal wireless services, and that
the proposed transmitters are FCC regulated and approved.
C. The structure to which any mount or antenna is attached is a legally built structure under zoning, or a
preexisting, legal nonconforming structure.
D. If the location is within a designated historic district, the applicant shall secure a certificate of
appropriateness,to the extent required.
E. Structural components including guy wire anchors and equipment shelters shall comply with all required
setbacks of the zoning district.
F. Any equipment or base receiver station, not located within an existing building or underground vault, shall
be designed to fit in with traditional Cape Cod architecture styles and materials, or shall be screened from
view-
§240-108.Antennas permitted by special permit in all zoning districts.
Except where permitted as of right in§240-109 below, in all zoning districts, an antenna mounted or located on
any existing building or structure other than a communications tower may be permitted by special permit from the
Zoning Board of Appeals, provided that no antenna exceeds the height of the existing structure by more than 12
feet, unless the Board finds that additional height is necessary to provide coverage, and the additional height will
not be visually intrusive upon the surrounding area.
§240-109.Antennas permitted as of right in all zoning district.
Antennas permitted as of right in all zoning district shall be as follows:
A. An antenna and/or tower used in accordance with the terms of an amateur radio service license issued by
the Fed Ilbmmunications Commission provided that any facility tower is not licensed or used for any
commercial use,subject to all the requirements of§240-8, Exempt uses.
B. Television and radio anteana-so, including satellite dishes not exceeding a diameter of four feet,for personal
use, accessory to a residential use, or to provide entertainment for a single business such as a restaurant.
C. Ana_rdenna-completely enclosed within an existing structure other than a communications tower, provided
that the associated equipment or base transceiver station is located within an underground vault, or within
an existing building or addition thereto, other than an equipment or base receiver shelter.
D. An antenna located upon the roof of an existing building or structure other than a communications tower,
provided at the antenna does not exceed a height of 12 feet, and provided that the equipment shelter is
set back from the roof edge a distance equal to the height of the equipment shelter
E. An antenna located on a water tower belonging to a public water supply utility, by permission of the water
utility, not to exceed the height of the water tower by more than 12 feet, except that the Zoning Board of
Appeals may by special permit increase the height of the antenna up to 20 feet where the location of the
water tower and design of the antenna is such that it will not be visually intrusive upon the surrounding area.
F. Antennas located on existing utility stanchions, not to exceed a height of 12 feet above the utility stanchions,
located within a Commonwealth Electric Company easement,with permission of the landowner to location
and maintenance of an equipment or base receiver station shelter, or submission of recorded easement
language demonstrating the right to install an equipment or base receiver station for a wireless
communication facility.
ARTICLE XI Growth Management [Added 7-19-2001 by Order No. 2001-118 Note:The following
Growth Management Ordinance is a DCPC(District of Critical Planning Concern)implementing regulation.The DCPC was approved by the
Barnstable Assembly of Delegates on September 5,2001;and the Cape Cod Commission gave its final approval on September 20,2001.
• The Commission also approved this ordinance(originally approved by the Barnstable Town Council on July 19,2001)as the implementing
regulation on September 20,2001.This implementing ordinance became a part of the Zoning Ordinance on September 21,2001.
§240-110.Authority.
This article is adopted under the authority of the Home Rule Amendment,Article 89 of the Constitution of the
Commonwealth,the Cape Cod Commission Act, Chapter 716 of the Acts of 1989, as amended, MGL Ch.40A,
Ch.41 §§81 L through 81 GG, and Ch. 111.
§240-111. Purposes.
A. The purpose of this article is to ensure that a harmonious pattern and predictable rate of development
occurs in Barnstable, which protects the health, safety and welfare of current and future Barnstable
residents.The consequences of the historical and current patterns and rates of development in Barnstable
such as our historic inability to fund our capital needs and the further degradation of our environmental
assets are described in the Local Comprehensive Plan.The rate of residential development in Barnstable is
determined by and should not exceed the ability of the Town to provide adequate infrastructure and to
protect the natural environment. In addition,this development rate is intended to further the legitimate
commonwealth and local interests in the provision of a fair share of housing that is affordable to persons
with both low and moderate incomes. This development rate will also guard against potential increases in
the growth rate, which could adversely affect the Town's environmental resources, economy and land
values.
B. This article establishes a development rate adequate to ensure that the Town,with prudent reliance on local
and other financial sources and in compliance with the revenue generating guidelines of Proposition 2 1/2,
can and will provide infrastructure and operate in a manner which provides current and future Barnstable
residents with an adequate and responsible level of Town services, as defined by relevant, commonly
accepted professional standards.This article also establishes a development rate adequate to ensure that
• the Town has the ability to implement its affordable housing goals, as set forth in the Barnstable Local
Comprehensive Plan as updated by the Barnstable Affordable Housing Plan dated January 31, 2001.Editors
Note:See Ch.9,Affordable Housing.
C. It is anticipated by this article that during the time until buildout occurs,the Town will strive to upgrade its
infrastructure to keep pace with its total population, as outlined in the Capital Improvements Plan and
consistent with the growth rate established by this article. This includes the preparation of a long-term
capital plan and a commitment to make contributions, as practical, to infrastructure and to the established
DocuSign Envelope ID:84C4p533-0974-499A-9EOC-1 DC35A3FOOFF
ill ® 09 E3 01 ® ® TOWN OF BARNSTABLE ETD sMobile °
I U111
I i
4 SYLVAN WAY
_ L�7`� ! -11 PH 1' 1 7 PARSIPPANY,NJ 07054
T-MOBILE SITE NUMBER: 4HY0558A BUSINESS UNIT #: 875052
T-MOBILE SITE NAME: HY558 SPRINT CENTERVILLE SITE ADDRESS: HYANN SOUTH RD CRDWWN
, � N C1047
A
SITE TYPE: MONOPOLE COUNTY: BARNSTABLE
TOWER HEIGHT: 118'-0" JURISDICTION: TOWN OF
T-MOBILE APU DC GENERATOR PROJECT BARNSTABLE
SITE INFORMATION DRAWING INDEX LOCATION MAP
T-MOBILE SITE NUMBER:
CROWN CASTLE USA INC. SHEET# SHEET DESCRIPTION cQr. c,;�' �C m { ' 4HY0558A
.
SITE NAME: ASSOCIATED ALARM SYSTEM God. (j1 fj/ ,d is KIt} re.Gl .
SITE ADDRESS: 1047 FALMOUTH RD -
s T1 TITLE SHEET BU #: 875652
HYANNIS,MA 02601 T-2 GENERAL NOTES ++ ' - /`"` `} .€ z. W" ASSOCIATED ALARM
COUNTY: BARNSTABLE C-1 SITE PLAN !
MAP/PARCEL#: HYAN-000250-00000-000004 C_2 INSTALLATION AND EQUIPMENT DETAILS f `�� � - - m m J I ,c � � , SYSTEM
AREA OF CONSTRUCTION: EXISTING j ,.�„""'. '`•..
C-3 INSTALLATION AND F_QUIPMENT DETAILS
LATITUDE: 41°39'32.18' ea 3 1`L '`^ :Q 1047 FALMOUTH RD
C-4 INSTALLATION DETAILS AND CABLE SPECIFICATIONS „ ^' �°' ` T ?' a°� `w t �� s' Mc� Or
LONGITUDE: 70°19'32.81" +� E b a� S- l b HYANNIS,MA 02601
C-5 PHOTOS AND ONE-LINE DIAGRAM 41
f r`
LAT/LONG TYPE: NAD83 yc ! !yd a e
GROUND ELEVATION: 54 FT. A.
C-6 SIGNAGE REQUIREMENTS P`?D f 3��Q�ifse°�a a o CCU d I ", 28 P h
fp, c A> � ro p N,o, Q X aau, EXISTING 118-0 MONOPOLE
CURRENT ZONING: NOT AVAILABLE G-1 GROUNDING DETAILS cac
JURISDICTION: TOWN OF BARNSTABLE G-2 GROUNDING DETAILS c / v f JJ yyS -s L
J Marsh Rd +<Ya. ti� � IQui1i Rd,
OCCUPANCY CLASSIFICATION: U < ? = 7 a` 8anssta8le
..n?' el• .'�,:""' 4° (,. ..fy�y lnt¢rrnedmta�'v
d C r b v .�"" -
TYPE OF CONSTRUCTION: IIB l
--�i. -,y,� �.e �CVS.:Phamaocy_3 "�.Schoo/ � ,,��^^..
A.D.A.COMPLIANCE HUMAN
IS UNMANNED_D AND NOT FOR y Z ) .m
HUMAN HABITATION - j `,,,�J
PROPERTY OWNER: RELD CORPORATION ALL DRAWINGS CONTAINED HEREIN ARE FORMATTED FOR 11X17. a. C'�y� ~ § �`�~ _
Gow s �� M _ y. 41.65894,=70.32578 a'
1047 FALMOUTH ROAD CONTRACTOR SHALL VERIFY ALL PLANS AND EXISTING DIMENSIONS f.
—] ,..,.,.Q`�S �Fa111tpD!�.Ril-.-�7( asy F �, ;�'•- r .. ISSUED FOR
HYANNIS,MA 02601 AND CONDITIONS ON THE JOB SITE AND SHALL IMMEDIATELY NOTIFY - 'r. - J[ ,f "'-`-` ''*dy �,y ."'^-1 _ {
TOWER OWNER, GLOBAL SIGNAL ACQUISITIONS II LLC THE ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE ,,,..-�^"�:,,.r` -": �4.J. . MAor� '�1 /�f'T-"a ? REV DATE DRwN DascRlrnoN DES./Q.
2000 CORPORATE DRIVE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR SAME. •,."- " � '*y iiilll A,.� ;1 'S,,�'t8amitaltJe High (/ A 04/06/18 IAs PRELMUNARY ZTK
CANONSBURG,PA15317M thoa! - - / o oP/ze/:8 JAs CONsrRucnoN AF
CARRIER/APPLICANT: T- OBILE m4SYLVAN WAY S aIPI:
' b s
PARSIPPANY,N APPROVAL
07054
CROWN CASTLE USA INC. h�cc 1 _ Q S F� Cn s j P"N FIT,
a
APPLICATION ID: 404103 APPROVAL SIGNATURE DATE 4 1 p 'a ?a 3 9._ O �S .Y �.+ a� `b Q ^ ifELECTRIC PROVIDER NATIONAL GRID ``•* 1 r 2 S �D�` .. °� / �^ � Ui�gd+(800)892-2345 .. - :��. g' .. ;._.The Da1Jy Papei. w. ca"'�,_. ,. `�TELCO PROVIDER COMCAST PROPERTY OWNER OR REP. {J ti,- r I( _ _ x ��e 5t tCapr 4Viirds +' 1 InNO SCALEFIA
y0�-..,._..,.,.... - S+s
(888)428-7300 -TURAL GAS PROVIDER: MASSACHUSETTS GAS LAND USE PLANNER(800)233-5325 40SEPH u,
FANDOZZI III `T4
PROJECT TEAM CIVIL
T-MOBILE APPLICABLE CODES/REFERENCE DOCUMENTS
OPERATIONS No.51667
THE PURPOSE OF THIS PROTECT 15 TO ENHANCE BROADBAND ALL WORK SHALL BE PERFORMED AND MATERIALS INSTALLED IN '0
A&E FIRM: 2CROWN CASTLE USA INC.000 CORPORATE DRIVE RF CONNECTIVITY AND CAPACITY TO THE EXISTING ELIGIBLE WIRELESS ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING �0 9FG/STER�O�<(�Q -
CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES.
CANONSBURG,PA 15317 NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK 9/2 N*L .17 PM T
CROWNAE.APPROVAL@CROWNCASTLE.COM NETWORK TOWER SCOPE OF WORK NOT CONFORMING TO THESE CODES:
•NO TOWER WORK CODE TYPE CODE
CROWN CASTLE 12 GILL STREET,SUITE 5800 BACKHAUL GROUND SCOPE OF WORK BUILDING MA STATE BUILDING CODE,9TH EDITION(780
USA INC.DISTRICT WOBURN,MA 01801 •NEW 7.5KW,48VDC NATURAL GENERATOR�' ) MECHANICAL M MA STATE(LISTED UL 2200 A ST2015 IBC W/AMENDMENTS
ATE BUILDING CODE,9TH EDITION(780
CONTACTS: CHRISTINE TROTTA-PROJECT MANAGER CONSTRUCTION MANAGER CDBR)/2015 IMC W/AMENDMENTS
(518)396-8023 ELECTRICAL MA ELECTRICAL CODE/2017 NEC
MICHAEL RULEY-CONSTRUCTION MANAGER W/AMENDMENTS
THE PARTIES ABOVE HEREBY APPROVE AND ACCEPT THESE FIRE MASSACHUSETTS COMPREHENSIVE FIRE SAFETY
(508)789-7023 DOCUMENTS AND AUTHORIZE THE CONTRACTOR TO PROCEED WITH CODE
THE CONSTRUCTION DESCRIBED HEREIN. ALL CONSTRUCTION INSTALLER NOTE:
REBECCA ALESCIO-A&E PROTECT MANAGER DOCUMENTS ARE SUBJECT TO REVIEW BY THE LOCAL BUILDING THIS SITE TO HAVE A NATURAL GAS
REBECCA.ALESCIO GENERATOR INSTALLED.
@i CROWNCASTLE.COM
DEPARTMENT AND ANY CHANGES AND MODIFICATIONS THEY MAY I i
. T IS A VIOLATION OF L.9W FOR ANYPERSON� -
(518)373-3547 IMPOSE. UNOS AT HETYOA ALT ALCR THNIGS DUNOD ER T HE DIREC ON
FLICENP
T-MOBILE CONTACT: SIALIN PATEL SED PROFESSIONALENGINEER,
.
(973)397-4899 NOTE:
DESIGN PACKAGE BASED ON THE APPLICATION CAr.r.NIASSACHUSFM ONE CAr r O
PRIOR TO ACCESSING/ENTERING THE SITE YOU MUST CONTACT 888 34a-7233 SHEET NUMBER: VISION.
ID: SIO . ( ) 0: I
THE CROWN NOC AT(800)788-7011&CROWN CONSTRUCTION CALL s uzoRhlNG Days
MANAGER REVISION:3 BEFORE YOU DIGI 0 O
DocuSign Envelope ID:84C40533-0974-499A-9EOC-1DC35A3FOOFF
SITE WORK GENERAL NOTES: MASONRY NOTES: ELECTRICAL INSTALLATION NOTES GREENFIELD GROUNDING NOTES:
1. THE SUBCONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF 1. HOLLOW CONCRETE MASONRY UNITS SHALL MEET A.S.T.M. SPECIFICATION C90, GRADE 1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT Mobfle
CONSTRUCTION. N. TYPE 1. THE SPECIFIED DESIGN COMPRESSIVE STRENGTH OF CONCRETE MASONRY SPECIFICATIONS, NEC AND ALL APPLICABLE FEDERAL, STATE, AND LOCAL 1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION. IT 0 ®(F'm) SHALL BE 1500 PSI. CODES/ORDINANCES. RADIO, LIGHTNING PROTECTION AND AC POWER GES'S) SHALL BE
2. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES WHERE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER
ENCOUNTERED IN THE WORK, SHALL BE PROTECTED AT ALL TIMES AND WHERE REQUIRED 2. MORTAR SHALL MEET THE PROPERTY SPECIFICATION OF A.S.T.M. C270 TYR "S" 2. CONDUIT ROUTINGS ARE SCHEMATIC. SUBCONTRACTOR SHALL INSTALL CONDUITS SO BONDING CONDUCTORS IN ACCORDANCE WITH THE NEC.FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS DIRECTED BY MORTAR AND SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2000 PSI. - THAT ACCESS TO EQUIPMENT IS NOT BLOCKED AND TRIP HAZARDS ARE ELIMINATED. 4 SYLVAN WAY
CONTRACTOR. EXTREME CAUTION SHOULD BE USED BY THE SUBCONTRACTOR WHEN 2. THE SUBCONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL PARSIPPANY,NJ 07054
EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES, SUBCONTRACTOR SHALL 3. GROUT SHALL MEET A.S.T.M. SPECIFICATION C475 AND HAVE A MINIMUM 28 DAY 3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR GROUND
PROVIDE SAFETY TRAINING FOR THE WORKING CREW. THIS WILL INCLUDE BUT NOT BE COMPRESSIVE STRENGTH OF 2000 PSI. REQUIREMENTS OF THE NEC. HILTI EPDXY ANCHORS ARE REQUIRED BY CROWN CASTLE ELECTRODE SYSTEMS, THE SUBCONTRACTOR SHALL FURNISH AND
LIMITED TO A) FALL PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING - USA INC- INSTALL SUPPLEMENTAL GROUND ELECTRODES AS NEEDED TO ACHIEVE
AND EXCAVATION. 4. CONCRETE MASONRY SHALL BE LAID IN RUNNING (COMMON) BOND. A TEST RESULT OF 5 OHMS OR LESS.
4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS
WORK T M - - "INSTALLATION STANDAR F R V BRACING. TEMPORARY
REQUIRED BY THE NEC.
3. ALL SITE I 0 COMPLY WITH QAS STD 10068STANDARDS 0 5. WALL SHALL RECEIVE TEMPORARY FULL B C G E ORARY BRACING SHALL NOT BE 3. THE SUBCONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING /1^O{ /�.
CONSTRUCTION ACTIVITIES ON CROWN CASTLE USA INC. TOWER SITE"AND LATEST VERSION REMOVED UNTIL GROUT IS FULLY CURED. GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT fV,L,�`► V\•/
OF TIA 1019 "STANDARD FOR INSTALLATION, ALTERATION, AND MAINTENANCE OF ANTENNA 5. CABLES SHALL NOT BE ROUTED THROUGH LADDER-STYLE CABLE TRAY RUNGS. ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO
THE CONDUIT AND PROVIDE TESTING RESULTS. CASTLE
SUPPORTING STRUCTURES AND ANTENNAS." 6. EACH END OF EVERY POWER, POWER PHASE CONDUCTOR (I.E., HOTS), GROUNDING AND
4. ALL SITE WORK SHALL BE AS INDICATED ON THE STAMPED CONSTRUCTION DRAWINGS AND T1 CONDUCTOR AND CABLE SHALL BE LABELED WITH COLOR-CODED INSULATION OR 4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE
PROJECT SPECIFICATIONS. ELECTRICAL TAPE (3M BRAND, 1/2" PLASTIC ELECTRICAL TAPE WITH UV PROTECTION, ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY
OR EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA. BONDING ACROSS THE DISCONTINUITY WITH #6 AWG COPPER WIRE UL
5 REMOVED NECESSARY,
FROMRHE SITE ATND DISPOSEDSOF STICKS,
EGALLYSTONES AND OTHER REFUSE SHALL BEraERAL NOTES: 7. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH PLASTIC TAPE PER APPROVED GROUNDING TYPE CONDUIT CLAMPS. -
COLOR SCHEDULE. ALL EQUIPMENT SHALL BE LABELED WITH THEIR VOLTAGE RATING, 5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED
6. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH PHASE CONFIGURATION, WIRE CONFIGURATION, POWER OR AMPACITY RATING AND EQUIPMENT GROUND CONDUCTOR. STRANDED COPPER CONDUCTORS
INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED AND/OR CAPPED, R THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY: BRANCH CIRCUIT ID NUMBERS (I.E. PANEL BOARD AND CIRCUIT ID'S). WITH GREEN INSULATION, SIZED IN ACCORDANCE WITH THE NEC, SHALLPLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE WITH THE ONTRACTOR- ---------- BE FURNISHED AND INSTALLED WITH THE POWER CIRCUITS TO BTS -
EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL OF CONTRACTOR, OWNER AND/OR SUBCONTRACTOR- GENERAL CONTRACTOR (CONSTRUCTION) 8. PANEL BOARDS (ID NUMBERS) AND INTERNAL CIRCUIT BREAKERS (CIRCUIT ID NUMBERS) EQUIPMENT.
LOCAL UTILITIES. CARRIER- T-MOBILE SHALL.BE CLEARLY LABELED WITH PLASTIC LABELS. -
TOWER OWNER- CROWN CASTLE USA INC. 6. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER -
7. THE SUBCONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL OEM- ORIGINAL EQUIPMENT MANUFACTURER 9. ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL EQUIPMENT _c
SPECIFICATION FOR SITE SIGNAGE. SHARP EDGES. GROUND WIRES, 6 AWG STRANDED COPPER OR LARGER FOR INDOOR
2. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING SUBCONTRACTOR SHALL VISIT THE CELL BTS; #2 AWG SOLID TINNED COPPER FOR OUTDOOR BTS.
S. THE SITE SHALL BE.GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE-BTS SITE TO FAMILIARIZE WITH THE EXISTING CONDITIONS AND TO CONFIRM THAT THE WORK CAN 10.POWER, CONTROL AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE
EQUIPMENT AND TOWER AREAS. BE ACCOMPLISHED AS SHOWN ON THE CONSTRUCTION DRAWINGS. ANY DISCREPANCY FOUND SINGLE CONDUCTOR (#14 AWG OR LARGER), 600 V. OIL RESISTANT THHN OR THWN-2, 7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR T-MOBILE SITE NUMBER:
SHALL BE BROUGHT TO THE ATTENTION OF CONTRACTOR AND CROWN CASTLE USA INC. CLASS B STRANDED COPPER CABLE RATED FOR 90- C (WET & DRY) OPERATION LISTED STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE OF THE ,fT Tyr 1 1JMB
9. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN OR LABELED FOR THE LOCATION AND RACEWAY SYSTEM USED UNLESS OTHERWISE GROUND BUS ARE PERMITTED. yri y OSJr HA
MATERIALS, SNOW OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT. 3. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL SPECIFIED.
APPLICABLE CODES, REGULATIONS AND ORDINANCES. SUBCONTRACTOR SHALL ISSUE ALL 8. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND
10. THE SUB GRADE SHALL BE.COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS 11.SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE BARS AND THE GROUND RING SHALL BE #2 AWG SOLID TINNED
PRIOR TO FINISHED SURFACE APPLICATION. AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE OF THE CONDUCTOR (#5 AWG OR LARGER), 60OV, OIL RESISTANT THHN OR THWN-2 GREEN COPPER UNLESS OTHERWISE INDICATED. µy per/
WORK. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND BU #:875052
11.THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY UTILITY COMPANY,SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND INSULATION LILTED B STRANDED COPPER CABLE RATED FOR 90' C (WET AND DRY)
OPERATION LISTED OR LABELED FOR THE LOCATION AND RACEWAY SYSTEM USED 9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL ASSOCIATED ALARM
THE TOWER, EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND APPLICABLE REGULATIONS.
UNLESS OTHERWISE SPECIFIED. NOT BE USED FOR GROUNDING CONNECTIONS.
STABILIZED TO PREVENT EROSION AS SPECIFIED ON THE PROJECT SPECIFICATIONS.
12.POWER AND CONTROL WIRING, NOT IN TUBING OR CONDUIT, SHALL BE 10.USE OF 90' BENDS IN THE PROTECTION GROUNDING CONDUCTORS SYSTEM
12.SUBCONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. 4. DRAWINGS PROVIDED HERE ARE NOT TO SCALE AND ARE INTENDED TO SHOW OUTLINE MULTI-CONDUCTOR, TYPE TC CABLE (#14 AWG OR LARGER). 600 V, OIL RESISTANT SHALL BE AVOIDED WHEN 45' BENDS CAN BE ADEQUATELY SUPPORTED.
EROSION CONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN ONLY.CONFORMANCE WITH THE LOCAL GUIDELINES FOR EROSION AND SEDIMENT CONTROLTHHN OR THWN-2, CLASS B STRANDED COPPER CABLE RATED FOR 90' C (WET AND
5. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, DRY) OPERATION WITH OUTER JACKET LISTED OR LABELED FOR THE LOCATION USED 11.EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING 1047 F n r MOUTH M
APPURTENANCES AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED UNLESS OTHERWISE SPECIFIED.' CONNECTIONS BELOW GRADE. 7 Y 1T��n1���.
13.NOTICE TO PROCEED- NO WORK TO COMMENCE PRIOR TO COMPANY'S WRITTEN NOTICE TO ON THE DRAWINGS. r11 A1V 1V js�MA OZ6O1
PROCEED AND THE ISSUANCE OF A PURCHASE ORDER. 13.ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP-STYLE, COMPRESSION 12.ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR)
SHALL BE FORMED USING HIGH PRESS CRIMPS.
14.ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITED TO, ERECTION 6. "KITTING LIST" SUPPLIED WITH THE BID PACKAGE IDENTIFIES ITEMS THAT WILL BE SUPPLIED WIRE LUGS AND WIRE NUTS BY THOMAS AND BETTS (OR EQUAL). LUGS AND WIRE
PLANS, RIGGING PLANS, CLIMBING PLANS, AND RESCUE PLANS SHALL BETHE BY CONTRACTOR. ITEMS NOT INCLUDED IN THE BILL OF MATERIALS AND KITTING LIST SHALL NUTS SHALL BE RATED FOR OPERATION AT NO LESS THAN 75- C (90- C IF 13.COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXISTING 11 oO1-On MONOPOLE
RESPONSIBILITY OF THE GENERAL CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THE BE SUPPLIED BY THE SUBCONTRACTOR. AVAILABLE). EXOTHERMIC WELD CONNECTIONS.
WORK CONTAINED HEREIN AND SHALL MEET ANSI/ASSE (LATEST EDITION); FEDERAL,INDUSTRY
STATE, AND LOCAL REGULATIONS; AND ANY APPLICABLE INDUSTRY CONSENSUS STANDARDS 7 THE SUBCONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH 14.RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN 14.ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED
RELATED TO THE CONSTRUCTION ACTIVITIES BEING PERFORMED. ALL RIGGING PLANS SHALL MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE. ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND NEC. OR BOLTED TO THE BRIDGE AND THE TOWER GROUND BAR.
ADHERE TO ANSI/ASSE A 0.48 (LATEST EDITION)AND CROWN STANDARD CED-STD-10253 B. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS,
INCLUDING THE REQUIRED INVOLVEMENT OF A QUALIFIED ENGINEER FOR CLASS IV 15.ELECTRICAL METALLIC TUBING (EMT) OR RIGID NONMETALLIC CONDUIT (I.E. RIGID PVC 15.APPROVED ANTIOXIDANT COATINGS (I.E. CONDUCTIVE GEL OR PASTE)
T
CONSTRUCTION TO CERTIFY THE SUPPORTING STRUCTURE(S) IN ACCORDANCE WITH THE HE SUBCONTRACTOR SHALL PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY SCHEDULE 40 OR RIGID PVC SCHEDULE 80 FOR LOCATIONS SUBJECT 70 PHYSICAL SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND
ANSI/TIA-322 (LATEST EDITION). THE CONTRACTOR AND CROWN CASTLE USA INC. PRIOR TO PROCEEDING WITH ANY SUCH DAMAGE) SHALL BE USED FOR EXPOSED INDOOR LOCATIONS. CONNECTIONS.
CHANGE OF INSTALLATION.
16.ELECTRICAL METALLIC TUBING (EMT), ELECTRICAL NONMETALLIC TUBING (ENT) OR RIGID 16.ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A
9. SUBCONTRACTOR SHALL DETERMINE ACTUAL ROUTING OF CONDUIT, POWER AND T1 CABLES, NONMETALLIC CONDUIT (RIGID PVC, SCHEDULE 40) SHALL BE USED FOR CONCEALED CORROSION RESISTANT MATERIAL.
GROUNDING CABLES AS SHOWN ON THE POWER, GROUNDING AND TELCO PLAN DRAWINGS. INDOOR LOCATIONS.
17.MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES,
STRUCTURAL STEEL NOTES: 0.THE SUBCONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, 7.SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN ISSUED FOR:
LANDSCAPING AND STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT ELBOWS/90s AND ALL APPROVED ABOVE GRADE PVC CONDUIT. ACCORDANCE WITH THE NEC. REV DATE DR%VN DESCRIPTION DES./Q
SUBCONTRACTOR'S EXPENSE TO THE SATISFACTION OF OWNER.
1. ALL STEEL WORK SHALL BE PAINTED IN ACCORDANCE WITH THE PROJECT 11.SUBCONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH 18.LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-TITE FLEX) SHALL BE USED 18.BOND ALL METALLIC OBJECTS WITHIN 6 FT. OF MAIN GROUND WIRES A 04/06/18 JAS PREI.ID•IINARY ZTK
SPECIFICATIONS AND IN ACCORDANCE WITH ASTM A36 UNLESS OTHERWISE NOTED. AS COAXIAL CABLES ANDOTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS INDOORS AND OUTDOORS, WHERE VIBRATION OCCURS OR FLEXIBILITY IS NEEDED. WITH 1-#2 AWG TIN-PLATED COPPER GROUND CONDUCTOR. 0 09/28/18 JAS CONSTRUCTION AF
REMOVED SHALL BE RETURNED TO THE OWNER'S DESIGNATED LOCATION. 19.GROUND CONDUCTORS USED IN THE FACILITY GROUND AND LIGHTNING
2. BOLTED CONNECTIONS SHALL BE ASTM A325 BEARING TYPE (3/4"m) CONNECTIONS AND 19.CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION-TYPE AND PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH METALLIC
SHALL HAVE MINIMUM OF TWO BOLTS UNLESS NOTED OTHERWISE. 12.SUBCONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD APPROVED FOR THE LOCATION USED. SET SCREW FITTINGS ARE NOT ACCEPTABLE. OR
THAT FORM A RING AROUND THE CONDUCTOR, SUCH AS
BE REMOVED FROM SITE ON A DAILY BASIS. METALLIC CONDUITS. METAL SUPPORT CLIPS OR SLEEVES THROUGH
3. NON-STRUCTURAL CONNECTIONS FOR STEEL GRATING MAY USE 5/8"0 ASTM A307 20.CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN WALLS OR FLOORS, WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT
BOLTS UNLESS NOTED OTHERWISE. ACCORDANCE WITH NEMA, ILL, ANSI/IEEE AND NEC. TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS, NON-METALLIC
4. INSTALLATION OF CONCRETE EXPANSION/WEDGE ANCHOR, SHALL BE PER 21.WIREWAYS SHALL BE EPDXY-COATED (GRAY) AND INCLUDE A HINGED COVER, DESIGNED MATERIAL SUCH AS PVC PLASTIC CONDUIT SHALL BE USED. WHERE
MANUFACTURER'S RECOMMENDED PROCEDURE. THE ANCHOR BOLT, DOWEL OR ROD TO SWING OPEN DOWNWARDS; SHALL BE PANDUIT TYPE E (OR EQUAL); AND RATED USE OF METAL CONDUIT IS UNAVOIDABLE (E.G., NONMETALLIC CONDUIT
SHALL CONFORM TO MANUFACTURER'S RECOMMENDATION FOR EMBEDMENT DEPTH OR AS NEMA 1 OR BETTER). PROHIBITED BY LOCAL CODE) THE GROUND CONDUCTOR SHALL BE
( BONDED TO EACH END OF THE METAL CONDUIT. - DOCu
SHOWN ON THE DRAWINGS. NO REBAR SHALL BE CUT WITHOUT PRIOR CONTRACTOR � YOF M S
APPROVAL WHEN DRILLING HOLES IN CONCRETE. SPECIAL INSPECTIONS, REQUIRED BY ABBREVIATIONS AND .SYMBOLS: 22.CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON-PERFORATED 20.ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE
GOVERNING CODES, SHALL BE PERFORMED IN ORDER TO MAINTAIN MANUFACTURER'S STRAPS AND HANGERS. EXPLOSIVE DEVICES FOR ATTACHING HANGERS TO STRUCTURE MUST BE #2 TINNED SOLID IN 3/4" LIQUID TIGHT CONDUIT FROM 24'
MAXIMUM ALLOWABLE LOADS. WILL NOT BE PERMITTED. CLOSELY FOLLOW THE LINES OF THE STRUCTURE, MAINTAIN
ABBREVIATIONS: SYMBOLS: CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. BELOW GRADE TO WITHIN 3" IQ D TIGHT
CAD-WELD TERMINATION POINT. N
CHANGES IN DIRECTION TO ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT THE EXPOSED END OF THE LIQUID TIGHT CONDUIT MUST BE SEALED �6 6dOSEPH
AGL ABOVE GRADE LEVEL OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WITH SILICONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL FANDOZZIiII
BTS BASE TRANSCEIVER.STATION S G SOLID GROUND BUS BAR PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT AS WELL). 0 -1
MEN. MINIMUM S N SOLID NEUTRAL BUS BAR SHALL BE FISHED TO CLEAR OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE V- CIVIL y
�- TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT CONCRETE, PLASTER OR
REF REFERENCE - SUPPLEMENTAL GROUND CONDUCTOR DIRT FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY - A No.51667
CONCRETE AND REINFORCING STEEL NOTES: RF RADIO FREQUENCY �- GALVANIZED MALLEABLE IRON BUSHIN ON INSIDE AND GALVANIZED MALLEABLE IRON fly. �O 11
�Q
NG
T.B.D. TO BE DETERMINED D=° 2-POLE THERMAL-MAGNETIC CIRCUIT LOCKNUT ON OUTSIDE AND INSIDE. �� GiS7r�P
T.B.R. TO BE RESOLVED BREAKER NEC INSULATOR COLOR CODE r� \
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACT 301, ACI 318, ACT TYP TYPICAL 23.EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE 9/2 NI+1L .17 PM IT
336, ASTM A184, ASTM A185 AND THE DESIGN AND CONSTRUCTION SPECIFICATION REQ REQUIRED ° SINGLE-POLE THERMAL-MAGNETIC GALVANIZED OR EPDXY-COATED SHEET STEEL; SHALL MEET OR EXCEED UL 50 AND
FOR CAST-IN-PLACE CONCRETE. EGR EQUIPMENT GROUND RING CIRCUIT BREAKER RATED NEMA 1 (OR BETTER) INDOORS OR NEMA 3R (OR BETTER) OUTDOORS. DESCRIPTION PHASE/CODE LETTER WIRE COLOR -
AWG AMERICAN WIRE GAUGE
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT MGB MASTER GROUND BAR e CHEMICAL GROUND ROD 24.METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY-COATED LEG 1 BLACK
28 DAYS, UNLESS NOTED OTHERWISE. SLAB FOUNDATION DESIGN ASSUMING EG EQUIPMENT GROUND OR NON-CORRODING; SHALL MEET OR EXCEED UL 514A AND NEMA OS 1; AND RATED 240/120 10 -
ALLOWABLE SOIL BEARING PRESSURE OF 2000 PSF. BCW BARE COPPER WIRE ® TEST WELL NEMA 1 (OR BETTER) INDOORS OR WEATHER PROTECTED (WP OR BETTER) OUTDOORS. LEG 2 RED
SIAD SMART INTEGRATED ACCESS DEVICE AC NEUTRAL N WHITE
3. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, DEFORMED GEN GENERATOR E7' DISCONNECT SWITCH 25.NONMETALLIC.RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA GROUND (EGC) -G- GREEN
UNLESS NOTED OTHERWISE. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185 IGR INTERIOR GROUND RING (HALO) OS 2; AND RATED NEMA 1 (OR BETTER) INDOORS OR WEATHER PROTECTED (WP OR
WELDED STEEL WIRE FABRIC UNLESS NOTED OTHERWISE. SPLICES SHALL BE CLASS RBS RADIO BASE STATION a METER BETTER) OUTDOORS. VDC POS + RED-POLARITY MAR
"8"AND ALL HOOKS SHALL BE STANDARD, UNO. AT TERMINATION
4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING EXOTHERMIC WELD (CADWELD) 26.THE SUBCONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE - 'BLACK-POLARITY
UNLESS OTHERWISE NOTED) CONTRACTOR BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. VDC NEG MARK AT
STEEL UNLESS SHOWN OTHERWISE ON DRAWINGS: ( NO ) TERMINATION
CONCRETE CAST AGAINST EARTH..................3 IN. MECHANICAL CONNECTION AND
THE SUBCONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS. CABLES
CONCRETE EXPOSED TO EARTH OR WEATHER: AND DISTRIBUTION PANELS IN ACCORDANCE WITH THE APPLICABLE CODES AND PHASE A BLACK
STANDARDS TO SAFEGUARD LIFE AND PROPERTY. -
#6 AND LARGER..................................2 IN. GROUNDING WIRE 24OV OR 208V, 30 PHASE B RED(ORG. IF HI LEG) IT IS A VIOLATION OF LAW FOR ANY PERSON,
#5 AND SMALLER & WWF...................1 1/2 IN. - 28,INSTALL PLASTIC LABEL ON THE METER CENTER TO SHOW "T-MOBILE". PHASE C BLUE UNLESS THEY ARE ACTING UNDER THE DIRECTION
CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR NOT CAST AGAINST THE - OF LICENSED PROFESSIONAL ENGINEER,
GROUND: 29.ALL CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD PHASE A BROWN TO ALTER THIS DOCiJbffiNT.
SLAB AND WALLS................................3/4 IN. INSTALLED. 480V, 30 PHASE B ORANGE OR PURPLE
PHASE c YELLow
BEAMS AND COLUMNS........................1 1/2 IN. SHEET NUMBER: VISIO
5. A CHAMFER 3/4" SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE,
UNLESS NOTED OTHERWISE. IN ACCORDANCE WITH ACT 301 SECTION 4.2.4. SEE NEC 2T0.5(C)(1) AND (2) 0
T-2
DocuSign Envelope ID:84C40533-0974-499A-9EOC-1DC35A3FOOFF
FlaaMobile o a a
4 SYLVAN WAY
PARSIPPANY,NJ 07054
16'-10"3 1'-1"f 12'-0"t 3'-5"t
(GATE)
FCROWN
CASTLE
(2) AC UNITS I
x x— X /
I/
T-MOBILE SITE NUMBER:
(E) FENCE / FOLLOW EXISTING GAS LINE 4HY0558A
(E) GENERATOR (E) CONCRETE PAD / ROUTING TO GAS MANIFOLD
TED TO
X X X X X MAITCHNE T BUIILDING O BE NAND TOF— X—
/ BE LABELED) BU#:875052
ASSOCIATED ALARM
x (E) POWER CONDUITS SYSTEM
/
1047 FALMOUTH RD
/ HYANNIS,MA 02601
x / (E) BUILDING
7777� / EXISTING 118'-0"MONOPOLE
+ + + + + + + + + + + + + +
(E) 118'-0" MONOPOLE + + + + + + + + + + + + + + + /
+ + + + + + + + + + + + + + + /
x + +
+ /
+ + + + + + + + + + + (E) ICE BRIDGE
+ + + + + + + + + + + + (TMP) / ISSUED FOR:
x + + + + + + + + + + + REV DATE DRWN DESCRIPTION DES./Q
1 1 A 04/06/18 J.AS PRELMENAKY ZTK
/ 0 09 28 16 JAS CONSTRUCTION AF
� +
x (E) PLATFORM + + T—MOBILE
CABINET /
+ + GENERATOR FUEL INLET +
+ GENERATOR POWER & I I
ALARM CABLE ACCESS
DxU
+ + le!�YOFM
x + + NEW 2" CONDUIT _. NEW 1-1/2" NATURAL GAS .9C
WITH DC CONDUCTORS LINE (75'—O"t LONG)
(E) T—MOBILE 7'-0"i + + 1 I yG
ICE BRIDGE s 'bfk1$kdQSEPH
N
+ + T-M BILE / o FANDOZZI III
+ + 6131 CABINET 1 X X / 0 CIVIL y
x 1I 1 I NA URAL GAS ERATOR�C ,0 9 No.51667 O Q
\` ON CONCRETE PAD
I \ I GENERATOR EXHAUST 9/2 ®N*L \� .17 PM I IT
1 \\ 1 /
1 \\ 1 /
x \
\
LX X X X X XIi \
GENERATOR CLEARANCE
REQUIRED PER NFPA _
(E) T—MOBILE4'-10x6'—O" REF: 5/C-3
CONCRETE PAD IN
7'-0"x16'-7" LEASE AREA
23'-6"} IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
�\ TO ALTER THIS DOCUMENT.
/ 9 \SITE PLAN SHEET NUMBER: VISIO
SCALE: 1/2'=1'-0"(FULL SIZE)
C- 1 0
DocuSign Envelopq ID:84C40533-0974-499A-9EOC-1 DC35A3FOOFF
f
- - T Mobil eo . a
i 4 SYLVAN WAY
PARSIPPANY,N]07054
.1 cCROWN
CASTLE
r
1.
�g 1
T-MOBILE SITE NUMBER:
4HY0558A
}
ASSOCIATED ALARM
SSt. SYSTEM
1047 FALMOUTH RD
HYANNIS,MA 02601
EXISTING 118'-0"MONOPOLE
NOT USED GENERATOR LOCATION PHOTO
CLE OT E E A A ISSUED FOR:
REV DATE DRWN DESCRIPTION DES./Q
A 04/06/18 JAS PRELIMINARY ZTK
0 09/28/18 JAS CONSTRUCTION AF
0•
Docu roF 1y
MINIMUM 18" CLEARANCE TO — �' 4SS9
42" 7" POWER CABLE OPENING FOR 2" CONDUIT — — — — ) —
COMPLY WITH NFPA 37 ARTICLE a 6 1 �dUSEPHcyG
2 ANCHOR BOLT (TYP 4
ALARM CABLE OPENING FOR 1" CONDUIT [TI
LPG OR NG FUEL ENTRY 3/4" NPT o FANDOZZI III
34' CIVIL 03
No.51667
i i AAp
9 O Q
® ®®® 9/2 ��N*L .17 PM T_
®� ®®
®ga ®®®
®® ®®® ®� ®Egg— EXHAUST _ R2
�� ®� S
��®®®®® ®®v®mm ®®®®®®
®® ®mm®�® ®®®®®® ®®®®®
®®®®®® EXHAUST SIDE MIN 5'-0"
®® ®®o® ®®®®®® ®®®®® CLEARANCE FROM ANY 42"
®®®®®®® ®®®®®® ®®®®®® ®®®®® - STRUCTURES. SHRUBS. TREES.
OR ANY KIND OF VEGETATION
TO COMPLY WITH NFPA 37
7.5KW GENERATOR FUEL REQUIREMENTS: 56.4 CF/H (LP VAPOR) ARTICLE 4 MINIMUM 18" CLEARANCE -
41" 25" WEIGHT 635 LEIS MAX (WITH BATTERY—PYL12V100FS x 4PCS) TO COMPLY WIIH NFPA
3 ARTICLE 4
IT IS A VIOLATION OF LAW FOR ANY PERSON,OPTIONAL STANDBY SYSTEM AGENCY LISTINGS: ILL 2200 — — — — — — — — UNLESS TREY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
DOOR OPENING
MIN 22-1/2" CLEARANCE FOR TOALTER THIS DOCUMENT.
7.5kW, 48VDC GENERATOR (DELTA POWERGEN 7500) SHEET NUMBER: vISIo
JCL E E
DocuSign Envelopq ID:84C40533-0974499A-9EOC-1DC35A3FOOFF
} 1 a aMobile a a a
t >• Tf
4 SYLVAN WAY
r •�.. ` r � ry d PARSIPPANY,NJ 07054
cm
CCROWN
CASTLE
1/2"0 HILTI KWIK BOLT TZ
STAINLESS STEEL ANCHOR::: / ANCHOR LOCATION (TYP) •P '
(ICC REPORT ESR-1917) / ,•; �w
GENERATOR •. - ` r
w
�'i ( 1 °'/
��e T-MOBILE SITE NUMBER:
Z o iI -10.. i j4 wi 4HY0558A
-k. k I ;�`r BU#: 875052
° a r , rt €+ ASSOCIATED ALARM
CONCRETE SLAB � ,pr { i a "k«_ SYSTEM
ISOMETRIC VIEW
1047 FALMOUTH RD
a 4 HYANNIS,MA 02601
_ 4 11 MONOPOLE
�t�
EXISTING 118-0 ANCHORAGE DETAIL (,T� E: NOT ANCHORING SCHEMATIC
SCALE: NOT TO SCALE SCAL TO SCALE 48VDC GENERATOR 7.5KW
�SCALE: NOT TO SCALE
ISSUED FOR:
\\ REV DATE DRW/N DESCRIPTION DES./Q
A 04/01/18 JAS PRELIhIINARY ZTK
0 09/28/18 JAS CONSTRUCTION AF
EXHAUST SIDE MIN 5' CLEARANCE
FROM ANY STRUCTURES. SHRUBS,
MIN 18"CLEARANCE TO COMPLY TREES, OR ANY KIND OF
VEGETATION TO COMPLY WITH NFPA
WITH NFPA 37 ARTICLE 4 / 37 ARTICLE 4
I
Day y10F AyA
S
dQS
3/4" NPT FUEL ENTRY 6'
FLEXIBLE FROM APU 70 3/4" r�
JSHUTOFF VALVE � 6 EPH N
POWER CABLE OPENING FOR CONDUIT- / - 0 FANDOZZI III
INSTALL 2" UOUIDTIGHT CONDUIT q / ' - - V CIVIL - cn I
W/ DC CABLES TO SSC CABINET / NO.51667 -
\ $� SHUTOFF VALVE - A9O 9FGISTEP�O Q
SIGNAL CABLE OPENING FOR 1" - - pp�� ` g��`v
CONDUIT INSTALL 1" UOUIDTIGHT // NATURAL GAS LINE SIZE 1-1/2" - 9/2 /aNryll I •17 PM T -
CONDUIT W/ CATSE ALARM CABLE SCH 40 GALV. PIPE
/
MIN 22-1/2" CLEARANCE FOR / `—(E) GROUND RING - -
DOOR OPENING.
MIN 18"CLEARANCE TO COMPLY
WITH NFPA 37 ARTICLE 4 -
IT IS.q\40LATION OF LAW FOR ANY PERSO
MECHANICAL GROUND CONNECTION EXOTHERMIC GROUND CONNECTION N,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
AT GENERATOR TO EXISTING GROUND RING OFALICENSEDPROFESSIONALENGINEER,
NOT USED UTILITY ENTRY DETAIL TO ALTER THISDocun¢NT.
q 5 SHEET NUMBER VISIO
SCALE: NOT TO SCALE SCALE: NOT TO SCALE
C-3
0
DocuSign Envelope ID:84C4D533-0974-499A-9EOC-1DC35A3FOOFF
TO a aMobile o ■
4SYLVAN WAY
PARSIPPANY,-NJ 07054
FUEL LEAKAGE SENSOR
WEB
ACCESS WATER SENSOR
ALARM DRY PAD SHEAR SENSOR CROWN
CONTACT CONTROLLER
DOOR SENSOR
CASTLE
10A
CB
OIL TANK
OIL
�\ PUMP
�\ 63A CB LOW PRESSURE
SENSOR
t0A 48V
CB BATTERY BATTERY
= T SOLENOID
'4 T-MOBILE SITE NUMBER:To
TELECOM --�� GEN ENGINE 4HY0558A
SYSTEM 200A
MCB
DC LOAD BIDIRECTIONAL FUEL
SPD SOLENOID DC/DC CONVERTER SOLENOID BU#:875052
ASSOCIATED ALARM
NATURAL GAS METER ® - SYSTEM
10"-14"WATER COLUMM
(144,000 BTU/HR)
GAS .
METER 1047 FALMOUTH RD
HYANNIS,MA 02601
DELTA POWERGEN 7500 DC GENSET BLOCK DIAGRAM 2 NOT USED EXISTING 1181-0"MONOPOLE
SCALE: NOT TO SCALE SCALE: NOT TO SCALE
ISSUED FOR:
REV DATE DRWN DESCRIPTION DES./Q
A 04/06/18 JAS PRELIbDNARY ZTK
0 09/28/18 J.9S CONSTRUCTION AF
AC NORMAL: Doeu YOFMAs
UNDER NORMAL CONDITIONS WITH AC POWER TO THE TELECOM CABINET, TELECOM s9Qy
CABINET RECTIFIERS PROVIDE POWER TO LOAD EQUIPMENT AT FLOAT VOLTAGE ABOVE �8 $k
53V, AND THE GENSET IS NOT RUNNING. 8 d.QSEPHGN
AC FAIL: FANOOZZIIII
CIVIL 03
WHEN AC FAILS, TELECOM CABINET BATTERIES PROVIDE POWER TO LOAD EQUIPMENT, A No.51667
D T GENSET
BEGIN
OSET S AND PROVIDES POWER TO LOAD AND POWER TO RECHARGE
DISCHARGE.
STAR H TELECOM
PIISA BELOW
9�9�G/ST�48V
THE TELECOM CABINET BATTERIES TO 52V. GENSET OUTPUT IS ACTIVELY LIMITED TO 9/2 ®NIL .17 PM IT
PREVENT BATTERY RECHARGE OVERCURRENT.
AC RECOVERY:
WHEN AC RECOVERS, TELECOM CABINET RECTIFIERS RESUME PROVIDING POWER TO
LOAD EQUIPMENT AND RECHARGE THE TELECOM CABINET BATTERIES A FLOAT VOLTAGE
ABOVE 53V AND THE GENSET GOES TO NO OUTPUT. WHEN VOLTAGE GOES ABOVE 53V
THE GENSET COOLS DOWN AND SHUTS DOWN.
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OFA LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
K-z--�DELTA POWERGEN 7500 DC GENSET OPERATING MODES ---,,NOT USED SHEET NUMBER: : vIsio
�SCALE: NOT TO SCALE Q�SCALE: NOT TO SCALE
C-4 0
DocuSign Envelope.ID:84C40533-0974499A-9EOC-1 DC35A3FOOFF
T �TVlobile Y 0
4SYLVAN WAY
PARSIPPANY,NJ 07054
CCROWN
CASTLE
T-MOBILE SITE NUMBER:
4HY0558A
FASTEN GENERATOR WITH (4) 1/2"0 HILTI KWIK .�µ BOLT TZ STAINLESS STEEL ANCHORS (ONE EACH BU#: 875052
CORNER)
ASSOCIATED ALARM
ADD 1" SCHEDULE 80 CONDUIT WITH CAT5e ALARM CABLE SYSTEM
MAXIMUM OF 6' CORRUGATED
STAINLESS STEEL TUBING 2" SCHEDULE 80 (BURIED) OR LIQUIDTIGHT (ABOVE GROUND) CONDUIT WITH
TO CONNECT TO APU . (2) 2/0 DC CONDUCTORS WITH #6 GROUND. ALL CONDUCTORS TO BE THHW, T T 7 r i 7��77-��
NATURAL GAS LINE SIZE 1-1/2" (INSTALL W/.DRIP LOOP) THWN. THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 COPPER 1i_0747 FALMOUTH M
SCH 40 GALV. PIPE - CONDUCTORS (90'C RATED FOR WET LOCATIONS). POLARITY FOR DC y 1YANNIS,1VfA 02601
(75'-0"i LONG) CONDUCTORS TO BE MARKED RED/BLACK AT TERMINATIONS.
NATURAL GAS METER SHUTOFF VALVE
o-1 WATER COLUMM
(144,000 B7U/HR) EXISTING 118'-0"MONOPOLE
(1
(E) T—MOBILE SSC
r�
MECHANICAL GROUND CONNECTION
ISSUED FOR:
REV DATE DRWN D CLINJI IONARY DETK
TERMINATION AT CABINET MADE WITH THE A 04/0!>/18 J.95 PRELIIvONARY ZTK
INSTALLER NOTE: SB 175 ANDERSON POWER CONNECTOR
RATED FOR 105'C 0 09/28/18 J.4S CONSTRUCTION AF
METER INSTALL TO FOLLOW NATURAL GAS - (E) GROUND RING TERMINATION AT GENERATOR MADE WITH
UTILITY INSTALL STANDERS AND (E) GROUND RING BURNDY 2—HOLE LUGS RATED FOR 90'C
GUIDELINES.
NEW T—MOBILE 7.5kW, 48VDC GENERATOR WITH 2O0A,
EXOTHERMIC GROUND CONNECTION 2—POLE BREAKER ON (E) CONCRETE PAD. GENERATOR
TO GROUND RING FUEL CONSUMPTION IS 56.4 CF/H AT FULL LOAD.
Dora 'F Mqs
P
�s 6 $b4SEPH yGN
o FANOOZZIIII
U CIVIL N
9 No.51667 o Q
A�O,r �Q/ TEP�
9/2 ®NFL .17 PM I T
IT IS A VIOLATION OffiCUME�NT �
ON,
UNLESS THEY ARE ACTICTION
OF A LICENSED PROER,
TO ALTER T
ONE LINE DIAGRAM SHEET NUMBER: VIsIo
�JSCALE: NOT TO SCALE C-5
O
DocuSign Envelope ID:84C40533-0974-499A-9EOC-1 DC35A3FOOFF
T o aMobile e o
4 SYLVAN WAY
PARSIPPANY,NJ 07054
SIGNAGE REQUIREMENTS: LABEL REQUIREMENTS ON NATURAL GAS PIPE: CROWN
1. STORAGE CONTAINER MUST HAVE A DATAPLATE. (PROVIDED BY TANK MANUFACTURER ALL LABELS SHOULD BE PLACED ON PIPES. CASTLE
DURING TANK FABRICATION) ADJACENT TO ALL VALVES AND FLANGES
NFPA 58:5.2.8.3 ADJACENT TO ALL CHANGES IN PIPE DIRECTION
ON BOTH SIDES OF WALL, FLOOR OR CEILING PENETRATIONS NATURAL GAS
2. STORAGE CONTAINER MUST BE MARKED DESCRIBING THE CONTENTS (PROPANE OR EVERY 50 FEET ON STRAIGHT RUNS OF PIPE (OR EVERY,25 FEET IN
LIQUEFIED PRETROLEUM GAS) AND A STATEMENT OF THE HAZARD (FLAMMABLE). CONGESTED AREAS)
NFPA 1:60.1.13 & IFC:2703.5
PIPE OUTER DIAMETER
3. STORAGE CONTAINER MUST BE MARKED WITH HAZMAT ID. (CERTAIN ENTRANCES TO MIN. LABEL LENGTH
STORAGE OR DISPENSING AREAS MAY ALSO REQUIRE HAZMAT ID MARKING) MIN. LETTER HEIGHT
NFPA 1:60.1.13, NFPA 704:1.3 & IFC:2703.5 0.75 - 1.25 INCHES
8 INCHES
4. NO SMOKING SIGNS MUST BE POSTED IN AREAS OR SITES WHERE FLAMMABLE GASES 0.5 INCH T-MOBILE SITE NUMBER:
ARE USED OR STORED. NO SMOKING OR OPEN FLAMES WITHIN 25 FT. OF POINT OF
TRANSFER.
4HY0558A
NFPA 1:60.1.13, IFC:3807.2, IFC:2703.7, & NFPA 58:7.2.3.2(6)
5. THE MAXIMUM PERMITTED PERCENTAGE (%) OF TANK CAPACITY MUST BE MARKED BU#: 875052
EITHER ON THE DATAPLATE OR ADJACENT TO THE FIXED MAXIMUM LIQUID LEVEL GAUGE. ASSOCIATED ALARM
NFPA 58:5.7.5.4
SYSTEM
1047 FALMOUTH RD
HYANNIS,MA 02601
\ \ EXISTING 118'-0"MONOPOLE
1 SIGNAGE REQUIREMENTS T \NATURAL GAS LINE LABEL PIPE LABEL
SCALE: NOT TO SCALE L SCALE: NOT TO SCALE �SCALE: NOT TO SCALE
ISSUED FOR:
REV I DATE DRXVN DESCRIPTION DES./Q
A 04/06 18 JAS PRELEYENARY ZTK
0 09/28/18 JAS CONSTRUCTION AF
p Q o«� M p e � YoF ASs9
6 ffieh d.O.SEPH�yR+
FANDOZZIIII -�
c�.� CIVIL ti
NATURAL GAS 9 No.51667o Q
MAIN GAS 9°� �°�S��P
FLAMMABLE9/2 -�N*L .17 PM T
SHUT-OFF NO SMOKING
NO OPEN FLAME
TT IS A\70LATTON OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
MAIN GAS SHUT-OFF � NOT USED 1 NO SMOKING SIGN
SHEET NUMBER: VISIO
r
SCALE: NOT TO SCALE �JSCALE: NOT TO SCALE v SCALE: NOT TO SCALE C-6
O
i
DocuSign Envelope ID:84C40533-0974499A-9EOC-1 DC35A3FOOFF
8" PVC PLUG
TO ANTENNA COAX TO ANTENNA COAX 8" PVC PLUG CPLG. (THIRD.) �
T/FINISH GRADE T a aMobile a a a
COPPER/GALVANIZED GROUND BAR COPPER/GALVANIZED GROUND BAR
4SYLVAN WAY
0 0 0 o O O O 0 0 0 0 0 0 0 0 0 0 o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 00 PARSIPPANY,NJ 07054
0 0 0 00000000000000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
000 0 0 0 0 00000 0000000 O o 0 0 0 0 0 00 000 00 0 0 00 Q I RHms,BGRADE
' w
#2 SOLID TINNED COPPER z #2 SOLID (TEST LOOP)
CONDUCTOR TO TOWER/SHELTER Z = NOTCH SIDES OF 8" PVC SCH 40 PIPE CROWN
TWO HOLE LONG BARREL COMPRESSION LUG GROUND RING (2 TYP. FOR N TO ALLOW EXIT/ENTRANCE OF
TWO HOLE LONG BARREL BOTTOM GROUND BAR ONLY) w EXOTHERMIC WELD GROUND RING WIRE CASTLE
COMPRESSION LUG (TYP) (TYP) o
cc
NOTES: NOTES: I I—III—III— —I I—III— I I
1. DOUBLING UP "OR STACKING" OF CONNECTIONS IS NOT PERMITTED. 1. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS. TRENCH BOTTOM
2. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS. 2. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL (TOWER ONLY).
3. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL. 3. GROUND BAR SHALL BE ISOLATED FROM BUILDING OR SHELTER. !` 2/0 TINNED CU EXTERNAL
CAOWELD TEST LOOP TO TOWER GROUND RING WIRE
GROUND RING WIRE
NOTES: 5/8" 0 x 10'-0" LONG COPPER CLAD GROUND ROD
1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE
VERTICAL
2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE.
(WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D) T-MOBILE SITE NUMBER:
I 4HY0558A
ANTENNA GROUND BAR DETAIL r_—\\TOWER/SHELTER GROUND BAR DETAIL �Z�SCAINSPECTION WELL DETAIL BU #:875052
SCALE: NOT TO SCALE L SCALE: NOT TO SCALE `� LE: NOT TO SCALE ASSOCIATED ALARM
SYSTEM
1047 FALMOUTH RD
HYANNIS,MA 02601
STAINLESS STEEL BOLT
(TYP)
EXISTING 1181-0"MONOPOLE
TO TOWER MOUNTED EQUIPMENT STAINLESS STEEL
(TYP) FLAT WASHER
TO ANTENNA MONOPOLE 2—HOLE CRIMP/ (TYP
CL COMPRESSION
ANTENNA GROUND BAR CONNECTOR
LOCATED AT MCL
(BONDED TO TOWER STEEL) GROUND
STANDARD COAX BAR
CABLE GROUND KIT I I 2 HOLE LUG (TYP)
(TYP) STAINLESS STEEL
FLAT WASHER
6 AWG STRANDED Cu WIRE STAINLESS STEEL (TYP) ISSUED FOR:
WITH GREEN, 60OV, THWN I BELLVILLE WASHER STAINLESS STEEL NUT
6 WIDE METALLIC HAP REV DATE DRWN DESCRIPTION DES./Q
INSULATION (OR AS PROVIDED (TYP) (TYP) GRADE WARNING/LOCATOR TAPE AT
WITH GROUND KIT) (TYP) SINGLE CONNECTOR AT GROUND BARS 12" DEPTH A 04/06/18 JAS PRELININARY ZTK
N 0 09/28/18 JAS CONSTRUCTION AF
STAINLESS STEEL BOLT
0
k� D
CHANICAL CONNECTION
YP) STAINLESS STEEL �= z
AX GROUND BAR WITH FLAT WASHER w OM
COAX CABLE o EXOTHERMIC WELD
SULATORS, CONNECTED
(TYP FOR ALL) RECTLY TO THE BOTTOM DRAGON TOOTH WASHER MONOPOLE. SEE NOTE 1. (TYP) STEELTO BTS EQUIPMENT VIADiuTRAY OR ICE BRIDGE2/0 TINNED BARE
COPPER WIRE 2-HOLE CRIMP/
MONOPOLE PIER COMPRESSION STAINLESS STEEL GROU NO RING #2 COPPER WIRE
-
CONNECTOR FLAT WASHER SOLID, TINNED FOR CARRIER AND ICE G
GROUND WIRE (TYP) BRIDGE GROUND LOOP �B B $kdQSEPH N
1 1 SEE NOTE 3 STAINLESS STEEL O CIVIL y
(TYP)
GROUND WIRE STAINLESS STEEL NUT GROUND RING 2/0 FOR FAND0221111 --I
BELLVILLE WASHER (TYP) U
NOTE 3 TOWER GROUND LOOP
No.51667
SINGLE CONNECTOR AT STEEL OBJECTS 10 9 O Q
INSPECTION WELL EXOTHERMIC WELD (TYP) 90,E FG/STEPS
NOTES: STAINLESS STEEL ` y�
SELF-DRILLING STAINLESS STEEL 9/2 �N*L .17 PM T
1. NUMBER OF GROUNDING BARS MAY VARY DEPENDING ON THE TYPE OF TOWER, ANTENNA METAL SCREW FLAT WASHER
LOCATIONS AND CONNECTION ORIENTATION. COAXIAL CABLES EXCEEDING 200 FEET ON THE (TYP) (TYP) _ GROUND ROD COPPER
TOWER SHALL HAVE GROUND KITS AT THE MIDPOINT. PROVIDE AS REQUIRED. CLAD STEEL ROD W/MIN.
2. ONLY MECHANICAL CONNECTIONS ARE ALLOWED TO BE MADE TO CROWN CASTLE USA INC. 2—HOLE CRIMP/ 5/8 0 x 10'-0" LONG
TOWERS. ALL MECHANICAL CONNECTIONS SHALL BE TREATED WITH AN ANTI—OXIDANT COATING. COMPRESSION
CONNECTOR
3. ALL TOWER GROUNDING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE
RECOGNIZED EDITION OF ANSI/TIA 222 AND NFPA 780. DRAGON TOOTH METALLIC OBJECT NOTES:
WASHER -(TYP) 1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE
VERTICAL
SINGLE CONNECTOR AT METALLIC/STEEL OBJECTS 2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE.
(WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D)
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
ATYPICAL ANTENNA CABLE GROUNDING �- HARDWARE DETAIL FOR EXTERIOR CONNECTIONS 6 GROUND ROD DETAIL OFA L CENSED PROFESSIONAL ENGINEER,
SCA TO ALTER THIS DOCUMENT.
E: NOT 5L TO SCALE SCALE: NOT TO SCALE SCALE: NOT TO SCALE
SHEET NUMBER. VISIO
G- 1 0
DocuSign Envelope ID:84Q40533-0974-499A-9EOC-lDC35A3FOOFF Y
WIRE SIZE BURNDY LUG BOLT SIZE
I \
b6 AWG GREEN INSULATED YA6C-2TC38 3/8" - 16 NC S 2 BOLT
TYPE GY a a a a o a a
TYPE HS TYP -YA- TYP XA TYPE Y- AWG 1 E 2 2 � PE A 2 2 G SOLD TINNED YA3C-2TC38 3 8" 6 NC 5 2 BOLT T M bile a /
b2 AWG STRANDED YA2C-2TC38 3/8" - 16 INC S 2 BOLT 4 SYLVAN WAY
PARSIPPANY,NJ 07054
#2/0 AWG STRANDED YA26-2TC38 3/8" - 16 NC S 2 BOLT
b4/0 AWG STRANDED YA28-2N 1/2" - 16 NC S 2 BOLT
TYPE W TYPE VN TYPE N TYPE S TYPE GR BURNDY GROUND LUG W/
LONG BARREL HEAT SHRINK CROWN
(SEE CHART) (CLEAR) cc
CASTLE
NUT GROUNDING
CONDUCTOR LOCK -.
LOCK WASHER
# (TYP)
TYPE VS TYPE VB TYPE PT TYPE or
I!
NOTE: 4
GROUND BAR BOLT
1. ERICO EXOTHERMIC "MOLD TYPES" SHOWN HERE ARE EXAMPLES. CONSULT WITH CONSTRUCTION MANAGER FOR SPECIFIC ' (SEE CHART)
MOLDS TO BE USED FOR THIS PROJECT. (TYP)
2. MOLD TYPE ONLY TO BE USED BELOW GRADE WHEN CONNECTING GROUND RING TO GROUND ROD.
BURNDY TWO HOLE LUG W/
LONG BARREL
CADWELD GROUNDING CONNECTIONS F (SEE CHART) T-MOBILE SITE NUMBER:
/ "I ,SCA BARE WIRE TO BE 4HY0558A
NO-OX AT BOTH ENDS
LE: NOT TO SCALE //..{{
STRANDED (GREEN INSULATED)ONLY FOR #6 AWG BU#: 875052
TO ANTENNAS (SEE CHART) ASSOCIATED ALARM
Na
SYSTEM
a (TYPICALLY)
ANTENNA CABLE
12' TO 24" WEATHERPROOFING �7 T��T 1�,� 7 r 7�7 t�7�120" MAX. RX2V#6AWGO
KIT 104/ 1'n�,1V O TH RD
(Ty')
WEATHERPROOFING
HYANNIS,MA 02601
GROUND KIT 1. ALL GROUNDING LUGS ARE TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. _
COAX JUMPER (TYP.) (TYP) ALL HARDWARE BOLTS, NUTS, BE
WASHERS SHALL BE STAINLESS STEEL. ALL
HARDWARE ARE TO BE AS FOLLOWS: BOLT, FLAT WASHER,GROUND BAR, GROUND LUG,
WEATHERPROOFING KIT (SEE FLAT WASHER AND NUT. EXISTING 1181-011 MONOPOLE
NOTE 3)
WEATHERPROOFING
CONNECTOR
r--�MECHANICAL LUG CONNECTION
CABLE GROUND KIT (TYP. SEE NOTE 2) L SCALE: NOT TO SCALE
COPPER/GALVANIZED
COAX GROUND BAR
#6 AWG STRANDED COPPER GROUND WIRE BONDED DIRECTLY TOWER
(GROUNDED TO GROUND BAR). SEE NOTE 1 & 2
CABLE CONNECTOR #6 AWG MIN. FROM ANTENNA
ANTENNA CABLE CABLE GROUND KIT
TO BTS EQUIPMENT (TYP.) A ISSUED FOR:
NOTES:
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND REV DATE DRWN DESCRIPTION DFS./Qll
WIRE DOWN TO GROUND BAR. NOTES: - A 04/0G/18 pis PREL UNARY ZTK
2. GROUNDING KIT SHALL BE TYPE AND PART NUMBER AS SUPPLIED OR RECOMMENDED BY CABLE MANUFACTURER. 1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND 0 09/28/18 JAS CONSTRUCTION AF
WIRE DOWN TO ANTENNA GROUND BAR. GROUND BAR ON SHELTER. ICE
3. WEATHER PROOFING SHALL BE TWO-PART TAPE KIT, COLD SHRINK SHALL NOT BRIDGE, OR ON ANTENNA TOWER
BE USED. 2. WEATHER PROOFING SHALL BE TWO-PART TAPE KIT. COLD SHRINK SHALL NOT BE
USED.
CABLE GROUND KIT CONNECTION O On O Oo 0 o Oo Oo
3 SCALE: NOT TO SCALE
GROUND CABLE CONNECTION I � 0���° � �� � 0 0O
4 SCALE: NOT TO SCALE oeu �` OF MASS
'TWO HOLE LUG, OR GROUNDING SHALL BE qC
3/8-11x1'TAMPER EXOTHERMIC WELD TO BE USED ELIMINATED WHEN GROUND BAR y
RESISTANT BOLT WITH #2 AWG BARE CONDUCTOR IS ELECTRICALLY BONDED TO � 6 I$�4SEPII G
(TYP) WIRE TO BUILDING SERVICE METAL TOWER N
FANOOZZIIII -4
INSULATORS GROUND OR GROUND RING � O -I
SEE NOTE 2. V CIVIL y
(TYP) No.51667
WALL BRACKET
0 00 GROUNDWIRE INSTALLATION 10 9FG PLO ti,Q
(ttP) 0 0 NOTE: MINIMUM OF - S/S NUT SCALE: NOT TO SCALE �'° �ST6
0 0 0 3 THREADS TO BE (TYp) 9/2 ®N*L .17 PM T
VISIBLE I{
O O O (TYP)
0 S/S SPLIT,
0
O 0 2 HOLE LONG WASHER I
0 0 BARREL TINNED (TYP) //2 TINNED SOLID IN 3/4" UOWp TIGHT - PIPE
UNIVERSAL COPPER SOLID COPPER ` CONDUIT FROM 24" BELOW GRADE TO
O GROUND BAR (4"x20") LUG S/S FLAT WITHIN 3" TO 6" OF CAD-WELD
I TERMINATION POINT. EXPOSED END OF
LOCK WASHER ® (TYP) WASHER. THE LIQUID TIGHT CONDUIT MUST.BE
P/N M10 (TYP) - SEALED WITH SILICONE CAULK. AIR
(T
YP) TWO-HOLECADWELD
COMPRESSION LUG TIN COATED SOLID fNOTES: COPPER BUS BAR S/S FLAT (TYP)WASHER
1. DOWN LEAD (HOME RUN) CONDUCTORS ARE�I TO BE INSTALLED ON CROWN CASTLE CHERRY INSULATOR - (TYP) IT 1SA VIOLATION OF LA�X%FOR ANYPERSON,
USA INC. TOWER, PER THE GROUNDING DOWN CONDUCTOR POLICY OAS-STD-10091. NO INSTALLED IF REQUIRED UNLESS THEY ARE ACTING UNDER THE DIRECTION
MODIFICATION OR DRILLING TO TOWER STEEL IS ALLOWED IN ANY FORM OR FASHION, S/S BOLT �� TIE INTO EXISTING GROUND RING OF A LICENSED PROFESSIONAL ENGINEER,
CAD-WELDING ON THE TOWER AND/OR IN THE AIR ARE NOT PERMITTED. - -.TYP
( )
TO ALTER T HIS DOCUbffiNT
2. OMIT INSULATOR WHEN MOUNTING TO TOWER STEEL OR PLATFORM STEEL ._
USE INSULATORS WHEN ATTACHING TO BUILDING OR SHELTERS.
SHEET NUMBER: VISIO
GROUND BAR DETAIL LUG DETAIL 1 TRANSITION GROUND DETAIL
6 � G ,2 .-78SCALE: NOT TO SCALE SCALE: NOT TO SCALE SCALE: NOT TO SCALE0